Академический Документы
Профессиональный Документы
Культура Документы
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 12, December 2014)
VPRE (24)
I 0 PQ =C02 I 0F =C02
ZΣ +3R F
VPRE (26)
I0MP =C03 I 0F =C03
ZΣ +3R F
519
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 12, December 2014)
VAM
Z APP = (27)
I AM +K 0L I 0F
Z +3R F
I1LdZ1L +3R F +2C11C12dZ1L +C01C02dZ0L (30)
ZAPP = VPRE
Z +3R F
I PRE +2C11C12C13 +C01C02C03 (1+K 0L )
VPRE
It can be seen from equation (30) that the fault resistance
is not only the factor causing the measured impedance
deviation, but also the line capacitance. The ZAPP is also
dependent on power system conditions and line length
520
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 12, December 2014)
Table .B Table C:
Line parameters Percentage error in R, X and ZAPP in transmission line at 95 %
distance with h=0.96, δ=160
Line R L C
RF Without With % error in % error in % error in
parameters (Ω/Km) (mH/ (µF/ Reactance
Km) Km (Ω ) Capacitance Capacitance Resistance Impedance
)
0 8.71 +j90.55 9.62 9.45 4.92 4.9
Positive and 0.0301 1.0 0
negativesequenc .011 +j95.24
e impedance 2
200 361.35 +j60.84 374.54+ 3.52 3018.8 16.11
Zero 0.2269 2.2 0
sequence .009 j1.951
impedance 4
The distance relay tripping characteristic at h=0.96 and Fig.6 shows the amount of increase in the measured
load angle is 160 shown in Fig.5,(I) first boundary line is impedance for the various fault points, in the case of zero
for zero fault resistance and fault location varies from relay fault resistance. Here, the increase in the measured
point to reach point (II) in the second boundary-line, the resistance, reactance, and impedance magnitude are shown
fault is at reach point with fault resistance varying from 0 by dotted, dashed, and full curves, respectively. It can be
to 200 Ohm (III) third one refers to fault resistance of 200 seen that the impedance deviation is a function of fault
Ohm with fault position varying from relay to reach point location. Because of different deviation of the measured
and (IV) fourth line is for relay location with fault resistance and reactance, the angle of the measured
resistance varying from zero to 200 Ohm. impedance varies as well as its magnitude.
The characteristic without considering the line
capacitance is also in the dotted form for comparison. In
the Fig.5 the other important thing observed in this plot is
that there is significant difference in trip characteristic
while considering line capacitance.
Z APPC Z APP
Error % 100
Z APPC
(31) Fig.7. Tripping characteristic variations with changes in power
system conditions
521
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 12, December 2014)
In Fig.7, curve (1) is the tripping characteristic of Fig.5.
When the load angle increases from160 to 220 and the
voltage ratio decreases from 0.96 to 0.94, curve (2) would
be resulted. On the other hand, when load decreases, curve
(3) is resulted for δ = 100 and h = 0.98.
A. Load Angle Variation Fig.11. Increase in measured resistance, reactance, and impedance
magnitude as load angle changes.
Once the load level of a transmission line increases, the
load angle also increases, and vice versa. If power flow B. Voltage Ratio Variation
direction in a transmission line reversed, the sign of load Variation of the voltage ratio of transmission line affects
angle is inversed. Fig.10 shows the effect of the load angle the reactive power flow through the line. The amount of
variation on the tripping characteristic. Here, load angle reactive power flowing through the line increases as this
takes the values 250, 150, 50, -50, -150 and -250. factor decreases (for ratios lower than 1).
522
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 12, December 2014)
If the ratio is higher than 1, it means that the reactive
power flow direction is inversed. Fig.12 shows the impact
of voltage ratio, the magnitudes of 0.95, 1.00 and 1.05 are
considered for this factor, while the other parameters are
the same as Fig. 5.
Fig 13 .Increase in measured resistance, reactance, and impedance VII. ADAPTIVE DISTANCE RELAY SETTING
magnitude.
A. Effect Of Z1SN & Z0SN Trip Boundary
Fig.13 shows the amount of increase in the measured From the equation. (31), it is clear that the change in trip
resistance, reactance, and impedance magnitude for voltage boundary is due to VPRE, IPRE. Further the VPRE, IPRE,
ratios of 0.95, 1.00, and 1.05. are function of factors δ, h, Z1L etc. The variation of
apparent impedance with change in Z1SN with zero fault
C. Line Length Variation
resistance is given in table D .
Fig.14 shows the tripping characteristic for the line
lengths of 100,200,300, and 400 km. It can be that as the Z1SN Apparent Impedance
line length increases, the covered region by tripping
characteristic also increases in both resistance and 5850 95.7984.2200
reactance axis. Fig.15 shows the amount of increase in the
measured resistance, reactance, and impedance magnitude
for the mentioned line lengths. 2.5850 95.7884.2240
523
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 12, December 2014)
From table D, it is observed that the effect of remote
source impedance on apparent impedance is quite
negligible.
524
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 4, Issue 12, December 2014)
[8] S. Jamali ,H. Shateri, “Measured Impedance by Distance Relay [10] Dash, P. K. Pradhan, A. K. Panda, G. and Liew, A. C.“Adaptive
Considering Double Model of the Line Capacitance”, 2006 relay setting for flexible AC transmission systems (FACTS)”, in
International Conference on Power System Technology. Proc. IEEE Power Eng.
[9] Dash, P. K. Pradhan, A. K. Panda, G. and Liew, A. C.“Digital
protection of power transmission lines in the presence of series
connected FACTS devices”, IEEE Trans. Power Delivery, 15(1): 38-
43 (2000).
525