Академический Документы
Профессиональный Документы
Культура Документы
Features
• Four 24 V (ac) powered zone outputs
Zone 1
Zone 2
Power
tN2
• For use with tekmarNet®2 Thermostats
End Switch
Zone 3
Zone 4 Input Power:
24 V (ac) ±10%
100 VA max 60 Hz
• tN4 expansion terminals
Class 2
Control Load
End Switch:
Zone Outp
: 10VA
24 V (ac) 2
ut: 2 A (48V A
A) per zone
4 A (96VA)
• Isolated end switch
max total
tN2 Wirin
Four Zon g Center
313
Made in Can
tektra 1034
ada
-01
• External diagnostic LEDs
e Valves
Benefits
• Simple, convenient wiring location
• Compact enclosure for flexible installation
tN2 tN2
Zone 1
tN2 tN2
Zone 2
tN2 tN2
Zone 3
tN2 tN2
• Reduce equipment cycling through the use of
tekmarNet®2 Thermostats
Zone 4 H8003A
Zone 1 For use with
Use at least 167°F (75°C) conductors
±10% 60 Hz
Control Load 100 VA Max, Class
: 2
End Switch: 10 VA
Zone Outp 24 V (ac) 2 A
ut: 2 A (48
VA) per zone
4 A (96 VA)
X R C
max total
Made in Can
ada
tN2 Wirin tektra 1034
Four Zon g Cente -01
e Val r 313
ves
Zone 1
Zone 2
C Vlv Zone 3
C Vlv Zone 4
Note
C Vlv
C Vlv Vlv
Table of Contents
Control Location .............................................................2 Sequence of Operation...................................................3
Mounting the Control .....................................................2 Application Drawings ...................................................4-5
Sizing the Transformer ...................................................2 Troubleshooting Guide.................................................6-7
Wiring the Control ...........................................................3 Technical Data ................................................................8
Control Location
When choosing the location for the control, consider the • Provide adequate ventilation.
following: • Keep away from equipment, appliances or other sources
• Keep dry. Avoid potential leakage onto the control. of electrical interference.
RH 90 % in a non-condensing environment. • Locate the control near the zone valves and thermostats.
• Do not expose to temperatures beyond 32 to 122°F
(0 to 50°C).
Zone 1 2 3 4
Thermostat
Load Transformer
Zone Valve Control must exceed:
Load Load (VA)
Total Zone Load + + + + 3 VA
Sequence of Operation
• When a thermostat calls for heat, it sends a message Synchronized End Switch
to the Wiring Center and the corresponding zone LED
turns on. Power is then supplied to the appropriate zone tekmarNet®2 thermostats provide the Wiring Center with
output as indicated by the LED. a synchronized end switch feature. This ‘synchronizes’
the start times of zones and reduces short cycling of
• The end switch relay (‘XX’) closes and the end switch
equipment connected to the Wiring Center’s end switch.
LED turns on. The switch remains closed as long as any
The net effect is increased system efficiency and reduced
zone is calling for heat. This can provide a boiler demand
wear on equipment.
to a reset control such as a tekmar Boiler Control 260.
• If the Wiring Center is connected to a tN4 bus, all
communication messages will pass through the 313’s
tN4 expansion connection. tN4 messages are required
in order to create a boiler demand on a device such as
a tekmar Boiler Reset Module 420.
Electrical Drawings
The electrical drawing examples on the following pages determine the necessary components for and configuration
show the 313 in common applications. These drawings of the particular system being designed including additional
have a brief explanation of what is being operated in each equipment isolation relays (for loads greater than the
system. Choose the components in your system and use controls specified output ratings) and any safety devices
the drawings as a guide to aid in wiring your system. which in the judgement of the designer are appropriate in
These are only concept drawings, not engineered drawings. order to properly size, configure and design that system
They are not intended to describe a complete system nor and to ensure compliance with building and safety code
any particular system. It is up to the system designer to requirements.
tNt tNt
tNt tNt
External
tN4
C
Connection tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 H8003A
Use at least 167°F (75°C) conductors
Made in Canada
T tektra 1034-01
T
tN2 Wiring Center 313
Four Zone Valves
Zone 1 Zone 2 Zone 3 Zone 4
C Vlv C Vlv C Vlv C Vlv Vlv
es
Fu
R
L
N
C
Transformer 24 V (ac)
See “Transformer Sizing” on Page 2 Refer to Transformer Data Sheets for Maximum Allowable Loads
tNt tNt
260
Outdoor 313 provides ‘boiler
Sensor demand’ to the 260
313
through the Wiring
Center’s end switch
Made in Canada
tektra 1034-01
R
L
N C
tekmar 009
Transformer 24 V (ac)
Valve Valve Valve Valve
See “Transformer Sizing” on Page 2
General
1. Remove the front cover from the control. 4. If the transformer is being powered with line voltage and
2. Use an electrical test meter to measure (ac) voltage the power LED is not lit:
between the input power R and C terminals. The reading • If using the tekmar Transformer 009 check the field
should be 24 V (ac) + / – 10% and the power LED should replaceable transformer fuse in line with the 24 V (ac)
be lit green. output of the 009.
3. If power is not present and the light is off: • If the fuse is blown, determine the cause of the failure
before replacing the fuse.
• Check the circuit that supplies power to the tN2 Wiring
Center. • If a transformer other than the tekmar 009 is used then
a fuse may not be present. Verify that the transformer is
being fed the proper voltage. If the input voltage is correct,
and there is no output voltage, then the transformer is
likely damaged and should be replaced. Find the cause
of the overload before replacing the transformer. Ensure
transformer is sized for the entire load (See “Transformer
Sizing” on Page 2).
tekmarNet®2 Thermostats 4. Go back to the original end of the wires and, using a
To test the tekmarNet®2 Thermostats, check the wires for wire nut, cap each tN2 wire individually so that these
continuity and shorts. ends cannot touch another conductor.
1. Disconnect the two tN2 wires at one end and twist them 5. Go to the other end of the wires and again, test for shorts.
together. Resistance should be infinite, or O.L. and there should
be no tone. If tone exists or less than 50 000 ohms is
2. Go to the other end of the wires and disconnect them.
found, then the wires are not insulated from one another.
3. Using an electrical test meter, check for continuity. This is generating a short on the wires connecting the
Resistance should read 0 ohms, or continuity should thermostats to the 313.
produce a tone. If not, this indicates that there are
6. Replace the damaged wires, test, and reconnect them
damaged wires connecting the thermostat to the 313.
to their proper terminals.
Repair or replace them as necessary.
1. Use an electrical test meter to measure the (ac) voltage Note: If power to the zone valve is present but the zone
between the C and the Vlv terminals for each zone valve does not operate properly, refer to any troubleshooting
valve output. information supplied by the zone valve manufacturer.
• When the Zone light is off, the reading should be 0 V (ac)
and the valve should be closed.
• When the Zone light is on, the reading should be 24 V
(ac) + / – 10% and the valve should be open.
To test the tN4 Network, check the wires for continuity 4. Go back to the original end of the wires and, using a
and shorts. wire nut, cap each expansion wire individually so that
1. Disconnect the two tN4 expansion wires (tN4 and C) at these ends cannot touch another conductor.
one end and twist them together. 5. Go to the other end of the wires and again, test for shorts.
2. Go to the other end of the wires and disconnect them. Resistance should be infinite, or O.L. and there should
be no tone. If tone exists or less than 50 000 ohms is
3. Using an electrical test meter, check for continuity. found, then the wires are not insulated from one another.
Resistance should read 0 ohms, or continuity should This is generating a short on the wires connecting the
produce a tone. If not, this indicates that there are tN4 control to the 313.
damaged wires connecting the tN4 control to the 313.
Repair or replace them as necessary. 6. Replace the damaged wires, test, and reconnect them
to their proper terminals.
If the tN4 expansion terminals are not used to connect 2. Use an electrical test meter to measure continuity across
the tN2 Wiring Center to the system, the end switch may the XX end switch terminals on the 313.
be used. • When the end switch LED is off, no continuity should be
1. Remove the wires from the end switch terminals. present (no tone).
• When the end switch LED is on, continuity should be
present (tone).
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely, this Class
B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations.
However, if this control does cause harmful interference to radio or television reception, which is determined by turning the control off and on, the user
is encouraged to try to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control,
and/or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
The liability of tekmar under the Limited Warranty shall be limited to, at THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS
tekmar’s sole discretion: the cost of parts and labor provided by tekmar OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO
to repair defects in materials and / or workmanship of the defective prod- CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION,
uct; or to the exchange of the defective product for a warranty replace- IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
ment product; or to the granting of credit limited to the original cost of the A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE
defective product, and such repair, exchange or credit shall be the sole PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS
remedy available from tekmar, and, without limiting the foregoing in any OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLA-
way, tekmar is not responsible, in contract, tort or strict product liabil- TION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY
ity, for any other losses, costs, expenses, inconveniences, or damages, LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY
whether direct, indirect, special, secondary, incidental or consequential, CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL
arising from ownership or use of the product, or from defects in work- NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE
manship or materials, including any liability for fundamental breach of PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS
contract. ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to
The pass-through Limited Warranty applies only to those defective Prod- have defects in workmanship or materials must be returned, together
ucts returned to tekmar during the warranty period. This Limited War- with a written description of the defect, to the tekmar Representative
ranty does not cover the cost of the parts or labor to remove or transport assigned to the territory in which such Product is located. If tekmar
the defective Product, or to reinstall the repaired or replacement Product, receives an inquiry from someone other than a tekmar Representative,
all such costs and expenses being subject to Purchaser’s agreement and including an inquiry from Purchaser (if not a tekmar Representative) or
warranty with its customers. Purchaser’s customers, regarding a potential warranty claim, tekmar’s
sole obligation shall be to provide the address and other contact informa-
tion regarding the appropriate Representative.
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com
Product design, software and literature are Copyright © 2009 by: All specifications are subject to change without notice.
tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
8 of 8 Printed in Canada. D 313 - 10/09.