Вы находитесь на странице: 1из 19

Project: Development of South Shamkha ETAP Page: 1

Location: LOT-3 12.6.0C Date: 03-11-2015


Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: LF02A RELAY


MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SJ62 Phase: 600/1 22.000 14.34 3 ph, Sym. (Calc.)
2.73 LG, Sym. (Calc.)
GND: 600/1 22.000 2.73 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Normal Inverse
Pickup (Tap) 0.1 - 2 Sec - 1A 0.800
Time Dial 0.130
Ground TOC IEC - Normal Inverse
Pickup (Tap) 0.05 - 4 Sec - 1A 0.200
Time Dial 0.130

OCR: LF02B RELAY


MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SJ62 Phase: 600/1 22.000 23.52 3 ph, Asym. (Calc.)
2.73 LG, Asym. (Calc.)
GND: 600/1 22.000 2.73 LG, Asym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Normal Inverse
Pickup (Tap) 0.1 - 2 Sec - 1A 0.800
Time Dial 0.130
Ground TOC IEC - Normal Inverse
Pickup (Tap) 0.05 - 4 Sec - 1A 0.200
Time Dial 0.130

OCR: SHS0108 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.98 3 ph, Sym. (Calc.)
36.93 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.93 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 2
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS0108 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 9.23 3 ph, Sym. (Calc.)
2.44 LG, Sym. (Calc.)
GND: 100/1 22.000 2.44 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS0109 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.91 3 ph, Sym. (Calc.)
36.87 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.87 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 3
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS0109 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 8.97 3 ph, Sym. (Calc.)
2.36 LG, Sym. (Calc.)
GND: 100/1 22.000 2.36 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS0401 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.84 3 ph, Sym. (Calc.)
36.83 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.83 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 4
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS0401 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 8.76 3 ph, Sym. (Calc.)
2.31 LG, Sym. (Calc.)
GND: 100/1 22.000 2.31 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS0402 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.77 3 ph, Sym. (Calc.)
36.78 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.78 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 5
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS0402 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 8.55 3 ph, Sym. (Calc.)
2.28 LG, Sym. (Calc.)
GND: 100/1 22.000 2.28 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS0403 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 36.10 3 ph, Sym. (Calc.)
37.01 LG, Sym. (Calc.)
GND: 2000/1 0.415 37.01 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 6
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS0403 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 9.63 3 ph, Sym. (Calc.)
2.46 LG, Sym. (Calc.)
GND: 100/1 22.000 2.46 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS0404 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 36.00 3 ph, Sym. (Calc.)
36.94 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.94 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 7
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS0404 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 9.26 3 ph, Sym. (Calc.)
2.42 LG, Sym. (Calc.)
GND: 100/1 22.000 2.42 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS0405 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.68 3 ph, Sym. (Calc.)
36.72 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.72 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 8
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS0405 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 8.28 3 ph, Sym. (Calc.)
2.26 LG, Sym. (Calc.)
GND: 100/1 22.000 2.26 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS0406 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.64 3 ph, Sym. (Calc.)
36.69 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.69 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 9
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS0406 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 8.17 3 ph, Sym. (Calc.)
2.26 LG, Sym. (Calc.)
GND: 100/1 22.000 2.26 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS1001 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.67 3 ph, Sym. (Calc.)
36.71 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.71 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 10
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS1001 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 8.23 3 ph, Sym. (Calc.)
2.32 LG, Sym. (Calc.)
GND: 100/1 22.000 2.32 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS1002 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.69 3 ph, Sym. (Calc.)
36.73 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.73 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 11
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS1002 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 8.28 3 ph, Sym. (Calc.)
2.33 LG, Sym. (Calc.)
GND: 100/1 22.000 2.33 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS1003 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.63 3 ph, Sym. (Calc.)
36.68 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.68 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 12
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS1003 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 8.10 3 ph, Sym. (Calc.)
2.31 LG, Sym. (Calc.)
GND: 100/1 22.000 2.31 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS1004 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.59 3 ph, Sym. (Calc.)
36.66 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.66 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 13
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS1004 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 8.01 3 ph, Sym. (Calc.)
2.30 LG, Sym. (Calc.)
GND: 100/1 22.000 2.30 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS1006 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.49 3 ph, Sym. (Calc.)
36.58 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.58 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 14
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS1006 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 7.73 3 ph, Sym. (Calc.)
2.26 LG, Sym. (Calc.)
GND: 100/1 22.000 2.26 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS1009 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.50 3 ph, Sym. (Calc.)
36.59 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.59 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 15
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS1009 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 7.75 3 ph, Sym. (Calc.)
2.26 LG, Sym. (Calc.)
GND: 100/1 22.000 2.26 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS1011 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.55 3 ph, Sym. (Calc.)
36.63 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.63 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 16
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS1011 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 7.89 3 ph, Sym. (Calc.)
2.28 LG, Sym. (Calc.)
GND: 100/1 22.000 2.28 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OCR: SHS1012 SBEF


MFR: ABB Tag #: CT Base kV If (kA)
Model: SPAJ 140C(SPCJ 4D29) Phase: 2000/1 0.415 35.51 3 ph, Sym. (Calc.)
36.60 LG, Sym. (Calc.)
GND: 2000/1 0.415 36.60 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC IEC - Extremely Inverse
Pickup (Tap) 0.5 - 2.5 xCT Sec 0.600
Time Dial 0.700
Project: Development of South Shamkha ETAP Page: 17
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

OCR: SHS1012 TR RELAY


MFR: ABB Tag #: CT Base kV If (kA)
Model: REX 521 Phase: 100/1 22.000 7.79 3 ph, Sym. (Calc.)
2.27 LG, Sym. (Calc.)
GND: 100/1 22.000 2.27 LG, Sym. (Calc.)

OC Level: OC1
Range Setting
Phase TOC Normal Inverse
Pickup (Tap) 0.05 - 40 xCT Sec 0.580
Time Dial 0.400
Phase INST Pickup 0.05 - 40 xCT Sec 8.500
Time Delay 0.05 - 300 Sec 0.050

Ground TOC Normal Inverse


Pickup (Tap) 1 - 500 xCT Sec 20.000
Time Dial 0.050
Ground INST Pickup 0.1 - 12 xCT Sec 4.000
Time Delay 0.05 - 300 Sec 0.050

OLR: LF02A RELAY


MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SJ62 Phase: 600/1 22.000 14.34 3 ph, Sym. (Calc.)
2.73 LG, Sym. (Calc.)
GND: 600/1 22.000 2.73 LG, Sym. (Calc.)

OLR: LF02B RELAY


MFR: Siemens Tag #: CT Base kV If (kA)
Model: 7SJ62 Phase: 600/1 22.000 23.52 3 ph, Asym. (Calc.)
2.73 LG, Asym. (Calc.)
GND: 600/1 22.000 2.73 LG, Asym. (Calc.)

Fuse: Fuse1
MFR: Bussmann Tag #: 3-Phase kA: 46.58 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.92 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse10
MFR: Bussmann Tag #: 3-Phase kA: 45.51 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.16 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000
Project: Development of South Shamkha ETAP Page: 18
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

Fuse: Fuse11
MFR: Bussmann Tag #: 3-Phase kA: 45.59 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.22 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse12
MFR: Bussmann Tag #: 3-Phase kA: 45.66 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.27 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse13
MFR: Bussmann Tag #: 3-Phase kA: 45.76 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.34 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse14
MFR: Bussmann Tag #: 3-Phase kA: 45.80 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.36 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse15
MFR: Bussmann Tag #: 3-Phase kA: 46.45 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.83 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse16
MFR: Bussmann Tag #: 3-Phase kA: 46.67 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.99 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse2
MFR: Bussmann Tag #: 3-Phase kA: 46.40 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.80 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse3
MFR: Bussmann Tag #: 3-Phase kA: 46.31 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.73 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000
Project: Development of South Shamkha ETAP Page: 19
Location: LOT-3 12.6.0C Date: 03-11-2015
Contract: Revision: Base
Engineer: SENTHIL
Filename: LF02 Protective Device Settings

Fuse: Fuse4
MFR: Bussmann Tag #: 3-Phase kA: 46.15 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.62 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse5
MFR: Bussmann Tag #: 3-Phase kA: 45.93 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.46 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse6
MFR: Bussmann Tag #: 3-Phase kA: 45.84 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.40 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse7
MFR: Bussmann Tag #: 3-Phase kA: 45.39 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.07 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse8
MFR: Bussmann Tag #: 3-Phase kA: 45.40 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.08 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Fuse: Fuse9
MFR: Bussmann Tag #: 3-Phase kA: 45.43 Asym. (Calc.)
Model: NH (Size 02 & 2) kV: 0.500 LG kA: 47.10 Asym. (Calc.)
Speed: Other Breaking kA: 120.000 Base kV: 0.415 (Calc.)
Size: 400 Cont. Amp: 400.000

Вам также может понравиться