Вы находитесь на странице: 1из 1

Amps X 10 Bus32 (Nom. kV=22, Plot Ref.

kV=22)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

T17 LF02B RELAY - P


500 500
FLA OC1
Siemens
300 300
7SJ62
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 0.8 (0.1 - 2 Sec - 1A)
100 Time Dial = 0.13 100
3x = 0.819 s, 5x = 0.556 s, 8x = 0.429 s

50 50

30 30

10 10
T17
SHS0404 TR RELAY - P 1500 kVA (Secondary) 5.83 %Z
5 Delta-Wye Solid Grd 5
OC1

Seconds
Seconds

ABB
3 REX 521 3

CT Ratio 100:1
Normal Inverse
Pickup = 0.58 (0.05 - 40 xCT Sec)
Time Dial = 0.4
1 1
3x = 2.52 s, 5x = 1.71 s, 8x = 1.32 s
Inst = 8.5 (0.05 - 40 xCT Sec)
Time Delay = 0.05 s
.5 .5

.3 R LF02B RELAY .3

.1 T17 .1

Inrush
.05 .05

I>

.03 SHS0404 TR RELAY LF02B RELAY - 3P .03

T17
1500 kVA SHS0404 TR RELAY - 3P
Dyn11
5.83 %Z
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 Bus32 (Nom. kV=22, Plot Ref. kV=22) ETAP Star 12.6.0C

SHS0404-LF02B

Project: Development of South Shamkha Date: 03-11-2015


Location: LOT-3 SN: SPACEAGE-1
Contract: Rev: Base
Engineer: SENTHIL Fault: Phase

Вам также может понравиться