190 bar 260 bar 262 bar 270 bar 325 bar
530 / 530 ºC 540 / 580 ºC 600 / 600 ºC 600 / 610 ºC 610 / 630 / 630 ºC
350 bar
700 / 720 ºC
1) Gross efficiency achievable with this technology – offered
304
Installed capacity
~ 50% ~ 85 GW
233
in 2014 ! 193
186
172
139
101
94 25
25
20 6
45
61 18 43
40
10 38 60
Hydro Wind onshore Wind offshore 3 44
25 18 29
Solar Bio Mass Biomass fraction of waste 2014
Mar-01 Mar-11 Jan-14 Jul-16 Oct-17
30+ Products
Time
Power on Minimum
Grid Services Maintenance Flexibility
Demand Part Load
• ST Stress Controller • Advanced Fast Loading • HP Turbine with Last MS-Valve • Fast Preservation
• SPP Hot Start On The Fly • Primary Frequency Response • Partial Bypass Concept • Fast Cooling
• HP internal bypass cooling • Condensate throttling • Part Load Optimization Package • ST Hot Standby
• Advanced Fast Loading • Dispatch Control • Minimum Load Reduction • FMS
• ST EOH Counter 4.0 • Maximum Load Plus • Top Feedwater Heater
• Low Loss Start
• Fast Start / Hot Start
Restricted © Siemens AG 2017
Page 8 01.12.2017 Sandeep Chittora Power Generation Services
Power on Demand
Reduction of Wall Thickness to Improve Start Up & Cycling Capabilities
100
Example: Reduced Casing thickness & reduced thermal
piston loading by HP bypass cooling 80
Design with
internal bypass
Significant improvement in LCF cooling
Load in %
60
Interstage Design without
admission cooling internal bypass
steam main steam 40 cooling
mixed steam
20
0
Time
Task
• Part load may lead to steam temperature changes,
especially hot reheat temperature
• Thermal stresses during operation are not considered in
IV. Generation
standard counting of equivalent operating hours (EOH EOH counting also
counter) considering load changes
• Maintenance needs may not be recognized
Solution
• Evaluation of operational history
• Implementation of a state of the art EOH counter considering III. Generation
load changes EOH consumption is a function
of actual thermal stress
II. Generation
Introduction of three start-up modes
Benefits with fixed EOH consumption
• More accurate EOH counting I. Generation
• Improved outage planning Maintenance interval defined by
operating hours and number of starts
• Enhanced operational flexibility
1 Power
2 HP IP LP LP G
5
control station
1 2 3 4 5
LP Feed Water
Feed Water Heaters 1 Throttling 4 HP heater
Pumps 2 Additional valve 5 Fuel increase
4 3 Condensate throttling
1
a. Remove throttling of control valves
2 HP IP LP LP b. Opening of last main steam valve
Power
1 2
Time
Condenser
Enlarged Condenser
Fast control Hotwell
Butterfly Valves
Condensate
Pumps
Enlarged Feed 3
Water Tank Fast Condensate
Control Station
LP Feed Water
Heaters
Power
Old minimum
Solution sustainable load
• Use of robust state space controller for unit control
• Adaptation, optimization and setting of lower-level controls for
new minimum load level
• Adaptation or addition of control sequences, burner and mill
scheduler
NEW, minimum
• Provision of additional instrumentation where necessary Savings sustainable load
Time
Benefits
• Reduced financial losses during off-peak periods
• Faster response to increased load demands as unit does not
need to be shut down The Minimum Load Reduction solution results in savings for minimum load operation through
optimization of lower-level controls.
• Avoidance of unnecessary startups and shutdowns
T
Top Heater
Load
Old minimum
sustainable load
NEW, minimum
sustainable load
Time
RWE Neurath
Europe’s 2nd biggest
lignite fired coal
power Plant
ED (4’400 MW)
starting contract proven further possible
situation (trial run) potential
CB
A
Load gradient 5 MW/min 12 MW/min 15 MW/min 20 MW/min
270 MW 250 MW
Minimum load
440 MW 290 MW (w/o bypass (with risks, e.g.
(gross)
operation) minimum fire interlock)
■ 2 x 600 MW units, lignite fired
Primary frequency 18 MW by 18 MW by
45 MW 50 MW
■ Built 1975 control (PFC) throttling of inlet valves condensate throttling
Secondary
■ Originally designed and run
frequency control n.a. 66 (75) MW 100 MW 110-115 MW
as base-load plants (SFC)
Simultaneous PFC 18 MW 18 MW
n.a. still under investigation
and SFC 66 (75) MW 75 MW
Sandeep Chittora
Advisory Expert – Steam Turbine Performance
Siemens Limited, India
siemens.com