1. Electrical, physical, and insulation tests were conducted on randomly selected 220kV cable drums to check compliance with specifications.
2. The cable passed all electrical tests including resistance, partial discharge, voltage withstand, and screening tests.
3. Physical dimension tests confirmed cable dimensions were within specifications including conductor diameter, insulation thickness, and sheath thickness.
4. Insulation and sheath materials exceeded tensile strength and elongation requirements prior to aging.
1. Electrical, physical, and insulation tests were conducted on randomly selected 220kV cable drums to check compliance with specifications.
2. The cable passed all electrical tests including resistance, partial discharge, voltage withstand, and screening tests.
3. Physical dimension tests confirmed cable dimensions were within specifications including conductor diameter, insulation thickness, and sheath thickness.
4. Insulation and sheath materials exceeded tensile strength and elongation requirements prior to aging.
1. Electrical, physical, and insulation tests were conducted on randomly selected 220kV cable drums to check compliance with specifications.
2. The cable passed all electrical tests including resistance, partial discharge, voltage withstand, and screening tests.
3. Physical dimension tests confirmed cable dimensions were within specifications including conductor diameter, insulation thickness, and sheath thickness.
4. Insulation and sheath materials exceeded tensile strength and elongation requirements prior to aging.
220 KV Cable Inspection Learning points at KEI Industries, Chopanki
Cable Details {127/220 (245) KV, 1 C X 1000 Sqmm}:
It is comprising of stranded Miliken overall compact circular plain copper
conductor, Nonconductive water blocking in each stranding layer longitudinally of conductor except outer layer, Semiconducting water Swellable tape over each segment and over final layer of central conductor. Screened by a layer of extruded semiconducting compound, XLPE insulated (Dry Cure) screened by an extruded semiconducting compound with semiconducting water swellable tape. Copper wires Metallic screen and copper tape in open helix, Semi conducting water swellable tape, Lead alloy “E” Sheathed, Anti corrosive layer with bedding tape, Non conducting water swellable tape Extruded HDPE (ST-7) (Anti Rodent & Termite) outer sheathed with Extruded semiconducting layer.
Test were conducted on randomly selected drums as per approved QAP/GTP
and IEC -62067.
Following test were conducted on selected drum:
1. Electrical Tests 2. Physical Dimension 3. Insulation Test 4. Test on HDPE (ST-7) Outer Sheath Black 1. Electrical Tests on Full Drum Length: S. Test Descriptions Unit Specified Observed No. Value Value 1 Electrical Resistance of conductor at 20 Ohm 0.176 (Max) 0.0172 deg. C /km 2 Partial Discharge (at 1.50 Uo Test pC 5 max 1.90 voltage i.e. 190 KV) 3 Capacitance measurement at ambient µf/Km 0.204 + 8 % 0.184 Temp (Max) 4 Power frequency voltage withstand test KV 318 KV for 30 Withstood at Room Temp minutes 5 Electrical Test on Non-metallic overall KV To withstand withstood sheath with conductive layer over /Minute 25 Kv DC for 1 minute sheath 6 Metallic screen resistivity (Copper wire Ohm. 0.01786 Max 0.016490 screen) mm2/m 7 Tan Delta measurement ------ 0.0001 max 0.0001239 8 Lightning Impulse test for 10 +ve & 10 KV To withstand Max 02 –ve at 1050kV on sample sample per contact as per IEC- 62067 cl. 10.2 (Already test conducted from first two lots) 9 Longitudinal water tightness test Visual Water should Max 02 (Water Penetration Test) not emerge sample per from ends of contact as test piece per IEC- 62067 cl. 10.2 (Already test conducted from first two lots) 2. Physical Dimension:
S Test Descriptions Unit Specified Observed
No. Values Values 1 No. of wires per segment(IEC – 60228 Cl-2) No. 61 wires / 61 wires / s/mm 5 segments 5 segments +7 +7 = 312 2 Approx. Overall Diameter of Conductor mm 41.2 41.35 Approx. 3 Thickness of Semi Conducting over mm 0.10 0.17 conductor 4 Thickness of Extruded Semi Conducting mm 1.15 / 2.5 2.51/2.73 Conductor Screen 5 Radial Thickness of Extruded XLPE mm 20.7 / 23.0 23.2/23.40 Insulation 6 Eccentricity of Insulation % 10 2.41 7 Thickness of Extruded Semi Conducting mm 1.15 / 1.5 1.68/1.77 Insulation Screen 8 Ovality of Core % 5 (Max) 1.05 9 Thickness/ Number of Semi Conducting mm 2x0.40 2x0.42 Water Swellable Tape over Insulation Screen 10 No. & Diameter of Copper wires No/mm 75/1.58 75/1.59- 1.60 11 Thickness of Copper Tape-Open Helix mm 0.1 0.103 12 Thickness of Semi Conducting Water mm 2x0.40 2x0.43 Swellable Tape over Metallic Screen 13 Thickness of Metallic Lead Alloy “ E” Sheath mm 3.04/3.30 3.23/3.38 14 Thickness of Non Conducting Water mm 0.40 0.45 Swellable Tape over Metallic Screen 15 Thickness of HDPE (ST-7) Outer sheath mm 3.6/4.30 5.78 / 6.05 16 Overall Diameter of Cable with Extruder mm 121 ±3.0 120.25 Semiconducting Layer 3. Tests on Insulation (Natural): S Test Descriptions Unit Specified Observed No. Values Values 1 a. Tensile Strength (Before N/mm2 12.5 Min 22.50 ageing) b. Elongation at break (Before % 200 Min 613 ageing) 2 HOT Set Test (200±3 ° C for 15 minutes) a. Elongation under load % 175 Max 60 b. Permament Elongation % 15 Max 0.15
4. Test on HDPE (ST-7) Outer Sheath Black:
S Test Descriptions Unit Specified Observed No. Values Values 1 a. Tensile Strength (Before N/mm2 12.5 min 29.24 ageing) b. Elongation at break (Before % 300 min 906 ageing) 2 Visual Check for Embossing & Visual KEI INDIA 127/220 Surface Finish KV 1C X100 SQMM CU XLPE 2019 3 Sequential Length marking at every Visual Shall be Provided meters provided