Isolated Footing Design(ACI 318-11)

Footing No. Group ID Foundation Geometry


- - Length Width Thickness
1 1 2.00m 2.00m 0.35m
2 2 2.00m 2.00m 0.35m
3 3 2.00m 2.00m 0.35m
4 4 2.00m 2.00m 0.35m
5 5 2.00m 2.00m 0.35m
6 6 2.00m 2.00m 0.35m
7 7 2.00m 2.00m 0.35m
8 8 2.00m 2.00m 0.35m
9 9 2.00m 2.00m 0.35m
10 10 2.00m 2.00m 0.35m
11 11 2.00m 2.00m 0.35m
12 12 2.00m 2.00m 0.35m
13 13 2.00m 2.00m 0.35m
14 14 2.00m 2.00m 0.35m
15 15 2.00m 2.00m 0.35m
16 16 2.00m 2.00m 0.35m
17 17 2.00m 2.00m 0.35m
18 18 2.00m 2.00m 0.35m
Footing Pedestal
Footing Reinforcement
No. Reinforcement
Bottom Bottom Top Top
- Main Steel Trans Steel
Reinforcement(Mz) Reinforcement(Mx) Reinforcement(Mz) Reinforcement(Mx)
1 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
2 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
3 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
4 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
5 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
6 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
7 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
8 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
9 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
10 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
11 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
12 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
13 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
14 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
15 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
16 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
17 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
18 9 - ϕ16 9 - ϕ16 N/A N/A N/A N/A
Isolated Footing 2

Design Calculations

Footing Size

Initial Length (Lo)= 2.00m

Initial Width (Wo)= 2.00m


Before consideration of self weight and load safety factor table

Moments are about the center of footing / pile cap (does not include moments caused by lateral
loads)

Reduction of force due to buoyancy = 0.00 kN

Effect due to adhesion = 0.00 kN

Area from initial length and width, Ao = Lo X Wo = 4.00 m2

Min. area required from


= 1.90 m2
bearing pressure, Amin

ote: Amin is an initial estimation considering self-weight, axial load and moment against factored bearing capacit

Final Footing Size

Length (L2) = 2.00 m Governing Load Case : # 22


Width (W2) = 2.00 m Governing Load Case : # 22
Depth (D2) = 0.35 m
Depth is governed by Ultimate Load Case
(Service check is performed with footing thickness requirements from concrete check)
Area (A2) = 4.00 m2
Final Soil Height = 0.00 m
Foundation Self Weight = 33.60 kN
Gross Soil Bearing Capacity = 167.98 kN/m2
Soil Weight On Top Of Footing = 0.00 kN

Pressures at 4 Corners

Please note that pressures values displayed in tables below are calculated after dividing by soil
bearing factor
Pressure at Pressure at Pressure at Pressure at
Area of footing
Load Case / top left top right bottom bottom left
in uplift (Au)
Combination corner corner right corner corner
(m2)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)

36 60.0659 59.9477 21.5722 21.6904 0.00

36 60.0659 59.9477 21.5722 21.6904 0.00

34 21.6835 21.5654 59.9546 60.0728 0.00

34 21.6835 21.5654 59.9546 60.0728 0.00

If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for
uplift, areas of negative pressure will be set to zero and the pressure will be redistributed to
remaining corners.

Summary of Adjusted Pressures at four Corners

Pressure at
Pressure at top Pressure at top bottom right Pressure at
Load Case / left corner right corner corner bottom left corner
Combination (kN/m2) (kN/m2) (kN/m2) (kN/m2)

36 60.0659 59.9477 21.5722 21.6904

36 60.0659 59.9477 21.5722 21.6904

34 21.6835 21.5654 59.9546 60.0728

34 21.6835 21.5654 59.9546 60.0728

Stability Check
Factor of safety against
- Factor of safety against sliding
overturning

Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.

22 1103.09 9688.35 1096.00 1.50 37036.65 2158.08 1.50

23 8.57 256.36 8.56 1.50 1844.24 6.91 1.50

24 1277.50 5.39 5.39 1.50 5.42 2499.30 1.50

25 8.45 245.16 8.45 1.50 1698.23 6.87 1.50

26 1277.50 5.39 5.39 1.50 5.42 2499.30 1.50

27 12.38 374.64 12.38 1.50 2732.41 9.96 1.50

28 1103.09 7.75 7.75 1.50 7.80 2158.08 1.50

29 12.11 347.75 12.10 1.50 2381.10 9.87 1.50

30 1103.08 7.77 7.77 1.50 7.80 2158.07 1.50

31 1028.34 9031.83 1021.73 1.50 34526.90 2011.84 1.50

32 1059.48 9305.38 1052.68 1.50 35572.63 2072.77 1.50

33 10.12 304.84 10.11 1.50 2211.84 8.15 1.50

34 1059.48 6.35 6.35 1.50 6.38 2072.77 1.50

35 9.93 286.09 9.92 1.50 1967.22 8.08 1.50

36 1059.48 6.35 6.35 1.50 6.38 2072.77 1.50

37 8.09 242.32 8.08 1.50 1745.53 6.52 1.50

38 1132.16 5.09 5.09 1.50 5.11 2214.95 1.50

39 7.97 231.06 7.97 1.50 1598.73 6.48 1.50

40 1132.15 5.09 5.09 1.50 5.11 2214.94 1.50

Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - X
Direction

Critical Load Case for Sliding along X- 39


Direction :
Governing Disturbing Force : -8.20 kN
Governing Restoring Force : 65.43 kN
Minimum Sliding Ratio for the Critical 7.97
Load Case :
Critical Load Case for Overturning about 38
X-Direction :
Governing Overturning Moment : 25.59 kNm
Governing Resisting Moment : 130.85 kNm
Minimum Overturning Ratio for the 5.11
Critical Load Case :

Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - Z
Direction

Critical Load Case for Sliding along Z- 38


Direction :
Governing Disturbing Force : 12.86 kN
Governing Restoring Force : 65.43 kN
Minimum Sliding Ratio for the Critical 5.09
Load Case :
Critical Load Case for Overturning about 39
Z-Direction :
Governing Overturning Moment : 20.18 kNm
Governing Resisting Moment : 130.86 kNm
Minimum Overturning Ratio for the 6.48
Critical Load Case :
Critical Load Case And The Governing Factor Of Safety For Sliding Along Resultant Direction
Critical Load Case for 38
Sliding along Resultant
Direction :
Governing Disturbing 12.86 kN
Force :
Governing Restoring Force 65.43 kN
:
Minimum Sliding Ratio for 5.09
the Critical Load Case :
Shear Calculation
Punching Shear Check
Design For Bottom Reinforcement Parallel to X Axis

Design For Bottom Reinforcement Parallel to Z Axis


Isolated Footing 10
Design Calculations

Footing Size

Initial Length (Lo)= 2.00m

Initial Width (Wo)= 2.00m

Before consideration of self weight and load safety factor table

Moments are about the center of footing / pile cap (does not include moments caused by lateral
loads)

Reduction of force due to buoyancy = 0.00 kN

Effect due to adhesion = 0.00 kN

Area from initial length and width, Ao = Lo X Wo = 4.00 m2

Min. area required from


= 1.83 m2
bearing pressure, Amin

ote: Amin is an initial estimation considering self-weight, axial load and moment against factored bearing capacit

Final Footing Size

Length (L2) = 2.00 m Governing Load Case : # 22


Width (W2) = 2.00 m Governing Load Case : # 22
Depth (D2) = 0.35 m
Depth is governed by Ultimate Load Case
(Service check is performed with footing thickness requirements from concrete check)
Area (A2) = 4.00 m2
Final Soil Height = 0.00 m
Foundation Self Weight = 33.60 kN
Gross Soil Bearing Capacity = 167.98 kN/m2
Soil Weight On Top Of Footing = 0.00 kN
Pressures at 4 Corners

Please note that pressures values displayed in tables below are calculated after dividing by soil
bearing factor

Pressure at Pressure at Pressure at Pressure at


Area of footing
Load Case / top left top right bottom bottom left
in uplift (Au)
Combination corner corner right corner corner
(m2)
(kN/m2) (kN/m2) (kN/m2) (kN/m2)

35 57.8058 24.4797 22.5226 55.8487 0.00

33 24.5362 57.6969 55.7954 22.6347 0.00

33 24.5362 57.6969 55.7954 22.6347 0.00

35 57.8058 24.4797 22.5226 55.8487 0.00

If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for
uplift, areas of negative pressure will be set to zero and the pressure will be redistributed to
remaining corners.

Summary of Adjusted Pressures at four Corners

Pressure at
Pressure at top Pressure at top bottom right Pressure at
Load Case / left corner right corner corner bottom left corner
Combination (kN/m2) (kN/m2) (kN/m2) (kN/m2)

35 57.8058 24.4797 22.5226 55.8487

33 24.5362 57.6969 55.7954 22.6347

33 24.5362 57.6969 55.7954 22.6347

35 57.8058 24.4797 22.5226 55.8487


Stability Check

Factor of safety against


- Factor of safety against sliding
overturning

Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.

22 2619.43 43.38 43.38 1.50 130.13 3036.28 1.50

23 6.06 52.66 6.02 1.50 154.19 6.18 1.50

24 78.50 8.74 8.68 1.50 7.13 77.50 1.50

25 6.03 48.23 5.99 1.50 148.00 6.16 1.50

26 84.01 6.57 6.55 1.50 6.61 82.28 1.50

27 8.71 44.56 8.55 1.50 131.76 8.89 1.50

28 111.05 14.23 14.12 1.50 10.60 109.92 1.50

29 8.65 42.27 8.48 1.50 128.55 8.84 1.50

30 122.63 8.66 8.64 1.50 9.20 119.75 1.50

31 2439.15 40.40 40.39 1.50 121.18 2827.31 1.50


Factor of safety against
- Factor of safety against sliding
overturning

Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.

32 2514.27 41.64 41.63 1.50 124.91 2914.38 1.50

33 7.12 42.97 7.02 1.50 126.74 7.27 1.50

34 91.29 11.08 11.00 1.50 8.56 90.28 1.50

35 7.08 40.39 6.97 1.50 123.13 7.23 1.50

36 99.71 7.31 7.29 1.50 7.61 97.47 1.50

37 5.71 46.46 5.67 1.50 136.24 5.83 1.50

38 73.80 8.32 8.27 1.50 6.74 72.88 1.50

39 5.68 42.78 5.63 1.50 131.09 5.80 1.50

40 79.33 6.14 6.12 1.50 6.21 77.67 1.50

Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - X
Direction

Critical Load Case for Sliding along X- 39


Direction :
Governing Disturbing Force : -11.34 kN
Governing Restoring Force : 64.45 kN
Minimum Sliding Ratio for the Critical 5.68
Load Case :
Critical Load Case for Overturning about 40
X-Direction :
Governing Overturning Moment : -20.91 kNm
Governing Resisting Moment : 129.88 kNm
Minimum Overturning Ratio for the 6.21
Critical Load Case :

Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - Z
Direction
Critical Load Case for Sliding along Z- 40
Direction :
Governing Disturbing Force : -10.58 kN
Governing Restoring Force : 64.94 kN
Minimum Sliding Ratio for the Critical 6.14
Load Case :
Critical Load Case for Overturning about 39
Z-Direction :
Governing Overturning Moment : 22.20 kNm
Governing Resisting Moment : 128.89 kNm
Minimum Overturning Ratio for the 5.80
Critical Load Case :
Critical Load Case And The Governing Factor Of Safety For Sliding Along Resultant Direction
Critical Load Case for 39
Sliding along Resultant
Direction :
Governing Disturbing 11.44 kN
Force :
Governing Restoring Force 64.45 kN
:
Minimum Sliding Ratio for 5.63
the Critical Load Case :

Shear Calculation
Punching Shear Check