Академический Документы
Профессиональный Документы
Культура Документы
Pumped CO2 in
Industrial Refrigeration Systems
REFRIGERATION &
aIR CONDITIONING DIVISION Application guide
Application guide Pumped CO2 in Industrial Refrigeration Systems
Contents Page
General description of CO2 fluid systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Differences to traditional NH3/brine systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Frequency control of the CO2 pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Defrosting CO2 systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Evaporator control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4 3
6 7 8
CO2 receiver
0
A typical schema of a low/medium temperature The CO2 gas flows up (7) into the cascade heat
NH3/CO2 system (fig. 1) consisting of exchanger, where it is cooled by NH3, condenses
a Standard NH3 refrigeration system with a and flows back down into the CO2 receiver
cascade heat exchanger acting as evaporator as liquid CO2 (8). On the ammonia side the
refrigeration cycle can be controlled using a high
CO2 acts as a volatile fluid in the evaporators pressure float valve (HFI) or by direct expansion
(flooded system (1-6)) into the evaporator (e.g. with an electronic
expansion valve type ICM, and a cascade
CO2 is circulated by gravity in the cascade heat controller type EKC 313).
exchanger, which gives good control of the CO2
temperature in the receiver.
DN 65
DN 150
Differences to traditional Optimising energy control: That can be done using Danfoss pack controller
NH3/brine systems. Further reduction of energy consumption by AK-PC 730/840.
NH3/CO2 systems is possible using smart control
(Continued) algorithms. A good way to improve the efficiency The management of the suction pressure
(COP) of the system is to reduce the pressure ratio is another area where there are differences
in the NH3 compressor. The 2 ways of doing this between CO2 cascade systems and brine/glycol
are systems.
Keep the condenser at the lowest possible Assuming a system design as shown in fig. 3.
pressure. A pressure signal from the CO2 receiver can
be used to control the capacity of the cascade
Keep evaporation at the highest possible compressors (the NH3-system).
pressure If the pressure in the CO2 receiver decreases,
The condenser control is similar to that of then the speed of the cascade compressors also
traditional systems, where fans can be controlled decreases, in order to keep up the CO2 pressure.
by an AKD102 variable frequency drive, and the This function can be provided by the AK-PC 730 /
condensing pressure can vary depending on the 840 Pack Controller.
ambient temperature.
AKD 102
AK-PC 730
AKS 2050
AKS 11
EKC 315A
AKS 2050
AKD 102
AKS 11
ICF
Control
Solution
SFA 15
Plant controller
AKS 3000
From coldrooms
Pump
AKD 102
To coldrooms
DCR
Frequency control
of the CO2 pumps
AKS 41 From
To evaporators
compressor SVA
suction line SFA SFA
SNV
From
receiver
SVA SVA
DSV SVA
Liquid
Separator
SNV
SVA
SVA SVA
REG REG
SVA SVA
FIA FIA
SVA
AKD
RT 260A RT 260A
Refrigerant
pumps
CVP(XP) CVP(XP)
SCA SCA
To
evaporators
Figure 4 - CO2 pump stations with AKD and the necessary valves and controls
There are two ways to control the liquid CO2 Better liquid distribution in the evaporators
pumps; using a simple on/off step control or A requirement for good performance of the
using a frequency converter (type AKD). evaporators / air coolers is a good distribution of
Frequency converter operation is becoming the refrigerant liquid in the system.
increasingly popular for 2 good reasons: Energy
savings and Better liquid distribution in the A precondition for good distribution of
evaporator coils. refrigerant liquid is having a stable pressure
differential across the evaporators.
Energy savings
CO2 pumps are typically controlled by a constant Pumps controlled by frequency converters can
pressure difference. Under standard conditions ensure that the pressure is kept at a stable level
the energy consumption is the same as or slightly under all load conditions. At low capacity the
higher than that of a fixed speed pump. When energy consumption will be low and at high
running under partial load conditions, a fixed capacity there will be sufficient flow of CO2.
speed pump would still consume the same
energy due to the increased pressure difference. A typical piping layout with CO2 pumps
A liquid CO2 pump using a frequency converter controlled by frequency drives (AKD 102 type)
will run at a lower velocity and consume less is shown in figure 4. Another benefit of pumps
energy. driven by frequency converters is that the Q-max
orifices can be omitted.
The savings will vary depending on the running
time and the actual running conditions. Savings
can, however, be up to 50% compared to pumps
operating on/off at full speed.
Defrosting CO2 systems There are several ways to defrost pumped CO2
systems
Electrical defrosting. This is the simplest and The process is similar to a traditional NH3
least energy efficient method of defrosting. defrosting system.
The additional power consumption for Brine defrosting. By using brine it is possible
defrosting can be quite significant in some to utilize the heat from the cascade system
cases. to defrost CO2 evaporators. This application is
Hot gas defrosting. CO2 hot gas defrosting especially attractive if the ammonia condenser
can be used if a compressor is built into the is water cooled.
system to support defrosting. That compressor Water defrosting. In some cases (especially
will then only operate when defrosting is in rooms with temperatures above zero)
needed. This method is more economic than evaporators can be defrosted using sprayed
electrical defrosting. water.
Controller
GPLX
AKS 21
SVA
SVA CVP-XP
To liquid
separator
ICS
ICFE
From liquid ICFS ICFR
separator
AKS 21
ICF AKS 21
SCA
From defrost ICFE
ICFS
compressor
Evaporator
ICFF
ICF ICFS
AKVA
Option 1
From liquid
separator
To liquid
SVA FIA EVRA REG SVA SVA separator
Option 2 Evaporator
Figure 6
In a traditional flooded system, the injection thermostat differential can cause unwanted side
of liquid is controlled by a thermostat which effects in some cases, such as dehumidification
constantly measures the air temperature. The and inaccurate temperature control.
solenoid valve is opened for a few minutes or
longer until the air temperature has reached Instead of injecting periodically, as described
the set point. During injection the mass of the above, one can also constantly adapt the liquid
refrigerant flow is constant. This is a very simple injection to current needs. This can be done by
way to control the air temperature, however means of a pulsing AKV(A) valve.
the temperature fluctuation caused by the
cut in
MTR ref
Figure 8
To download literature for other Danfoss products, please visit the Danfoss internet site
http://www.danfoss.com/Products/Literature/RA_Documentation.htm
System manager, AK-SC 255 Expansion valve, AKV Filter drier, DCR ADAP-KOOL® Drive, AKD 102
Pack controller, AK-PC 730 Solenoid valve, NRVH Ball valve, GBC
Case controller, AK-CC 550