Introduction:
The High Sulphur Diesel fuel has been planned as a backup fuel for heat generation to Spray
drier and Calciner. In addition to this the HSD is used as fuel for Emergency DG.
Infrastructure
The capacity of the HSD tanks are 50 KL. The consumption pattern for HSD is
Statutory Clearances:
For installation of this High Speed Diesel Storage classified under ‘B’ consumer pump of
Petroleum Class – B specified under Petroleum Storage Rules 2002, we need to satisfy and
obtain the following clearances.
Part – A:
1
Initial approval of Drawings and Site approval of the proposed High Speed Diesel Storage is to
obtained from the Chief Controller of Explosives, Nagpur complying with the requisite conditions
/ forms and enclosures.
Part – B:
And based on these NOC’s the final NOC will be awarded by the District Revenue Officer of the
District Collector.
‘Part – C’ :
After completion of Installation of Tanks and Civil works, Piping works along with the final NOC
awarded by the Collector / DRO along with the Tank Test Certificate and Safety Certificate
issued by the Competent Authority, we have to apply for the Storage License to the Chief
Controller of Explosives, Nagpur.
Safety:
1. The earth pit should be erected at the tank farm with meager value less than 10 Ohms.
2. Required Fire and Safety norms are to be adhered at the Site of the High Speed Diesel
Storage as given below:
3. 10 KG DCP Fire Extinguishers are to be installed
4. DCP Trolley Type 1 No is to be installed
5. AFFF Extinguishers 2 No’s are to be installed.
Drawings
2
1. Tank Farm drawing.
2. Tank drawing.