U P S S Y S T E M S W I T H D I G I TA L
C O M P U S AV E T E C H N O L O G Y
➜➜➜
Technical brochure
TA B L E O F C O N T E N T S
UPS SYSTEMS 4
➜ Description of function 6
➜ Structure 7
➜ Operating modes 8
➜ CompuWatch 16
SERVICE 31
3
UPS SYSTEMS
4
➜ System configuration/operating modes
Individual operation with Up to 4 units can be operated in units take over the additional
SBS, passive redundancy parallel with SVS Protect 3./SVS proportion of the load.
This is the standard operating Protect 4.
This parallel redundant operation is
mode. The consumers are powered As such, the UPS units operate in preferred for safety reasons in
online via the recitifer and inverter. permanent parallel mode without large (central) IT systems.
This means all disruptions in the central control components. The
power system, e.g. frequency and load is divided equally. In the event
voltage deviations, distorted of a malfunction in one UPS unit, it
voltage waveforms, brief interrup- is switched off without affecting the
tions and power cuts are kept consumers and the remaining UPS
away from "preferred consumers".
Redundant parallel
operation, active
redundancy
A further improvement in availability
is achieved by redundant parallel
operation (term used in standards:
parallel redundant operation) of
several UPS units. Active redundancy
means that at least one more UPS
unit has to be installed than would
be required simply on the basis of SBS SBS
AC-loads
5
➜ Description of function
6
➜ Structure
0,90
control unit equipped with and nominal load with cos w 0.8 0,85
0,70
part-load range, was achieved by 0 10 20 30 40 50 60 70 80 90 100
➜ Charging the battery by IU Utilisation in %
concentrating on reducing the
characteristics in accordance
losses which do not depend on the
with DIN 41773
load. The use of IGBT power
➜ Smooth rise in current and
transistors made a significant
voltage
contribution to this. It results in a
➜ Generating the trigger pulses high level of battery capacity
for the thyristors utilisation, amongst other factors.
7
➜ Operating modes
8
Battery management Safety first: The following tests The following parameters are
The availability of the UPS depends must be initiated manually using the measured:
on the accumulator, the battery. display and operation board (ABE) ➜ Battery voltage, current, test
Consequently, three different with password protection. Manual time and the battery capaci-
battery tests are implemented in initiation takes into account that tance drawn
SVS Protect 3./SVS Protect 4. The the autonomy times of the UPS are
The aforementioned measurement
objective of these tests is to give limited during the tests due to
parameters are available at the
the user reliable information about (partial) discharging of the battery.
end of the test and can be noted
the status of the battery and the Consequently, the tests should not
down.
connection to the UPS. An optional be performed unless the client
Test information: With a de-
flat battery monitor switches the processes permit this.
fined, constant discharge current,
battery off after the bridging time, the battery has a capacitance of
thereby guaranteeing that the Test 2: Full UPS test
X Ah and a bridging time of X.
battery is not irreparably damaged A reduction in the rectifier voltage
by exhaustive discharge. forces the battery to take over Test 2 is an option.
the inverter current. The rectifier
Test 1: Battery test provides protection against a Test 3: Permanent battery
failure of the UPS function in the monitoring
This is automatically triggered once
a week. A slow reduction in the event of a battery failure. Permanent battery monitoring can
rectifier voltage forces the battery The battery is discharged with a be offered as an option with the
to take over the inverter current. constant current defined by the BLÜ 2 assembly. Battery cell
The rectifier provides protection user. (The load current in this case failures are immediately detected
against a failure of the UPS must be large enough so the and reported.
function in the event of a battery rectifier current is approx. 5 %
Test 3 is an option.
failure. greater than the required discharge
Test information: Battery present, current.)
functional and connected.
9
S V S P RO T EC T 3. AND SVS PROTECT 4 . U P S S Y S T E M S
10
➜ AEG SVS power supply systems
create new perspectives
SVS Protect 3. and SVS Security and performance Unique feature: control by a
Protect 4. – Synonymous for by parallel operation redundant processor system
a new dimension in the SVS Protect 3./SVS Protect 4. The design is characterised by
world of UPS systems protect your processes even in having three processor systems.
For the first time, up to 500 kVA case of significantly greater power These are new developments by
power is available in a compact, requirements or particularly AEG SVS, especially for use in UPS
pre-wired unit. This opens up exacting reliability requirements. units. Each processor controls and
completely new dimensions in this This is ensured by a unique monitors the rectifier, inverter and
class. flexible multi-master static bypass switch (SBS) in-
technology (FMMT) in parallel dependently of the others. After
Whether for computer centres, file
mode. This technology is made all, you don't want to leave
servers, telecommunications or
possible by high-speed, robust anything to chance when it comes
industrial processes – SVS Protect
and redundant communication via to uninterruptible power supply –
3. and SVS Protect 4. allow you to
the CAN bus which is now in and we certainly don't either.
power your systems reliably.
widespread use in safety systems
Yield-oriented sustained operation employed in the automotive in- High capacity, compact,
in information technology would be dustry, for example. Two individual reliable
unthinkable without an uninterrup- units continuously undertake master SVS Protect 3. and SVS Protect 4.
ted power supply. Even the briefest functions. Each individual unit stand for the most modern tech-
of voltage fluctuations, frequency can take over this master function nology with efficient and extremely
deviations or power cuts may result instantaneously if required by a highly reliable operation. A 12-
in system crashes entailing untold defined strategy on the basis of pulse rectifier with sinusoidal mains
damage. SVS Protect 3. and SVS the situation in the overall system. current intake and battery charging
Protect 4. protect your sensitive Although the aforementioned CAN acc. to DIN 41733, a 3-phase
systems online against these risks – bus is very well suited to the secure inverter and an SBS are integrated
with a maximum degree of relia- and fast transfer of data, the ex- into a single, compact housing.
bility and without risky switching change of "critical" control data This arrangement guarantees an
operations. in parallel mode has not been even supply of alternating current,
implemented. Nevertheless, a very microprocessor-controlled battery
good static and dynamic current charging management and
distribution is achieved between changeover of the loads to the
the inverters without communication, existing power system with no
even for loads with fluctuating interruption.
vibrations (e.g. textile machinery).
The latter feature is made possible Computer-aided remote monitoring
by the status control concept which is just as much a feature of SVS
has been implemented. SVS parallel Protect 3. and SVS Protect 4. as the
systems are therefore characterised automatic shutdown of connected
by their high levels of availability, systems on the basis of defined
robustness and reliability in industrial specifications.
applications in particular.
11
Additive protection level against
EMC effects for SVS Protect 3./SVS Protect 4. ESD
electro-
static
discharge
Surge HF fields
Surge Resistence to
voltages interference
d
dar
roduc t-sEtaNn5-20091
P
EN 5 0091
L evel
-
EG SVS
Additional A
Burst
High-speed
transients
➜ Soaking up the
punishment
12
➜ Graphical display and operation board
13
Clearly structured menu
Example: Power on
Self-test
Language
Main menu
Inverter Evaluation
SBS
A self-test of the display and Once the test is completed The menus leading up to the main
operation board is carried out after successfully, the language select menu are in English in order to
the power-on reset. This self-test is function is activated if this is the meet international requirements.
indicated by the LEDs lighting up in first startup of the ABE. This allows
sequence as well as on the display. various languages to be selected
A status bar indicates the duration for the LC display. There are 14
of the self-test. The duration varies different languages available at
depending on the system present. The selected language is
configuration. loaded by pressing the ENTER key,
then the main menu appears.
14
Main menu of the graphical display and operation board
Current cursor position
15
➜ Communications options for SVS Protect 3./
SVS Protect 4. on different transmission media
Firmware
➜ Self-configuring firmware – networkmanagement
telecom
can be used for the entire
AEG SVS UPS range with telecom
activated back-lighting
when keys are pressed
➜ Online help function
➜ CompuWatch
Software for safeguarding It is based on the TCP/IP network using safety mechanisms to all
and controlling networks protocol and can be used in servers and computer systems
CompuWatch, developed with heterogeneous networks for safely powered by the UPS. The informa-
a client/server technology, is and automatically shutting down tion is then processed in the corres-
a system shutdown and UPS server and computer systems ponding software modules. A
management software package running under all kinds of operating staggered shutdown is possible by
from AEG SVS Power Supply systems when required. In other configuring all software modules to
Systems GmbH. words, all open databases and match the appropriate servers. All
files are closed. The intelligent modules in CompuWatch operate
communications link between the as a service or daemon (background
UPS and the server, combined with process). Individual procedures can
the existing network topology, be started using shell scripts or batch
allow the information to be sent processing.
16
Total network security uninterruptible power supply. It goes without saying that the
solution In other words, the entire data same look and feel is provided
network is powered down and for different UPS units: single and
In conjunction with an intelligent switched off safely after a lengthy three-phase. CompuWatch also has
subrack UPS from AEG SVS power failure: shutdown function. an SNMP proxy agent for the
Power Supply Systems GmbH, you Once the power failure has been APIs of various operating systems.
can be sure that serviceability of IT restored, the network is restarted This makes it possible to incor-
components and data security for automatically after a certain period porate UPS units into a network
the network servers are guaranteed. and the systems start up: reboot management system using a
Fig. 1 shows an example of a function. straightforward procedure.
heterogeneous network with a The products of AEG SVS Power
server running under Windows NT Supply Systems GmbH give you a
configured as the master as well as The Client of CompuWatch, a complete security package
various slave servers with different graphical front-end for all Microsoft for networks from a single
operating systems. Windows operating systems, makes source:
it possible to monitor and control Total network security solution.
all UPS systems connected to the
These products make it possible to network.
implement an automated system for In addition, the entire network
shutting down and rebooting the can be controlled by means of a
entire network including the scheduler.
Terminal
Terminal
Terminal Terminal
Terminal
Novell Unixware
MS-Win NT
SCO
Unix
HP-UX DEC
Unix
Siemens IBM
Sinix OS/2 Novell Netware
17
➜ The benefits to you
18
➜ Technical data of SVS Protect 3. UPS systems
Rated connected voltage 3 x 380 V – 3 x 415 V ±15 % over the entire voltage range
Frequency 50 Hz ±10 % or 60 Hz ±10 %
Start current ≤ I nom
Rated DC voltage 384 V
No. of cells in the lead-acid battery 192 cells with 400 V mains voltage
204 cells with 415 V mains voltage
Rated AC voltage 3 x 380 V or 3 x 400 V or 3 x 415 V, with fully load-capable N conductor
Setting range of the output voltage ±5 % at nominal DC voltage
Rated frequency 50 Hz ±0.1 % or 60 Hz ±0.1 %
Frequency cycling 50 Hz ±1 % or 60 Hz ±1 %
(synchronisation range)
Voltage form sinusoidal
Voltage distortion factor < 3 % over the total DC voltage, load and power factor range
Voltage harmonic distortion with IT load < 2 % under nominal conditions
Non-linear load permitted up to 80 % of UPS nominal load
Crest factor 3, permitted to < 3 at nominal load
Dynamic response for 0 – 100 % – 0 load cycle, voltage dip < ± 2 %; settling time approx. 1 ms
Power factor range capacitive to inductive over the entire cos w range
Unbalanced load response at 100 % load unbalance: voltage deviation < 2 %; angular displacement < 2
degrees el.
Overload response overload capacity 150 % for 1 min., 125 % for 10 min.
Bypass overload response 500 %
Short circuit response SVS Protect 3. is short circuit resistant, short circuit current 3 x Inom
EMC emitted interference interference level "A" acc. to EN 50091-2
EMC strength to EN 50082-2
Noise level 55 – 65 dB(A) measured acc. to DIN 45630 at 1 m distance, half-way up the
unit, depending on power level
Type of cooling assisted natural air cooling with integrated fans in redundant configuration
Operating temperature range -5 °C to +40 °C
Storage temperature range -35 to +75 °C
Installation height up to 1000 m above sea level at nominal load
Protective system IP 20 to DIN 40050
Equipment colour RAL 7022/7044, powder coating
Regulations VDE 0558, Part 1, Part 2 and Part 5
Size w x h x d (mm)
10 kVA, 20 kVA, 30 kVA, 40 kVA 600 x 1700 x 715
60 kVA 750 x 1700 x 715
80 kVA, 100 kVA, 120 kVA 1200 x 1700 x 715
Weight (kg) 370 420 460 480 650 890 950 1000
19
Connection cross sectional areas and fusing for SVS Protect 3.
Cross sectional configurations acc. to DIN 0298 part 4 table 3, routing type B1/B2
20
Principle view
Block diagram
400/230 V; 3/N/PE˜50 Hz
400 V; 3/N/PE˜50 Hz
1 4
Standard connection type
4 5
2 5
Q1 3 Bypass 6
CompuSave
Rectifier
~
–
Q 28
2
11 12 13
Inverter Thyrostat
Battery
–
~
Isolating
transformer
Q29
Signalling
7
5 10 7
9
400/230 V; 3/N/PE˜50 Hz
AC distribution
AC loads
21
SVS Protect 3. options
22
SVS Protect 3. communications options
23
SVS Protect 3. type table
D 400 D 400/ 15/2rfg-P 10 - 384 + SBS SVS Protect 3. 33/010 kVA 29436060
D 400 D 400/ 29/2rfg-P 20 - 384 + SBS SVS Protect 3. 33/020 kVA 29436010
D 400 D 400/ 44/2rfg-P 30 - 384 + SBS SVS Protect 3. 33/030 kVA 29436070
D 400 D 400/ 58/2rfg-P 40 - 384 + SBS SVS Protect 3. 33/040 kVA 29436020
D 400 D 400/ 87/2rfg-P 60 - 384 + SBS SVS Protect 3. 33/060 kVA 29436030
D 400 D 400/116/2rfg-P 80 - 384 + SBS SVS Protect 3. 33/080 kVA 29436040
D 400 D 400/145/2rfg-P 100 - 384 + SBS SVS Protect 3. 33/100 kVA 29436080
D 400 D 400/174/2rfg-P 120 - 384 + SBS SVS Protect 3. 33/120 kVA 29436050
Communication Communication
terminals terminals
Floor Space
24
➜ Technical data of SVS Protect 4. UPS systems
RECTIFIER UNIT
Rated connected voltage 400 V or 415 V
Frequency 45 – 66 Hz
Current consumption at full-load (A) 280 386 573 859
Current consumption at full-load
and charging of battery (A) 341 463 681 1013
Characteristic line IU to DIN 41773
Rated DC voltage 384 V or 408 V
System perturbation sinusoidal
INVERTER UNIT
Rated DC voltage 384 V or 408 V
Rated AC voltage 400 V or 415 V ±5 % nominal voltage
Static deviation ≤ 1%
Dynamic deviation < 5%
Settling time 2 ms
Frequency tolerance w/o mains control 0.1 % (50 ±0.005 / 60 ± 0.006 Hz)
Synchronisation range 50 Hz ±1 % or 60 Hz ±1 %
Power factor range 0 ind. – 1 – 0 cap.
Nominal output current per phase (A) 231 318 477 722
Voltage form sinusoidal
Voltage harmonic distortion ≤ 3 % over the total DC voltage, load and power factor range
Crest factor with non-linear load 3 with nominal load
Overload response overload acceptance of 150 % for 1 min.; 125 % for 5 min.
Short circuit response SVS Protect 4. is short circuit resistant, short circuit current 3 x Inom
GENERAL DATA
Efficiency, total (%) 94
EMC emitted interference interference level "A" acc. to EN 50091-2
EMC strength to EN 50082-2
Noise level approx. 76 dB(A) measured acc. to DIN 45630 at 1 m distance, half-way up unit
Type of cooling assisted natural air cooling with integr. fans in red. configuration, with monitoring
Operating temperature range -5 °C to +40 °C (max. cooling air temperature 35 °C)
Storage temperature range -35 °C to +70 °C
Installation height up to 1000 m above sea level without power reduction
Protective system IP20 to DIN 40050
Equipment colour RAL 7022/7044, powder coating
Size w x h x d (mm) 1200x1900x900 1200x1900x900 2100x1900x900 2100x1900x900
Weight (kg) 1670 1950 3450 3950
Operating mode continuous operation
25
Connection cross sectional areas and fusing for SVS Protect 4.
Cross sectional configurations acc. to DIN 0298 part 4 table 3, routing type B1/B2
26
Principle view
Block diagram
400/230 V; 3/N/PE˜50 Hz
400 V; 3/N/PE˜50 Hz
1 4 4
Standard connection type
4 5 5
2 5 5
Q1 3 Bypass 6 6
SVS Protect 4.
Rectifier
~
–
Battery
circuit
breaker
2
11 12 13
Inverter Thyrostat
Battery SBS
–
~
Isolating
Signalling transformer
7
7
10 Q 29
9 5
400/230 V; 3/N/PE˜50 Hz
AC distribution
AC loads
27
SVS Protect 4. options
28
SVS Protect 4. communications options
29
SVS Protect 4. type table
D 400 D 400/ 231/2rfg-P160 - 384 + SBS SVS Protect 4. 33/160 kVA 29437000
D 400 D 400/ 318/2rfg-P220 - 384 + SBS SVS Protect 4. 33/220 kVA 29437010
D 400 D 400/ 477/2rfg-P330 - 384 + SBS SVS Protect 4. 33/330 kVA 29437020
D 400 D 400/ 722/2rfg-P500 - 384 + SBS SVS Protect 4. 33/500 kVA 29437040
30
SERVICE
About quality and service Experience, the most up-to-date pro- With many technical agencies and
For many decades, inverter units duction systems and an unceasing, support centres, we offer direct
from AEG SVS have embodied uncompromising approach to qua- proximity to customers all over
lity assurance mean our customers Germany.
➜ rational technology, can be certain that AEG SVS prod-
ucts combine flawless processing The AEG SVS advisers working
➜ high returns on invested funds
with a long service life. Innovative there have been trained in the
and
and environmentally friendly tech- latest technology. They are highly
➜ absolutely outstanding quality. nologies are just as much features motivated and happy to make
of our operations as is an intensive time for an in-depth advisory meet-
approach to dealing with each in- ing. Consequently, if you select
dividual customer's problem. As a a battery charging rectifier or
result, our guiding principle is to inverter from AEG SVS, you will
function as an ever-present contact have decided in favour of reliable
so we can work out the optimum function and a secure investment.
solution together.
31