Академический Документы
Профессиональный Документы
Культура Документы
• 167.91. Ih • IA3ul
114
Specification for
sheet metal ductwork
:
. 1 STANDARDS
For each ductwork system, the designer shall
provide the information covered by 1.1 and 1.2, 3.3 Special finishes (SectioIl28)
and shall also state any departure from the Details of any special finishes required, e.g.
standard specification in respect of 1.3,1.4 and galvanizing after manufacture, metal spraying,
1.5. plating, anodizing, special paints.
1.1 Pressure classification (Table 1) 3.4 Thermal insulation (Secti,," 31)
1.2 Leakage classification (Table 2) The extent (if any) to which the ductwork is to
1.3 Materials (Section 7) be insulated and details of the type of insulation
1.4 Negative pressures (Table 1) to be applied.
1.5 Variable air volume (Section 9.2) 3.5 Vapour sealing (Sectioll 19.6)
The extent (if any) to which vapour sealing is to
2 COMPONENTS
be applied to insulated ductwork; and ifso,
The designer shall (where relevant and whether to be to Method 1 or Method 2.
practicable) provide information in respect of the 3.6 Acoustic treatment (Section 30)
items 2.1 to 2.5. The extent (if any) to which any acoustic lining
2.1 A~cess openings (Section 21) or any other treatment is to be provided for the
Number and location of all access doors, access ductwork; and by whom, with detailed
panels, test holes and instrument openings, . specification.
other than those regarded as standard practice. 3.7 Attachment to building structure (Sectiolls
2.2 Control dampers (Section 22) 19 alld 2'))
Det~i1s and location of all control dampers. Details of any limitations on the attachment of
the ductwork to the building structure
2.3 Fire dampers (Section 23)
(including any special provisions designed to
Specification and location of all fire dampers to prevent the transmission of vibration; or of any
meet the requirements of the Authority directly spanning steelwork or special ductwork
concerned with fire regulations. supports not covered by this specification.
2.4 Bendable/flexible ducts (Sections 24 and 25) .
3.8 Variable air volume systems
Details and location of any flexible ducts and
connections. Identification of any part of the ductwork
system requiring modified construction, e.g. to
2.5 Flexiblejoints (Section 26) counteract exceptional changes in pressure
Details and location of any flexible joints. when the system is in operation which might
otherwise give rise to an 'oil-canning' effect.
3 SPECIAL REQUIREMENTS
3.9 Negntive pressures
The designer shall also (where relevant and Any exceptional stiffening required to prevent
practicable) provide information in respect of the unacceptable panel distortion and excessive air
items 3.1 to 3.10. leakage if negative pressures are likely to
exceed the limits set out in Table I (page 13).
3.1 Air leakage testing
3.10 Other requirements
The extent of any leakage testing required for
ductwork other than high-pressure (see 6.4); Details of any requirements for the ductwork
and the method of testing if different from that not in accordance with the provisions of this
specification, including any modified
set out in Appendix B (page 77).
constructiolJ required to conform with any
3.2 Protective treatments (Section 28) . regulations concerning external ductwork or to
Details and specification of any fire resistant or meet the requirements of a lucal authority or
other special protective treatment. other controlling body.
2
r "'
tHVCAI
"- ..J
ISBN 0 903783 04 5
3
Previous sheet metal dudwoa-I!l: s~dIfi1:2~!O~S
Ductwork Specification for High-Velocity Air
Systems (Circular) 1963
Standard Range of Rectangular Ducting 1967
DW/131 Sheet Metal Ductwork Specification for High-
Velocity Air Systems (Rectangular) 1968
DW/121 Specification for Sheet Metal Ductwork (Low-
Velocity Low-Pressure Air system~)
(Rectangular and Circular) - Metric 1969
DW/122B Specification for Sheet Metal Ductwork (Low-
Vel.eocity Low-Pressure Air Systems)
(Rectangular and Circular) - British 1969
DW/112 Standard Range of Rectangular Ducts and
Fittings - Metric and British Units 1970
DW/132 Specification for Sheet Metal Ductwork (High-
Velocity High-Pressure Air Systems)
(Rectangular, Circular and Flat Oval) - Metric 1970
DW/141 Specification for Sheet Metal Ductwork (Low-
and High-Velocity/PressureAir Systems)
(Rectangular, Circular and Flat Oval) - Metric 1977
Note
4
ACKNOWLEDGEMENTS
The HVCA records its appreciation and thanks to the many persons
and organisations who have freely given information on various
aspects of this work, and in particular to the members of the Drafting
Panel, who contributed unstintingly of their knowledge and
experience.
5
·C:ontents
Page
6
List of Tables List of Illustrations
Table Page Figs Pages
Porl Two STANI>ARDS RECTANGULAR DUCTS
Ductwork c111ssification . 13 1-7 Longitudinal seams " .. 17
I
Air leaknge limits .. ,._ ,_ . 13 8 Illustrations of panel stiffening , . 23
2
Crossjoims
9-12 Socket and spigot (cross sectional) , ,., ... 24
PorI Three 13-19 ~ock~t and spigot (corners and
RECTANGULAR nUCTS Junctions) " ,.. " , " 28-27
.1 Standard sizes , , , , .. 15 20-24 Cleated (cross sectional) " .. 28
Minimum sheet thicknesses . 16
25-32 Cleated (corners and junctions) 29-30
4
.13-43 Flan~ed (cross sectional and corners
8 COllstruetloonl requirements- Ilnd Junctions) , ", .. " " ,,,, .. 31-33
low~prcssllrc (up 10 5<Xl Pa) . 18 44-49 Single stiffeners ", , .. 34
(0 Construclionlll requirements- 80 Tie rods , " .. 34
mcdium·prcssurc (up to HXX) Pa) . 19
7 Constructional requirements- Fittings
high·pressure (up to 2000 Pa) . 20 51 Examples of 'hard' and 'easy' , ,. 35
R Constructional requirements- 52-89 Bends , " ,.. " .. , . 37
high-pressure (up to 2500) . 20 (;0-63 Branches " " 38
9 Ductwork galvanized after 64-66 Offsets " """." . 3R
manufacture .. , _, . 21 67-69 Tapers " " " .. ". 38
10 Fastenings , . 21 70-71 Transformations , " " . 38
l~xample5 of the application or the 72-73 38
Change shapes " , ..
Joint rating sy!dem (Tables 5 to 8) . 22
II Fittin~s:- standard names and CIRCULAR DUCTS
descriptions , ,.'.,., ".",., . 36 Longitudinal seam
12 Number of turning vaneS where 74 Grooved seam (straight-seamed ducts) 42
r = 50mln., ,.. ,. 37
Cross joints
ParI Four - CIRCULAR DUCTS 75·81 Spirally-wound ducts " .. ', " .. 42-43
13 Standard sizes , . 39 fl2·86 Straight-seamed ducts " . 44-45
14 Constructional requirements-
Fittings
spirally~wound , , . 40 87·93 Bends " .. , ,.. 47
15 Constructional requirements-
straight~scamed , . 94-100 Branches " .. , ", .. 48
40 101·102 Change shapes , ", .. ,.", .. ",., .. ,." 48
16 Pennitted fastenings and maximum
spacings . 41
103·104 Transfonnations : ", , ,." 48
17 Fittings.- sheet thicknesses . 105·106 Offsets .... "., .. , .. ,.. , , " .. " ,... 4R
41 107-108 Connectors ,,,, ,.. 48
18 Fittings - spigots . 41
19 Fittings - standard names and 109-110 Closures " .. " " " .. 48
descriptions , . 46 FLAT OVAL nUCTS
111-113 Stiffening (tie rod positioning)-
Part Five FLAT OVAI. DUCTS low. and medium-pressures .. ,..... " .. "., 50
20 Standard sizes and sheet thicknesses .... 49 114~117 Stiffening (tie rod positioning)-
21 Stiffening requirements- high-pressure "." , 51
low- and mediulJ1~pressure . 50 118-120 Tic rod fastening methods , , 52
22 Stiffening requirements-
high~pressure . 51 Fittings
23 Filtin~s:- standard names and 121·129 Bends . 54
descriptions .. 83 Branc!les- for branches offnal pronle.
see rectangular duct fittings, Figs, 60-62
I'ort Six HANGERS AND Branclres- for branches off'ltml-
drcular profile, see circular fittings,
SUPPORTS Figs. Q4-100
24 Supports for horizontal ducts- 130·131 Tapers ., , ,." .", " " ", 54
rectangular .. 87 132-133 Transformations ,,, . 54
25 Supports for horizontal ducts- 134 Offsets " .. " , " .. , .. 54
circular . 57 135 Couplings ,.. " , , , ". 54
26 Supports for horizontal ducts-
nat oval . 58 136 Closures ." , , " .. ,., . 54
HANGERS AND SUPPORTS
Part Seven GENERAL Horizontal ducts
27 Aluminium ducts- rectangular- 137-B9 Attachment to structure " .. 5R
constructional requirements .. 63 140-145 Hangers ."'.',." ",.,., .. , ,, ,.. , . 59
28 Aluminium ducts - circular- 146-158 Duct supports " " .. 59-.60
constructional requirements . 64
29 Protective finishes for ductwork " 711 159-160 Vertical ducts "" ,,, . 61
30 Protective finishes for supporting
members, etc , , . 71 GENERAL
161-166 Fire dampers .. " " , 66·67
167-16R Flexible joint connections " "" 69
I'urt EI"hl AI'I'ENIJICES
31 Air Icakngc ratcs , ,., . 74 APPEN[)JCES
32 Recommcnded lest pressures (with 169 Permitted leakage at various
leakage rntes) .. 77 pressures .,., ., .. ,.. "., .. , , " . 75
~U Recommended duct identification . 80 ·170 Leakage as percentage of airflow., . 76
.14 Examples of furlher identification 171 Typical leakage test apparatus .. 78
synlhols " , . RI 172 Example of duct identificRtion ~ymbol RI
7
PREFACE
In our rapidly changing environment, engineering specifications need
frequent reassessment. The specification DW/141 (published in 1977) was
no exception.
This new specification DW/142 in no way minimises the widespread
acceptance of its predecessor as the yardstick for the manufacture and
installation of ductwork. Constructional principles have changed little, but in
order to meet the needs of designers, a medium-pressure class has been
introduced. Further, the requirements of energy-conscious users have
necessitated the introduction for the first time of performance levels in terms
of air leakage for all classes of ductwork.
The establishment of such leakage limits does not imply that all installed
ductwork needs to be pressure tested. This new ~pecification if
conscientiously followed during construction and erection will produce low-
leakage ductwork and will in general obviate the need for costly site testing.
The Duct Work Group of HVCA has for well over twenty years been
engaged in the compilation of specifications for the construction and
installation of ductwork. The principles underlying this work have ever been
that the client should obtain a reliable product, made in accordance with the
best technology available at the time, and that the specification sbould make
it possible for good ductwork to be made by tbe small firm using traditional
methods as well as by tbe large firm using computers and automated
machinery. I believe that we have succeeded in these aims, and the evidence
to support that claim is to be found in the growing acceptance and status
worldwide of the HVCA's ductwork specifications.
I would like to emphasize an important point. Just as OW/142 throws more
responsibility on the ductwork contractor, so it does also on the designer to
specify his requirements in greater detail than he has in many instances in the
past, for both technical and contractual reasons.
It was a conscious policy of the Executive Committee of the Duct Work
Group to consult widely in the compilation of DW/142, and the Drafting
Panel therefore included not only representatives of ductwork contractors,
but also of general mechanical services engineers, the hospital authorities,
consulting engineers and of the industry's research association. A large
number of other individuals and firms were consulted on specific matters.
Our thanks are due to them for their interest in the work and for their
valuable contribution to making this new ductwork specification the
outstanding work that it is.
My special thanks are due to Mr. W. R. Cox, our technical consultant,
and to Mr. J. M. Paynton, the Secretary of the Duct Work Group. Together
they have reduced to order a vast amount of raw material. As before,
Mr. Paynton has been responsible for the planning, typography and design
of the book itself.
R. J. Pitt,
Chairman, Executive Committee,
Duct Work Group, 1981/82
FOREWORD
Since the publication of ductwork specification HVCA a series of tests designed to establish norms
DW/141 in mid-1977, the need for e"ergy co",- for the ~ypes of longitudinal seams and cross joints
servation has been universally recognised, and in included in DW/141, and this work confirmed that
respect of the HVCA ductwork specification this the leakage limits proposed by EUROVENT
!Jas been expressed in an emphatic demand from could be accepted for ductwork manufactured and
many quarters for ductwork with a known rate of erected to the requirements of DW/142.
air leakage. This new specification therefore pro- The leakage limits for EURQVENT classifi-
vides leakage limits for all the ductwork covered cations A, Band C, as set out in their Document
by it. 2/2 (Air Leakage in Ductwork), have therefore
Enquiries among designers have shown that the been adopted for the low- and the medium- and for
classification of ductwork used in DW/141 no the high-pressure Class C classifications in
longer accords with practice. as the low-pressure DWjl42. Document 2/2 has no standard for a
specification was being used for systems in part of leakage class equivalent to our Class D, for which
which maximum operating pressures exceeded 500 DWjl42 retains the leakage limits used in DW/141
Pa, and operating pressures above 1500 Pa were for high-pressure ductwork.
being avoided because of high energy cost. The The new range of pressures required further
classifications in DW/142 have therefore been ex- investigation of the rigidity of cross joints and stif-
tended and now cover constructional require- fening. By using the res.ults of tests carried out in
ments and leakage limits for low-, medium- and 1966 by the then Heating and Ventilating Research
high-pressure ductwork, with the high-pressure Association (now BSRIA) on high-pressure rec-
classification in Iwo parIs so that the standard of tangular ducts, the stiffness under operating condi-
ail1ightness can be matched more closely to the tions of all the I-section cross joints could be com-
operating pressure. pared by a relatively simple testing procedure.
Testing for air leakage remains mandatory for BSRlA carried out such tests on behalf of HVCA
high-pressure ductwork, but is not for low- and in 1980.
medium-pressure ductwork. (The testing pro- With this more precise information available,
cedure in DWjl42 now covers all the pressure the constructional tables have been rearranged to
classes. ) give the limits, in terms of duct size and stiffener
Pressure the main factor spacing', for all the pressure classes.
Pressure rather than velocity is the basis of class-
ification used in DW/142, because air leakage is Design function facilitated
almost entirely a function of pressure, and pres- The inclusion of leakage limits in relation to duct
sure, not velocity) is the main factor in determining surface area will enable the designer to allow for
duct strength and panel deflection. leakage more precisely in his calculations. This in
turn will reveal what level of airtightness is needed
Reappraisal of constructional and erection to maintain the terminal air flow. For the air handl-
requirements ing system where the ratio of duct area to air flow
The new approach described above has necessi- falls within the normal range, the pressure classifi-
tated a reappraisal of constructional and erection cation will establish the degree of airtightness, and
requirements in relation to performance under the designer will only need to specify the class. But
working pressures. where the duct area is disproportionately large in
The constructional tables in DW/141 were based relation to air flow, the designer may need to call
on practical experience, supplemented by the re- for a higher class in order to keep total air loss
sults of tests commissioned by HVCA or made through leakage within an acceptable figure.
available from other sources; and on the informa- Leakage limits resulting from the application of
tion provided by manufacturers of proprietary the formula used in the EUROVENT Document
materials. 2/2 are set out in Table 2 for the three classes of
With the introduction of leakage limits for all ductwork A, Band C, and also for D, for which
classes of ductwork, more precise information was Document 2/2 has no equivalent. These pressure/
needed on leakage from ductwork under pressure. ·Ieakage relationships are shown graphically on
In 1979 the Building Services Research and page 75, and air loss as a percentage of air flow on
Infonnation Association carried out on behalf of page 76.
10
Contractual implications of DW/l42 tion of DW/I4I and of technical developments
It is necessary for all concerned with ductwork since the latter was published.
installation to appreciate the contractual impli- In order to help the designer to provide as soon
cations of DW/I42. as possible all the information relevant to the duct-
It will serve no one's interest for the specifier to work contract, the section 'Technical Information
shelve his responsibilities by stating: 'Ductwork to to be Provided by Designer' has been lifted out of
be to DW/I42' and to leave it at that. DW/I42 has the body of the specification and transferred to a
performance levels for all the pressure bands flap attached to the front cover.
covered by it. The specifier must therefore clearly The standardisation of names and descriptions
state at what pressure level or levels the system is of duct fitting will prove of value to all concerned
designed to operate, so that the ductwork con- with ductwork design and fabrication, particularly
tractor may select the appropriate constructional the increasing number of firms using computers in
details and not incur unnecessary manufacturing their work.
costs. Further, as the leakage testing of low- and
The provisions covering hangers and supports
medium-pressure ductwork is not mandatory, the
(Part Six) have been updated and expanded to
specifier must positively state his requirements in bring this important aspect of ductwork instal-
this respect, as the additional complexity in rela- lation into line with contemporary practice.
tion to the installation process, and the significant
additional cost, of the testing operation must be The appendices on stainless and pre-coated steel
provided for by the ductwork contractor. ductwork and aluminium ductwork will prove of
DW/I42 specifies a performance level in respcct value in cases where the conditions are such to
of air leakage for the ductwork alone. It does not warrant the use of ductwork made therefrom.
and in the circumstances cannot specify a perfor- Advice on transport, handling and storage of
mance requirement for the whole of the air distri- ductwork has been included in an appendix.
bution system, as the numerous items of equip- Finally, mention should be made of the new
ment forming part of the total air distribution publication of the Chartered Institution of Build-
system are not manufactured by the ductwork con- ing Services - the Design Notes for Ductwork.
tractor, who frequently has no voice in choosing This for the first time has codified the available
such equipment or knowledge of or coptrol over its information on duct design, and is a worthy com-
air containment characteristics. plement to the practical constructional and install-
The ductwork contractor will therefore usually ation provisions in DW/I42.
have fulfilled his obligations if he is able to demon-
strate that air leakage from the ductwork is within
the limits relevant to the pressure class.
General updating
In preparing DW/142, the opportunity has been
taken to incorporate modifications and additions J. H. G. Gardner,
arising from the experience gained in the applica- Chairman, DW/ I42 Drafting Panel
Notes
In this document:
(1) The expressions 'low-pressure,' 'medium-pressure' and 'high-
pressure' relate to the pressure/velocity classes set out in Table 1.
(2) 'Mean air velocity' means the design volume flow rate related to
the cross-sectional area.
(3) Reference to the air distribution system pressure relate to the
static pressure of the relevant part of the ductwork system and not
to the fan static pressure.
(4) The symbolfor litres is 'L': 1000 litres per second is equivalentto 1
cubic metre per second.
(5) The pascal (Pa) is the internationally agreed unit of pressure. The
relationship of the pascal to other units of pressure is: 500 pascals
= 500 Newtons per square metre = 5 millibars =approximately 2
inches water gauge.
(6) All dimensions quoted in this specification refer to the nominal
sizes, which are subject to the normal relevant commercial and
published tolerances.
(7) This specification includes a number of proprietary devices.
Where in respect of any such device there is divergence between
the requirements of DW/142 and the manufacturer's
recommendations for use, the former shall take precedence.
For example, some large systems could well be classified for leakage
limits as follows:
12
Part Two - Standards
7 MATERIALS
7.1 Appllc~tomly the responsibility of the d!es~gll'.et t:o Y:'~c~~\te ~he
This specification applies to ductwork made from type most suitable for the conditions in which the
materials as defined below, or equal. ('Sheet' is to ductwork will be exposed. In doing so, it is recom-
be understood to include coil.) mended that the factors set out in Appendix G
7.2 Zinc-coated steel should be taken into account. In this connection,
regard should be had to BS 1449: Part 2, which
7.2.1 Ductwork will normally be made from includes stainless steel sheet and strip.
hot-dip galvanized sheet to BS 2989, Grade Z2,
coating type, or equal. If this is not available, 7.5 Pre-coated steel
alternative types are: I f the designer for aesthetic or other reasons speci-
7.2.2 Hot-dip galvanized sheet to BS 2989, fies the use of pre-coated steel for the ductwork, he
Grade Z2 or Grade Z3, with iron-zinc alloy should consider the availability of the material and
coating type IZ.l00 or IZ.I80, or equal. the restrictions on fabrication methods - see
AppendixH. .
7.2.3 Cold-reduced sheet to BS 1449, Grade
CR4, having a zinc coating applied by electro- 7.6 Aluminium
plating (coating thickness 2.5 microns), or Where aluminium sheet is specified, it will be the
equal. responsibility of the designer to indicate the type
most suitable for the conditions to which the duct-
7.3 Blacl\ steel work will be exposed. In so doing, regard should
Where black sheet is specified, it shall be cold- be had to BS 1470 for aluminium sheet and BS
reduced steel sheet to BS 1449: Part 1, Grade CR4 1474 for aluminium section. (Sec Section 20 herein
GP, or equal. for constructional requirements for ductwork
7.4 Stainless steel made from aluminium sheet, and Appendix J for
Where stainless steel sheet is specified, it will be some general notes on the material.)
14
Pa.rt Three - Redangular Duds
The figures inside the boxes represeNt the surface area 0/ the ducts, itf square metres per metre length
15
Pard Three - Rec!angukw Ducts - continued
16
longitudinal seams Fig. 4 Button punch snap lock seam
Alternative
For pennitted fastenings (types sealant locations
and spacing), see Table 10 (page 21)
---.."""t
Note. -This
seam is accept-
able For use
on low- and
medium-pressure
docts only
------.------.----.--------------1
Fig. I Grooved seam Fig. 5 Standing seam (internal or external)
Minimum height 15 mm
-UJ-
Alternative
sealant Fastening
'"'"'''"'~
1--.----------------1----------------1
Fig. 2 Grooved corner seam Fig. 6 Capped standing seam (internal or
external)
Minimum height 15 mm
- - I I I I L Fastening
Alternative
sealant
locations
~ -----n i
I"-sealant
I
Alternative
sealant
locations
Note. - This seam is acceptable
for use on low- and mediuTll-
pressure ducts only
17
COll1lstrlllctiomli Requirements - Rectangular Ducts
Table 5 LOW PRESSURE (up to 500 Pa)
Dimensions in mm
20~
Maximum duel size
(longer side) or--+ 400 600 800 llOOO _ 1250 1600 3000
length of stiffeners
Minimum sheel 0.6 0.8 1.0 1.2
thickness --+
Type Rating 5heet Maximum spacing between joints and stiffeners
1 ____f.___ __ 3
'-"--"-'''---'.. " _1. 5 6 7 8 9 10 JJ 12
J!l 1'5 3000 .I
..,'S"
-g,
's,
AI 55
1'5
3000
3000 2000 1600 1250
Vl A2 3000 1600
'.
1250
55 3000
-
oll
....'" 1'5 3000 2000 1600 1250 800
1000 ...................
.. ..
~ A3 55 3000 3000 2000 1600 1250 SOO
1'5 3000 1600
CI 55 3000 3000 I I
J!l 1'5 3000 2000 1600 1250
"
..,
'S C2 55 3000 3000
.....
2000 1250
0
-
1l
~
C3
1'5
55
3000
3000
2000
3000
....
1600
'
1600
1250
1250
1000
1000
1'5 3000
.............. ... " ...........
-
3000 1600 1250 1000 SOO
C4 55 3000 3000 2000 1(,00 1250 SOO
1'5 3000 1600 1250 625
...... ...... ........
, - ......
JI/51 55 3000 3000 1250 (,25
1'5 3000 2000 1600 1250 625
~ ...... - .. -........ . ·1 .. ·
J2/52
~"'"
.:;:
55 3000 3000 1600 1250 625
Vl
1'5 3000 2000 1600 1250 1000 SOO
J3153 I· ......55
..... I·
oll 3000 3000 ZOOO 1600 1250 SOO
J!l
"
'S 1'5 3000 2000 1600 1250 1000 SOO. .... SOO
.... J4/54 55
.---"
3000
...... 1-
3000 ZOOO 1600
..
1250 1000
I'" ...
800
1:1
.."
OJ)
G:; J5/55
1'5
. -.
3000 ZOOO 1600 1250 1000 SOO
.....
SOO
. .-.
SOO
. .... i····
625
.. ---
55 3000 3000 ZOOO 1600 1250 1000 S(lo soo SOO
1'5 3000 2000 1600 1250 1000 SOO SOO Soo SOO
. . ....... --
J6/56
-
Notes
In the constructional tables 5 to 8:
(1) The joints and stiffeners have been rated in terms of duct longer side and maximum spacing - see 9.6.1 for
joints and 9.7.1 for stiffeners.
(2) In Col. 3:
'1'5' = plain sheet;
'8S' = stiffened sheet, by means of: .
(a) beading at 400 mm maximum centres: ur (b) cross-breaking within the frame formed by joints and/or.
stiffeners: or (c) pleating_
18
Constructional Requirements - Rectangular Ducts
Table 6 MEDIUM PRESSURE (up to 1000 Pa)
Dimensions in mm
(longer side) or -> 400 600 800 1000 1250 1600 2000 2500 3000
length of stiffeners
Minimum sheet
0.6 0.8 1.0 1.2
thickness->
Type Rating Sheet Maximum spacing between joints and stiffeners
1 2- 3 - .
4 5 6 7 8 9 10 II 12
~
c PS 3000
'0
.....
-""
0
'5.
AI
S5
P5
3000
3000
en
-'"
o<:l
-"
J1
A2
A3
SS
P5
SS
PS
.-
3000
3000
3000
3000
......
1600
:r-:r--
1250
3000 ---~600
1000 800
-1250800
Cl • m'h'
55 3000
~
c 1'5 3000
«".- .....
1600
'0 C2
..... SS 3000 3000
] PS 3000 1600
'"
0'" C3
.............. " ..
3000
5S 3000
PS 3000 1600
...... ...... " ........ .... ................
C4
55 3000 3000
P5 3000 1250 625
.......................
JIISI
SS 3000 1250 625
PS 3000 1250 1250 625
...'" J2/S2
'"c SS 3000 1600 1250 625
::.='"
Vi PS 3000 1600 1250 1000 800
. ,........."' ....... .........
o<:l J3/S3
SS 3000 3000 1600 1250 800
~
c
'0 I'S 3000 1600 1250 1000 800 800
..... J4/S4
SS 3000 3000 1600 1250 1000
1-c 1'5 3000 1600 1250 1000 800
800
800 800 625
'"
::L: J5/S5
S5 3000 3000 1600 1250
..... -......... ................,........
1000 800 800 800
I'S 3000 1600 1250 1000 800 800 800 800 625
J6/S6' ..................... --- ...... .-........ .. .............
SS 3000 30QO 1600 1250 1000 -800 800 1100 625
(3) Limits of length of single stiffeners apply to opposed side (transverse) stiffeners and to longitudinal
stiffeners: also to girth stiffeners, irrespective of corner treatment.
(4) With longitudinal stiffeners, maximum spacings apply both between stiffeners and from stiffeners to
duet edges. -
(5) The choice of lagging may be limited with stiffened panels.
(6) For ductwork galvanized after manufacture, see 9.8 and Table 9.
19
CIOUIlS[lrI!JlcliiOllllilll 1Q(eqllirements - RectalllgullaJr D!!cts
Table 7 HIGH PRESSURE (up to 2000 Pa)
Dimemijons ill mm
J4/S4
PS/SS
PS/SS
3000
3000
1250
1250 1000
625
SOO 625
20
9.8 Ductwork galvanized after manufacture by electro-galvanizing, Sherardizing, cadmium-
Table 9 (which is applicable to the low- and plating, or other equal and approved finish.
medium-pressure classes only) sets out the recom- 9.9.4 Self-tapping screws
mended sheet thicknesses and stiffening for duct-
Self-tapping screws, while not recommended,
work galvanized after manufacture. (See also
are acceptable in circumstances in which the use
Appendix F.)
of other types of fastening is not practicable.
Table 9 Ductwork galvanized after manu- 9.9.5 Weldlngofshcct
facture (low- and med. I>ressure The suitability of welding for sheet-to-sheet
only) fastening will be governed by the sheet thick-
Recom- Fig. 33 Fig. 44 Maximum ness, the. size and shape of the duct or fitting and
Maximum
duct size mended joint stiffener spacing the need to ensure airtightness. Welded joints
(longer sheet rating rating for joints! shall provide a smooth internal surface and shall
side) thickness stiffeners be free from porosity. Distortion shall be kept
]
to a minimum.
2 3 4 5
A reas where the galvanizing has been damaged
mm mm mm mm mm or destroyed by welding or brazing shall be suit-
400 1.2 D S2 3000 ably prepared and painted intanally and exter-
nally with zinc-rich or aluminium paint.
1000 1.6 J4 S3 1250
10 PLANT CONNECTIONS
1600 1.6 J5 S4 800 10.1 Dennitlon
2000 1.6 J6 S5 BOO The term 'plant connection' refers to the sheet
metal enclosure joining the components of an
9.9 Fa.tenlngs air handling assembly and connections between
9.9.1 Permitted types and maximum centres the assembly and the ductwork system.
Tables 10 sets out the permitted fastcnings and 10,2 Constructional requirements
the maximum spacings for low-, medium- and The maximum operating pressure of the plant
high-pressure rectangular ducts. All duct penc- shall determine which constructional require-
trations shall be sealed. ments and leakage limits are applicable to plant
9.9.2 Rivets connections.
Manufacturers' recommendations as to use, Where access to plant requires entry into the
size and drill size are to be followed. Rivets duct, a floor plate connected to the stiffeners
resulting in an unsealed aperture shall not be should be included so as to prevent local over-
used. loading of the sheet metal. If·local conditions
9.9.3 Bolt. and nuts require heavier construction, the designer
Bolts and nuts shall be of mild steel, protected should specify appropriately.
21
P,m Three - Rectangular Ducts - continued
II and 12
0.8 800 25 mm angle 1600 1600
30 mm angle 1600 2000
II and 12
0.8 1000 25 mill angle 1250 1250
301010 angle 1250 1600
1250 II and 12
1.0 30 10m angle 1000 1250
1600 I I and 12
1.0 800 800
! 30 mm angle
-
- --' •• _ _ 0 • • _ _ • • • _,.
-_._._-_._._--------_._-------_.,------
22
---,.. .._-----
,
mm mm mOl mm mOl mm mm
a
~
Beading (may also
be along the
duel)
~~/
~ ... -
Cross section
b
----.....--....
Cross section
23
Part Three - Recttmgular Ducts - continued
Fig. 9 Piain
Alternative sealant locat~ns .. 7stening
I I
I
I .. Low
I
I
- Al Medium
High
Fig. 10 Adjustable
~
Alternative sealant lo~tio~ Fa~tenjng
;
I ,,I I
Low
, - Al Medium
J~
I
High
,I
,
'/
1
Fig. II Angle reinforced
(opposed sides)
25 x 3 A2 Low
Fastening
\
I"
Alternative sealant locations
Applic"ble only where
I , duct shorter side is less
I
I th"n 400mm
F"slling
,,
I
I
I
30x4 A3 Low
,
I
Medium
\
permissible if provided
" ,, with rigid corners
, ""
,,, """
,
,, ,, 30x4 A3 Low
"" , Medium
L -.JI
24
Socket and spigot joints - corners and junctions
Fig. 14 Groovedcornerseam
25
SClI!:!ke1l: alllU<Ji spigot joints - corners and junctions (continued)
__ Fastening
.f .~,-
--,
1- . _
26
Socket and spigot joints - corners and junctions (continued)
(Notes
to Fig. 17 Fastening.
also apply)
27
Type
Thick-
Rating
Pressure Notes
ness classes
~~
lock seam, see Fig. 27.
For folded corner detail,
see Figs. 28 and 29.
Sealant
Fig. 24 Angle-reinforced
double standing 0.8 Used with 'C' cleat or standing 'C' cleat
r-
hemmed '5' cleat with: on opposed sides. May be used on all
25 x3 C3 Low fOUf sides if fixed to duct by mechanical
angle fasteners at 300 mm maximum centres.
For corner details of'S' cleat,
H 40x4
C4 Low see Figs. 27,29 and 31.
Sealant angle For intersection with grooved seam,
se'l~ see Fig. 26.
28
Cleated cross joints - corners and junctions
Fig. 25 'C' cleat with grooved seam Fig. 26 ·s· cleat with grooved seam
Sections cutaway Sections cut away
to show assembly to show assembly
Applies aiso
to all the Applies also to
standing '5' standing 'C'
cleats cleats
•
Fastening
",
(c)
Fig. 28 'C' cleat with folded corner Fig. 29 '5' cleat and 'C' cleat with folded
corner
Cleats cut back
to show duct Cleats cut back
treatment to show duct
treatment
1
Applies 1I1flO
to all the
For corner standing'S'
treatments, cleats For corner
see Fig. 27.
treatments,
see Fig. 27.
29
Cleated cross joints - corners and junctions (continued)
,....----' ,---------------------_.
Fig. 30 Standing 'C' cleat
(treatment for three corners;
for fourth corner; see Fig. 31) Fastening,__
'j.
Applies also to a combination
of standing and plain 'C' cleats
Corner sealing
dip between ____
1-- "l-
I
Fu:;tening
~I
Fig. 31. Combination of standing 'C' cleat Fig. 32 Standing 'C' cleat
and IS' cleat (alternative corner treatment to Fig. 30)
Flunges of 'C' "'-
deats extended
and fastened
togetncr
Fastening
Cmner sealing --"!-
clip inserted
inlO 'C' cleat
and fastened to
'$'cleat ~
f
i- T
Fastening
Applies also to all
the standing 'S'
cleats
'1' .?I
30
Flanged cross joints
Fastening
I \Fastening
r------------f-----!---------+-----------I
Fig. 34 Reinforced flange Corners of flange
cleat with 'C' cleat cleats extended to
provide bolted
Low
40x 0.8 13 Medium
corner
5)
Gnskelor
--y.J :
,. . :
/scnlant '
i
'··~1
'~:·':·
FEl!ltcning l 0
"-....:.'
\
Allemntivc ... _ -0'
SO
',iI'Altcrnntivc
~
J
1(
I'
':
I
:
I
I
, r""""1
: . I'
',_
Cleats cut
back to show
assembly
31
Flanged cross joints (coll/inued)
Low
25 x 0.8 J2 Medium
Fastening
I
Sealant
t
Gasket Sealant
Low
24 x 1.6 J3 Medium
Low
25 x 0.8 J2
Gasket
Medium ....
tt
Alternative
sealant
locations
,\
Alternative
sealant
locations
Corner piece
Fig. 40 Slide-on flange with _____ locked in
integral sealant ..---- position by
26 x 0.9 Jl Low ~ indenting
Medium flange section
32
Flanged cross joints (continued)
Type Di.me~
Slons
Rating Pressure
classes Notes/corner treatments
1---------1-
Fig. 41 Slide-on flange
20 x 0.8 J2
Low
30 x 1.0 .J3
Medium
40 x 1.25 .14
High
Alternative A Iternlltive 40 x 1.25 • J5
./<, ,
scalant sealant For duct sides
locations locations
.
Flange secti~""";/ / / ':'
over 4(X) mm,
intcnnediate
fastened
to duct
(' ~. , , cleats are
required at
/~
Fastening Gasket
'\Fastening
i
I.,
400mm
maximum
spacing
Corner section
Fig. 42 Slide-on flange fastened to
flange sections
20 x O.H J2
30 x 1.0
Low
J3
Medium
Flang~-
40 x 1.25 14
40 x 1.25 . . J5 High
fastened ']
to dUCI
For duct
sides over _ .
400 mm.
intermediate
clamps are
/
PUl'itcnlng
25 x 1.0 13 Low
required at
4lKJ mm maxi-
mum spcdng
Corner piece
fastened to
flange cleats
25 x 1.0 • 14 Medium
~(:::::--;:;_"'~1 Gasket
Alternative
sealant o
locations
I
33
Pari Three - Rectangular Ducts - continued
Single stiffeners
Dimensions and ratings
Section H Thickness Roting
mm mm
Fig. 44 25 3 S2
lL
J I
r--H----l
I
30
40
50
60
4
4
5
5
S3
S4
S5
S6
Fig. 45 25 1.6 SI
T~t\
30 1.6 S2
H J_ 40 1.6 S3
J 50 2.0 S4
Fig. 46 20 1.6 SI
Fig. 47
JL
,
', + - - - - 4 0 -I
I
25
35
40
15
1.6
1.6
2.0
1.2
S2
S3
S4
SI
T 20 1.2 S2
r 25
40
50
1.6
1.6
2.0
S3
S4
S5
Fig. 48
20 0.8 SI
30 1.0 S2
40 1.2 S3
TL
Fig. 49
25 0.8 SI
J
'--~---:::-:--:-::--:-:-:-----:----::.:""---:-'--C--'-:---:'-:------:--':-:---::-:-'---
Note - FIgs. 48 and 49 are notIOnal profIles of sectIons Sllllable for use as mtemledIate stIffeners
.....----------------_.
Fig. 50 Tie rods (alternative methods)
11ucluk:<.l nxl
sc:curctl by nUl
NOI<>-Tie rods illustrated in Figs. 118 to 120 (page 52) are also suitable.
34
II FITTINGS For single-skin vanes, the maximum length be-
11.1 Standardisation of flttlnllS tween supports shall be 615 mm, and for double-
The names and descriptions of rectangular duct skin vanes the maximum length between supports
fittings as set out in Table II are recommended for shall be 1250 mm.
adoption as standard practice, as being in the inter." The recommended minimum number of turning
csts of designers, quantity surveyors and ductwork vanes is given by the formula:
contractors, and of those using computers in duct- I.5W
work design and fabrication. N 0.= -1'- (see Fig. 55)
Bends are designated as 'hard' or 'easy', and these
terms as used herein have the following meanings: An inner face radius of 50 mm is commonly used,
'Hard' signifies rotation in the plane of the and Table 12 gives the minimum number of such
longer side of the cross section. vanes for the standard widths of rectangular ducts
'Easy' signifies rotation in the plane of the set out in Table 3.
shorter side of the cross section. 11.6 Twin bends
An example illustrating these terms is given in Fig. For examples of twin bends, see Figs. 56 to 58.
51. Turning vanes in twin bends in which the widths of
-----------_. the straight section and branch differ shall be set so
that the leading and the trailing edges of the turn-
Fig. 51 Bends - examples of 'hard' and
-easy' ing vanes are parallel to the duct axes.
11.7 Branches
A branch should be taken off a straight section of
duct, not off a taper. Branches should be con-
nected to the main duct as follows:
I 1.7.1 Branches for low- and medium-pressure
ducts
Connection of branch to duct may be by cleats,
rivets or bolts, and sealant shall be used be-
tween duct and branch.
Hard
11.7.2 Branches for high-pressure duct.
Ducts shall be stiffened as necessary to take the
branch connections, and the joints made by
rivets or bolts, with sealant between duct and
Easy branch.
11.7.3 Welding
As an alternative to the methods described in
11.7.1 and 11.7.2, branch connections may be
1l.2 General constructional requirements continuously welded.
The minimum metal thicknesses specified in Table 11.8 Change shapes
4 apply to duct fittings. In all cases the larger
dimension shall determine the sheet thickness and Where a change shape is necessary to accommo-
stiffening. Where fittings are to be galvanized after date the duct and the cross-sectional area is to be
manufacture, the requirements of Table 9 will maintained (Fig. 72), the slope shall not exceed
apply. 22';'° on any side. Where a change i" shape in-
cludes a local reduction in cross~sectional area
11.3 StllTeners (Fig. 73), the slope should not exceed 15° on any
The flat sides of fittings shall be stiffened in accor- side and the reduction in area should not exceed 20
dance with the construction tables 5 to 8. On the per cent.
flat sides of bends, stiffeners shall be arranged in a
II .9 Expansions and contractions
radial pattern, with the spacing measured· along
Where these are required, an expansion shall be
the centre line of the bend.
made upstream of a branch connection and a con-
1I.4 Splitters traction downstream of a branch connection. The
Splitters shall be attached to the duct by bolts or slope of either an expansion or a contraction
mechanically-closed rivets (or by such other fixing should not exceed 22 '/2° on any side. Where this
as can be shown to be equally satisfactory) at 1()() angle is not practicable, the slope may be increas-
rom maximum spacing. ed, providing that splitters (Fig. 68) are positioned
to bisect the angle between any side and the centre
11.5 Turning vanes
line of the duct.
Square bends shall be .fitted with turning vanes,
which shall be securely attached at each end either I 1.10 Sealant
to the duct or to internal runners and the runners Sealant shan be used in all longitudinal seams and
fastened to the duct by mechanically-closed rivets cross joints of fittings. Sealant shall be to the re-
or bolts at 150 mm maximum spacing. quirements of Section 27.
35
Table 11 RECTANGULAR DUCT FITTINGS-
STANDARD NAMES AND DESCRIPTIONS
Name and description Fig. No.
J 2
Bends
Short radius- 'W' up to 300 mm all angles .. .. .. .. .. .. .. .. .. .. .. 52(a)
Short radius- 'W' over 300 mm (all angles) .. .. .. .. .. .. .. .. .. .. 52(b)
Medium radius (all angles) .. .. .. .. .. .. .. .. .. .. .. .. .. .. 53
Long radius (all angles) .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 54
Square (with turning vanes) .. .. .. .. .. .. .. .. .. .. .. .. .. .. 55
Twin radius- equal (all angles) .. .. .. .. .. .. .. .. .. .. .. .. .. 56
Twin radius - unequal (all angles) .. .. .. .. .. .. .. .. .. .. .. .. 57
Twin square (with turning vanes) .. .. .. .. .. .. .. .. .. .. .. .. .. 58
Branch (all angles) .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 59
Branches
Rectangular or circular (90°) .. .. .. .. .. .. .. .. .. .. .. .. .. .. 60
Rectangular or circular (all angles other than 90°) .. .. .. .. .. .. .. .. 61
Shoe (rectangular or circular) .. .. .. .. .. .. .. .. .. .. .. .. .. 62
Shoe (high pressure) - rectangular .. .. .. .. .. .. .. .. .. .. .. .. 63
Offsets
Angled .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 64
Mitred .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. " .. 65
Radiussed .. .. .. .. .. .. .. .. " .. .. .. .. .. .. .. " .. 66
Tapers
Concentric (without splitters) .. .. ..
.. " .. .. .. .. .. .. " .. 67
Concentric (with splitters) .. .. .. .. .. .. .. .. .. .. .. .. .. .. 68
Eccentric .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 69
Transformations
Rectangular to circular (concentric) .. " .. .. .. .. .. .. .. .. .. .. 70
Rectangular to circular (eccentric) .. .. .. .. .. .. .. .. .. .. .. .. 71
Change shapes
Cross-sectional area retained .. .. .. .. .. .. .. .. .. .. .. .. .. .. 72
Cross-sectional area reduced .. .. .. .. .. .. .. .. .. .. .. .. .. .. 73
36
Part Three - Fittings for rectangular ducts
For sealing requirements, see Sec. 11.10 (page 33)
Double skin
vane
I~,
radius - 'W' over
300 mm (Splitters
not applicable to
bends under 45°)
S~ul .."al plan
Splitters should be
positioned so that the r/W Table 12 Number of turning vanes
ratio for each air passage r-50mm
Example with a minimum is preferably above t .5,
throat radius (100 mm): with a minimum of 1.25. Minimum number of
Width of duct turning vanes:
'W' double or single-skin
W Number of
Rplittcnl J 2
mrn
mm
Up to 300 None 250 6
Over 300
300 9
up to 500 1 400 12
500 15
Over 500 600 18
up to 1000 2
800 24
Over 1000 3
Fig. 59 Branch
(all angles)
I I
y-./'l ---- -- I
l-w-J
·SpUUers in
accordance with Figs.
52(a) and (b)
"
\:S
37
Pcm Three - Rectangular duct fillings - continued
Branches Tapers
... .. ,
Fig. 60 90° branch r---Ol..--....- ~ ~
,,,
t__t
(rectangular or ,
eircular) Fig. 67 Concentric- j"' ,,
without splitters f "';>
,
'-,4--==,-- :,
,,
,
..... ~J
with splitters
.,-r ~
-----
.J
,r
••
Branch duct
width (W)
Dimensions
(A)
·:••,
..........
mm mm
."T""'------,
, .........,
Up to 300
200 75
400
100
125
Fig. 69 Eccentric ~
,;>
L....
.:
•
-t."
" 600 150 Fig. 62 Shoe branch 22¥lOmax. r
Over 600 200 (rect. or eire.) ••
........•,
Backing 1- -1
Straps
./ Transformations
Main duct Flat bar Fig. 70 Rect. to eire.
opening backing
-eccentric
(longer side) straps
r:::
...... ~_
mm
Up 10600 None
!.=::::::J ["'S
Over 600 up hHernal Fig. 71 Rect. to eire.
to 1000 only Fig. 63 Shoe branch - concentric
Over 1000 Internal and (rectangular)-
external
high'pressure
.....1
;
;r 30'
m.x Fig. 65 Mitred
L...,'--_-<..
,
····'1
';r
"'-_-'.....1
f·····
;r
L.... Fig. 66 Radiussed
\00
mm
min.
Fig. 73 Cross,sectional
I.- , .. ......L area reduced -J
38
Part four - Circular Duds
12 STANDARD SIZES 13 CONSTRUCTION
12.1 Tho size ranges of circular ducts are in use in 13.1 Spirally-wound ducts
the UK: ISO and Imperial. For design purposes The minimum constructional requirements set out
the same surface area, flow rate and frictional in Table 14 are common to the full range of pres-
resistance may be used for each corresponding sures covered in this specification. The method of
size. forming the duct and the specified cross joints
Col. 1 of Table 13 sets out the standard sizes accep- make additional stiffening unnecessary.
ted by the International Standards Organisation 13.2 Straight,seamed ducts
for conversion into an ISO standard; and Col. 2 Table 15 gives the differing minimum require-
gives the nearest Imperial size equivalent. ments according to the pressure classification. All
straight-seamed circular ducts shall be manu-
factured with a swage not less than 40 mm or more
than 75 mm from each end, unless a reinforcing
Table 13 Circular ducts - standard sizes angle ring is fitted.
-- Nearest Surface
If straight-seamed circular ducts are required to be
galvanized after manufacture, the sheet thickness
ISO standard Imperial area per used for such ducts shall be a minimum of 1.2 mm,
sizes (nominal size metre length irrespective of the size of the duct; and cross joints
diameter (nominal (ISO sizes
only) shall in all cases be angle flanged.
diameter)
13.3 Longitudinal seams
1 2 3
13.3.1 Spirally-wound ducts
mm mm Sq. metres The grooved seam used in spirally-wound circu-
lar ducts, provided it is tightly formed to pro-
63 64 0.198 duce a rigid duct, is accepted as airtight to the
71 76 0.223 requirements of all the pressure classifications
80 - 0.251 covered in this specification, without sealant in
90 89 0.283 the seam.
100 102 0.314 13.3.2 Straight-seamed ducts
112 - 0.352 The longitudinal seam for straight-seamed cir-
125 127 0.393 cular ducts shall be either the grooved seam
140 133 0.440 (Fig. 74), continued to the extreme end of the
160 152 0.502 duct and sealed during manufacture; or a con-
180 178 0.566 tinuous butt or lap weld, provided this gives a
200 203 . 0.628 smooth internal finish .
224 229 0.704 13.4 Cross joints
250 254 0.785 13.4.1 General
280 279 ·0.880 Cross joints for circular ducts, both spirally-
315 305 0.990 wound and straight-seamed, are illustrated in
355 356 1.115 Figs. 75 to 86. They include several proprietary
400 406 1.257 types and the limits of use in terms of diameter
450 457 1.413 and pressure classes are noted against each.
500 508 1.571 13.4.2 Sealant/welding
560 559 1.760 Sealant shall be used in all circular duct cross
630 610 1.979 joints, whether the ducts are spirally-wound or
710 711 2.229 straight-seamed. Alternatively, such cross
800 813 2.512 joints shall be continuously welded. (However,
900 914 2.826 the synthetic rubber gaskets incorporated in
1000 1016 3.142 joints Figs. 80 and 81 are regarded as providing
1120 1118 3.517 an effective sealant for those joints.)
1250 1270 3.927 The use of chemical-reaction tape or heat-
- sh,rinkable band shall be regarded as an
Note. The above sizes are subject to the normal manu- effective sealant in respect of the socket and
facturing tolerances. spigot joints illustrated.
39
Part Four- Circular Ducts - continued
13.4.3 Socket and spigot joint without gasket Where the joint is made by enclosure, such as
Where the joint is made with sealant, the ends with a chemical-reaction tape, heat-shrinkable
to be joined shall either be carefully cleaned band or strap, or other approved material, the
with a suitable solvent to a length of 100 mm and maker's instructions shall be followed.
sealant applied to the spigot so as to givea joint 13.4.4 Flanged joints
length in accordance with Table 18, or, sealant The duct end shall be turned up approximately
shall be applied in the alternative position indi- 10 mm. Alternatively, the duct shall be continu-
cated in figures nos. 75, 76, 77, 82, 83 and 84. ously welded inside the angle flange. Sealant or
Use of excessive sealant shall be avoided. The gasket shall be used between the angle flanges.
joint shall be held in place by a minimum of
13.4.5 Welded joints
three permitted fastenings.
The limitations for welded joints are given in
13.5.5.
1 2. 3 4
mm mm mm
40
13.5 Fastenings contractors, and of those using computers in duct-
13.5.1 Permitted types and maxmum centres work design and manufacture.
Table 16 sets out the pennitted fastenings and The requirements for circular duct fittings apply
maximum spacings for low-, medium- and high. throughout the pressure ranges covered in this
pressure ducts. All duct penetrations shall be specification.
sealed. 14.2 Nominal diameters
13.5.2 Rivets The nominal diameter (see Table 13) is the size
Manufacturers' recommendations as to usc, used for design and ordeling. With socket and
size and drill size are to be followed. Rivets spigot joints, care should be taken to ensure that
resulting in an unsealed aperture shall not be the dimensions of the ducts and filtings are cor·
used. rectly related, so that the joint can be effectively
13.5.3 Bolts and nuts sealed.
Bolts and nuts shall be of mild steel, protected 14.3 Sheet thickness
by electro-galvanizing, Sherardizing, cadmium- Sheet thicknesses for circular duct fittings (deter-
plating or other equal and approved finish. mined by the largest diameter) shall be not less
13.5.4 Selr·tuPllrn~ scrows than those quoted in Table 17.
Self-tapping screws, while not recommended, 14.4 Socket and spigot joints
are acceptable in circumstances in which the use
The minimum length of spigots are set out in Table
of other types of fastening is not practicable.
18. Fittings larger than 510 mm diameter shall have
13.5.5 Welding of sheet swaged ends.
The suitability of welding for shect-to-shcet
fastening will be governed by the sheet thick- 14.5 Scaling ofjoints
ness, the size and shape of the duct or fitting and Sealant shall be used in all cross joints of fittings.
the need to ensure airtightness. Welded joints Such sealant shall be in accordance with the re-
shall provide a smooth internal surface and shall quirements of Section 27.
be free from porosity. Distortion shall be kept
to a minimum.
Areas where the gulvanizing has been damaged Table 17 Circular duct fittings-
or destroyed by welding or brazing shall be suit- sheet thicknesses
ably prepared and painted internally' and exter-
nally with zinc-rich or aluminium paint. Maximum Minimum sheet
14 FITTINGS nominal diameter thickness
14.1 Standardisation of fittings I 2
The names and descriptions of circular duct fittings
as set out in Table 19 are recommended for adop- mm mm
tion as standard practice, as being in the interests 160 0.6
of designers, quantity surveyors and ductwork
510 0.7
630 0.8
Table 16 Permitted fastenings and 1020 1.0
maximum spacings- 1525 q
circular ducts
Sheet to section
(cross joint Oanges
Type of Sheet to sheet and intermediate Table 18 Circular duct fittings-- spigots
fastening (cross joints) stiffening nanges)
Maximum Minimum length
Spirally- Straight duct diameter .. of spigot
wound seamed
I 2
I 2 3 4
mm mm
10m 10m
Fittings
Mechanically 300 mm centres 150 150
closed rivets (minimum three) 160 30
Bolts and nuts - _i' 300 315 40
Lock bolts - - 300 1525 50 I
Spot welds - - 150 Closures 25
41
Part Four - Circular Ducts - continued
.....---------.;.....------------_._-....
Fig. 14 Grooved seam
(straight-seamed ducts)
Limits of use
Spirally-wound ducts Angle Maximum Pressure
size diameter classes
~
/
I
Low
~ I Alternative
I 1020 Medium
High
I sealant
I loc.ltions
Fig. 16
-\----r-·i--·.. --\-
Socket and spigot (duct to duct) with
connector Fastening
~""
I \ .. J~!%
I Low
I
\
I
\ 1020 Medium
\ Alternative I I High
\ sealant I \
\ locations I \
\ I I \
\ I, \
\ I I \
\
\
,I
I ,
I
,
\
\
Fig. 77 Angle reinforced socket and spigot with connector
n Alternative ~
: : / position for V
':;~'ililstcning
,: ::
: I
angle.~
,_~~~.,....
._'.~ .. -. I
I
'25 x3
I ' -'~'
762 Low
I II , I \
I
I : I
:Allcrnallvl...:
'30x3 1020 Medium
I I I Isealant J 40x4 l525 High
I I I IloCUII(lnS I
42
r--- -.------------,--- . -.,
Limits of use
Spirally-wound ducts
Angle Maximum Pressure
size diameter class
Fig. 78 Angle flanged (external)
~ii '~~i~\
*30 x3 1020 Medium
40x4 1525 High
I
I "
Sealant \\ Sealant : :Turn up \: Sealant
\ :lor gasket: : minimum:: \
,,:] : :oflOmm:: \
\ n :: ii " 'Where flanged joints
-\- -+---_. ~{-- -~" --- -
!-----.------
,
'" 11
"
._--;
, I I I \
{-__-!-
are specified
.JI -!
Fig. 79 Angle flanged
(Internal)
' sca~tl
A Iternauvc I I '
[.
"..' ..J]J ....-'lloeations
OCUtl?~S~ . :~ /61' _
"b Allemative
sealant
I S-Fllst~ning1/' .~'"~~r\ I
,,(
I
Low
:, ~ Fastening
*30x3
40x4
1020
1525
Medium
High
\ I Sealant
lor gasket
\ ,I
I
-
double gasket
-- -tI--I-K.-\~
I I
-'-HI - I - -- - - ,
\
tube
I Faste~ing '1'
~~'~::::::r::s5ii~--'
\ I I Not suit- 1020 J Low
, \
I
I
I
able for
helically
I Medium.
I \
I \ I beaded
I \ I spiral
~---+- r- ~-
tube
r-\_\_\..l,\r-,- -1----\.\-\
l - - - - ' - - - - -_ _,_ _..:-_ _- - l I -_ _.l--_ _..J
43
Pari Four - Circular Ducls - cominued
Limits of use
Straight-seamed ducls Maximum Pressure
Angle
size diameter class
''l : Fastening
I 800 Low
Medium
,,
I
I 1 High
\ \
!
--if-----'--- - I
\
- - - \\ -
I Low
Medium
High
\
Fig. 84 Socket and spigot - angle reinforced
! i \
Alternative . Fastening
sealant ~astemng
lQcatiOns~
~~ ,I "25 x3 762 Low
'30x3 1020 Medium
,I I I '/
: I I
40x4 1525 High
, I I
: I I
, , I
I I ' 'Only where angle ring
I
'25 x3 762 Low
/Fastening
~';':
: Gasket I
i\
I
I
T'!r? up
I
30x3
40x4
1020
1525
Medium
High
I' I I mlOimum
I , ,of 10 mm 'Only where flanged joint
44
-----------_.._-....-----------., Limits of use
Straight-seamed ducts
Size of Maximum Pressure
flat diameter class
Fig. 86 Flat
ring flanged
mm mm
""" ~k
Gas et
I I 25,x3 610 Low
""" "
11 Medium
30x3 1020
"" """ 40x5 1525
"""11 ""
11
II 11
- ·····1 I 11-,-,,'
1- i
45
II
Table 19 CIRCULAR DUCT FnnNGS-
STANDARD NAME AND DESCRIPTIONS
Name and description Fig. No.
J 2
Bends
Segmented - five section 90°.. .. .... .. .. .. .. .. .. .. .. .. .. .. 87
Segmented - four section 60° .. .... .. .. .. .. .. .. .. .. .. .. .. 88
Segmented - three section 45° .. .... .. .. .. .. .. .. .. .. .. .. .. 89
Segmented - two section 30°.. .. .... .. .. .. .. .. .. .. .. .. .. .. 90
Pressed - medium radius .. .. .... .. .. .. .. .. .. .. .. .. .. .. 91
Pressed -long radius .. .. .. .... .. .. .. .. .. .. .. .. .. .. .. 92
Pressed - twin radius (all angles) .. .. .. .. .. .. .. .. .. .. .. .. .. 93
Branches
Square .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 94
Angles (all angles less than 90°) .. .. .. .. .. .. .. .. .. .. .. .. .. .. 95
Conical .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 96
Bell mouth .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 97
Shoe .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 98
Tangential .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 99
Mitred .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 100
Change shapes
Concentric taper .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 101
Eccentric taper .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. !O2
Transformations
Circular to rectangular (concentric) .... .. .. .. .. .. .. .. .. .. .. .. 103
Circular to rectangular (eccentric) .. .. .. .. .. .. .. .. .. .. .. .. .. 104
Offsets
Mitred .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 105
Radiussed .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 106
Connectors
Male .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 107
Female .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 108
Closures
Plugend .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 109
Cap end .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 110
H~" -----_._---_.._..
46
Part Four - Fittings for circular ducts
For sealing requirements, see Sec. 14.5 (page 39)
.........---'----'------,-----------.......
Bends (segmented) Bends (radiussed)
(~D or ID throat radius)
I~I
Fig. 87
Segmented - five-
section 90° (also Fig. 91 Pressed
acceptable as a - medium radius
. four-segment bend) (available up to
4OOmm)
Fig. 88
Segmented -four-
section 60° Fig. 92 Pressed
-long radius
(available up to
300mm)
Fig. 89
Segmented-
three-section 45°
Fig. 90
~gmented - two-
soct~on lO°
,,
I
a separate fitting) ,......... I
I
Fig. 94 ~. A
II
: I I •
Square •, .••.J...;;::----:-:::-- I I
I I
Fig. 101 Taper- I I
• I
concentric I I
• I
...... ,),
...... ""
•
Fig. 95 • I
I
Angled-all
,,
I
I
angles other
than 90" Fig. 102 Taper- 4
II
eccentric ,
I •
I
,"--- I I
I I I
~\
: I
.,••• J..
~
..........\.) I,
:
Fig. 96
Conical Transformations
Fig. 103 Circular to
rectangular - concentric
Fig. 98
'r----r..--.,
Shoe
,,,......... .,..--- /.
.....
,"
.., ""---------~-
I I
_-.....
f I
I I
"'- ..
~~/
.........
•I
Fig. 99 4•
Tangential min Fig. 106 "
f I
, I
Radiussed ......._...J. ..... ~
Fig. 107 \
,- -----00------"
i! (, )
: ------~ ..
-----;
'00 ••• _.
Fig. 100
~- ~\
Mitred Closures
Fig. 109
Plug'Cnd
t ._---~
,,
, I
Fig. 110
Cap end
-
- --
I I
V
48
Part Five - Flat Oval Ducts
I 2 3
mm sq. metres mm mm mm mm mm mm mm mm mm mm mm
0.718 320
0.798 360 350 330 320
0.878 400 390 370 360
0.8 0.958 440 430 410 400
2.075
"':!2"
~
,.'""""
(/)
1040 1010 985 955 925 895 865 835
2.394 1120 1090 1065 1035. 1005 975 945 915
2.553 1200 1170 1145 1115 1085 1055 1025 1000
1.0 2.873 1335 1305 1275 1245 1215 1190 1160
3.192 1465 1435 1405 1375 1350 1320
3.511 1625 1595 1570 1540 1510 1480
3.830 1785 1760 1730 1700 1670 1640
•
49
Part Five - Flat Oval Duels - continued
mm mm mm mm mm mm mm mm mm mm mm
320
360 350 330 320
~
'I" 555 525
-
El
.~
1:>
880 845 825 I 790 765 735 705 680
Fig. 112
750 mm centres -
::>
"0
0
~930 900 875 I845 815 785 755
f3 I895
ettb
1-=-;:.=...1
~
1040 1010 985
975 I
865
945
835
915
Fig. 113 1200 1170 1145 111~5 1055 1025 11000
500 mm centres
1335 1305 11275 1245 1215 11190 1160
etID
1
:.= = =
--1-'-1-
I
I
1465 1435 1405 11375 1350 1320
mOl mOl mOl mOl mOl mOl mOl mOl mOl mOl mOl
320
-m
<'il
'§0 635 605 580
Fig. 115
~
c
I 715 I 690 660 630
750 mm centres
I 740
m-
Fig. 116
~
'~
I
'"
...
0
ROO
880
960
770
845
I 930
825
900
710
I 790
875
685
765
I 845
655
735
815
705
785
680
755
'or
500 mm centres
~
S
tl 1040 1010 I 985 955 925 -I 895 865 835
ettIP
i~~ ...
~
"
'l::l
0
0£3
:s!
~
1I20 1090 1065 11035 1005
51
Part Five - Flat Oval Ducts - continued
52
Table 23 FLAT OVAL DUCT FITTINGS-
STANDARD NAMES AND DESCRWTIONS
-
Name and description Fig. No.
Bends
Segmented - five-section 90" (hard) .. .. .. .. .. .. .. .. .. .. .. .. 121
Segmented - five-section 90" (easy) .. .. .. .. .. .. .. .. .. .. .. .. 122
Segmented - three-section 45° (hard) .. .. .. .. .. .. .. .. .. .. .. 123
Segmented - three-section 45° (easy) .. .. .. .. .. .. .. .. .. .. .. 124 Ii
I:
Square (hard) (rectangular body, flat oval ends).. .. .. .. .. .. .. .. 125 Ii
:1
r
Square (easy) (rectangular body, flat oval ends) .. .. .. .. .. .. .. .. 126
Square (hard) .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 127 II:1
.,
Square (easy) .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 128
1\vin .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 129
If
,I
II"
I
II
Branches
For flttinrlf: off flat rome, see rectangular
fittings, igs. 60, 6 and 62
For branches off seml-clrcular profile, see circular
fittings, Figs. 94 to 100
Tapers
Reducer- concentric .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 130
Reducer- eccentric .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 131
Transformations
Flat oval to circular .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 132
r
Offset
Mitred (hard or easy) .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 134
Coupling .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 135
Closure .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 136
m "
53
PilIB"t five - fittings for flat oval Ol!«:1l:s
For sealing requirements, see Sec. 18.1 (page 50)
li
Bends
Fig. 121
Segmented-
five-section
90'(hard)
Ie
1
-l 0.1--
Bends (ctd)
Fig. 129
Twin
Fig. 122
Segmented-
five-section
Tapers
90'(easy)
Fig. 130
Reducer-
concentric
ii;'w 18
Fig. 123
Segmented-
.three-section
45'(hard)
w, -lof-
Fig. 131
Reducer-
eccentric
~omax B
Transformations
Fig. 124 Fig. 132
Segmented- Flat oval to ."-r---,.-- A - - j
three-section circular ,~.
45'(easy) ""
.,-"-------'-----..::t==
y
8
Fig. 125 fig, 133
Square (hard) Flat oval to
(rect. body.
flat oval ends) 1 rectangu Jar
tc::::::::::d -1 0 [ -Offset
1----------1
Fig. 134
Fig. 126
Square (easy)
(rect. body,
flat oval ends)
en
r-w-j
Mitred
(hard or easy)
Coupling
Tw
8
Fig. 127
Fig. 135
rtf
Square
(hard)
_I
--I 0 I--
Closure
& CD
Fig. 128 T Fig. 136
Square (easy) o
-L
1-0-1
I-w---I
54
Part Six - Hangers and Supports
55
Pari Six - Hangers and Supports - cominued
corner cleats, are shown in Figs. 148, alld llsing ductwork. Where fire !l"cgu:~a1!frons a:lPP-~Y, approval
stirrup brackets in Figs. 149 and 150. of the relevant authority may be needed.
19.3.3.2 Circular ducts 19.6.1 Insulated ducts with vapour sealing
Table 25 gives minimum dimensions for the Where the temperature of the air within the
hanger and for the brackets. The three common duct is at any time low enough to promote mois-
methods of supporting circular ducts are; the ture penetration through the lagging and cause
Strap hanger (Figs. 151 and 153 - limited to condensation on the exterior surface of the
ducts with a diameter not exceeding 300 mm; duct, vapour sealing may be called for, and in
the half band clip (Figs. 155 and 157); and the this case the most important requirement is to
split band clip (Figs. 152 and 154). limit penetration of the seal.
19.3.3.3 Flat oval ducts The extent of any vapour sealing of ductwork,
Table 26 gives the mininum dimensions for the and the method to be used, must be clearly specl.
hanger; and for the bearer, depending on fied in advance, as follows:
whether the flat side of the duct is horizontal or Method 1
vertical. Where the risk of damage due to condensation
:. Typical arrangements for flat oval duct supports is slight, the vapour seal can be applied to the
are shown in Figs. 156 and 158. insulated duct and made good round the sup-
19.4 Vertical ducts ports to achieve an acceptable level of proofing.
The design of supports for vertical ducts is dictated Method 2
by site conditions, and they are often located to Where it is essential to keep penetration of the
coincide with the individual floor slabs, subject to vapour seal to a minimum, supports should be
a maxim,!m spacing of 4 metres. external to the insulation, as shown in Figs. 147,
Vertical ducts should be supported from the stif- 150, 154, 156, 157 and 158.
fening angle or the angle frame, or by separate The insulation and vapour banier should be
supporting angles fixed to the duct. abutted to the insulator incorporated with the
A typical method of supporting vertical rectangu- duct support. This insulator shall be non-
lar ducts is shown in Fig. 159 and for circular ducts hygroscopic and shall be capable of carrying the
in Fig. 160. The same methods are applicable to imposed load without significant compression.
vertical flat oval ducts. Typical materials are. hardwood or treated soft·
wood (in separate block form for circular
19,5 Heavy loadIngs ducts); GRP (glass.reinforced plastics); and
For ducts larger than those covered by Tables 24 to .hard rubber compounds. Some proprietary
26, or where heavy equipment, mechanical ser- systems of support for vapour.sealed ducts are
vices, ceilings or other additional load is to be available.
applied to the ductwork, supports shan be design- 19.6,2 Heat transfer
ed to suit the conditions. It is not nonnally necessary to make special
19.6 Insulated ducts arrangements for the limitation of heat transfer
Where ductwork is required to be insulated, this via the duct supports. However, there may be
must be clearly specified, so that hangers are special cases where the temperature difference
spaced to provide clearance for the insulation. justifies a heat barrier to conserve heat or to
Otherwise, supports may.be as for uninsulated prevent condensatiou.
56
Table
_. 24 Supports for horizontal ducts - rectangular
Hanger Bearing member
Maximum Maximum
Rod or Rolled steel Rolled steel Roll formed spacing
duct size studding
Flat strap . an~le channel channel of
(longer
side)
itwo~
dia.
(two) (or at)
W
section section profile
W
hanger
Hnu Hnu
1 2 3 4 5 6 7
mm mm 10m mm 10m mm mm
H W H W H W
400 6 25 x 0.8 25 x 25 x 1.5 25x25x1.5 20 x 25 x 1.5 3000
(plain or (or 25 x 3 Ilat)
perforated) (plain)
25 x 3
600 8 (plain) 25x25x3 25x25x3 25x25x 1.5 3000
30x 3
1000 8 (plain) 30x30x3 25x30x3 30x25x1.5 2500
40x 5
1500 10 (plain) 40x40x3 30x40x3 40x25x1.5 2500
40x 5
2000 10 (plain) 40x40x4 30x40x4 40x25x 1.5 2500
40x6
3000 12 (plain) According to circumstances
H = Height W = Width
J 2 3 4 5 6 7
mm mm mm mm mm mm mm
305 - 25 x 0.8 - 25 x 0.8 3000 1800
(plain or (plain or
perforated perforated)
813 8 25 x 3 30x4 25 x3 3500 2500
(plain)
1016 10 40x5 40x5 - 3500 2500
(plain)
1524 10 40x 5 40x 5 - .. 3500 2500
(phiirt)
Notes to Tables 24 10 26
(1) The dimensions included in Tables 24 to 26 are
to be regarded as minima.
(2) The maximum spacings set out in the tables
are related solely to duct weight consider-
ations. Closer spacings may be required by
reason of the limitations of the building struc-
ture or to achieve the necessary ducl rigidity.
57
Pari Six - Hangers and Supports - continued
Fig. 137
58
--------------_ _------------... ..
"
,."
"""
~ a b c
j!
. g- .
Ir~~~:
~ angle
Fig. I~J
Rolled._1 Fig. I ~5 Inverted profile
channel channel (alternatives)
Fig. 144
Profile
channel
(alternatives)
I ,, ,,
r' ,
,r -,,
-+--.. f
I I
,,,
I
,,, ,,I ,,,
,, ,, ,, ,,
I J--'
,
,
, ,
•••• _--. J;;>
I J
Fig. 146 Rectangular duct- Fig. I~7 Rectangular duct-
! plain or Insulated. Can be Insulated and vapour sealed
! vapour sealed to Method I. to Method 2.
Also applicable to nat
oval ducts.
Fig. I<18 Rectangular duct with Fig. 1~9 Rectangular duct with
corner brackets - plain or stlrnlp bracket - plain or
Insulated. Can be vapour Insulated. Can be vapour
sealed to Method I. sealed to Method I.
I
1
.«~.;~~~..,.
~ ~.~::~~~.___
_
r Flg. 150 Rectangular duct with
stirrup bracket. Insulated and
vapour sealed to Method 2.
~ 59
Part Six - General - Hangers and Supports - continued
I
Fig. 151 Circular duct with Fig. 153 Circular duct with
,, . wrap..round strip hanger - plain strip double hanger - plain or
or Insulated. Can be vapour Fig. 152 Circular duct with
split clip bracket - plain or insulated. Can be vapour sealed
_led to Method I. to Method I. (Applicable allo to
Insulated. Can be vapour sealed
to Method I. flat oval ducts)
o
---_/
Fig. 155 Circular duct with
Fig. 154 Circular Insulated duct with split clip stirrup bracket - plain or insulated.
bracket. Vapour sealed to Method 2. Can be vapour sealed to Method I.
Applies to both (Applicable also to flat oval ducts)
Figs. 156 and 157
Insulating
Insulation
'\ ~cer
~~;"'~'h....~
-:"~. ;;-;~_:,:
tJ
Insulating
vapour scaled to M.:thod 1, sec fig. 146. Insulauon spacer
\ ./
/-'- '.-.-, Ir·,'·-
"
""
"
- ----H-·-··
"""
" "
60
Fig. 159 Vertical re<:t:angularducts
h
,'
e'
,",,
"
i
:
:
I
,,
,
"r ,je-, "
I'/'J
"
0'
----,
------+;.,
.; "\
lor.ogle RS. flat
I "1
.,.
~. :
I-
I Plain or insulated. Can be vapour-sealed to
Method I. Vapour-sealing to Method 2 is not
applicable with vertical duct supports.
I,
61
20 ALUMINIUM DUCTWORK
20.1 Scope
This section applies only to aluminium ductwork stiffening requirements for circular ducts made
operating at low pressure, as defined in Table I. from aluminium, and the permitted types of cross
joint.
In general, the requirements of this spccification
for low-pressure galvanized steel ductwork also 20.6 Fa.'ltenings
apply to aluminium ductwork, subjcct to the spe- 20.6. I The types of fastening and the maximum
cial provisions set out below. spacings specified in Table 10 (rectangular) and
20.2 MaterIals Table 16 (circular) apply to aluminium duct-
work, exccpt that such fastenings shall be of
The aluminium sheet used should be chosen from
aluminium, stainless steel or monel metal.
those mentioned in Appendix J.
19.6.2 Some notes on the welding of aluminium
20.3 Constmctlon- rectangular ducts are contained in Appendix J.
Table 27 scts out the minimum constructional and
stiffening requirements for rectangular aluminium 20.7 FInishes
ducts and the permitted types of cross joint. 20.7.1 No protective finishes are required for
aluminium ductwork used indoors or outdoors
20.4 Sealant in normal atmospheric conditions. Appendix J
The sealant requirements sct out in this specifi- gives information on the use of protective fin-
cation for galvanized steel rectangular ductwork ishes for aluminium where it is considered
also apply to the longitudinal seams and cross necessary for their application.
joints in aluminium ductwork.
20.7.2 Mild steel section used with aluminium
20.5 Constn.ction - circular ducts ductwork shall be protected as specified in Sec-
Table 28 sets out the minimum constmctional and tion 28 (Table 30).
63
·_·_. _ _ • 0
----_.~-_.-
21 ACCESS OPENINGS
21.1 General designer, openings should not be larger than 1350
All access openings shall be rigidly framed, with mm high by 500 mm wide. Doors shan open
airtight covers designed so that they can be speed- against the air pressure. Both the opening in the
ily removed and refixed. Multiple set screws are duct and the access door itself should be adequate-
not recommended, and self-tapping screws are not ly reinforced to prevent distortion. A suitable seal-
acceptable, as a method of fiXing. ing gasket shall be provided, together with suffi-
cient clamping type latches to ensure an airtight
21.2 Access and inspection covers and watertight seal between the door and the duct.
21.2.1 Subject to the restrictions imposed by The latches shall have handles which can be oper-
duct dimensions, openings for aCCess should not ated from both the inside and the outside of the
be smaller than 375 x 300 mm or larger than 450 door.
x 375 mm; and openings for inspection should
have a minimum diameter of 100 mm. .For safety reasons, tbe designer sb<lUld incorporate
means to prevent personnel being trapl>cd inside
21.2.2:lt shan be standard practice to provide tbe duct, e.g. witb operating bandies both inside
access covers for the inspection and servicing of and outside the duct.
plant and equipment as follows.
21.4 Test holes fol' plant system commissioning
21.2.2.1 Fire dampers
It shall be standard practice to provide test holes,
Cover to be so located as to give access both
normally 13 mm diameter and fitled with an elIec-
to the damper and fusible links.
tive removable seal, at the follOWing locations; at
21.2.2.2 Control dampers fans (in the straightest section of duct near to the
Cover to be so located as to give access to fan outlet); at cooling coils and heater batteries
blades and linkages on ducts with diameter (both before and after the coil or battery). The
or side larger than 400 mm. In branch ducts location of these holes shall be confirmed by the
smaller than 400 mm diameter or side, designer.
inspection openings for dampers, not smaller
than 100 mm by 100 mm, shan be used, with 21.5 Access openings in Insulated duets
Wbere ducts are to be thermally insulated, it is
airtight cover as 21.1.
recommended that the frame of the access door or
21.2.2.3 Fillers cover be extended beyond the face of the duct by a
Cover to be located upstream. (Nore: measurement equal to the thickness of the insula-
Dimensions of access openings may need to tion and be so arranged that the insulation and
be changed to suit filter elements of the front finish can be 'dressed' into the frame, thereby
withdrawal type.) ensuring that the opening is not concealed and that
21.2.2.4 Cooling coils, beater hatteries and the edges of the insulation are protected from acci-
humldillers dental damage. If it is necessary to insulate the
Cover to be located upstream. access door or cover, it should be dished to contain
the insulation.
21.3 Hinged access doors
It shan be the designer's responsibility to indicate 21.6 Hand holes
on the drawings the location of any hinged access Hand hol~s to permit proper joining of duet sec-
doors required. Unless otherwise specified by the tions shall be provided at the manufacturer's dis-
64
cretion, but should be kept to a minimum and shown on the contract drawings, suitably drilled or
made as small as practicable. They shall be render- bossed and screwed to sizes given.
ed airtight with sealant and securely fastened.
21.8 Openings required for other purposes
21.7 Instrument connections It shall be the designer's responsibility to specify
Instrument connections shall be provided where the location .and size of any openings required
other than those covered in 21.2 and 21.4.
22 CONTROL DAMPERS
22.1 Functiou dampers are required for spans in excess of 1200
Control dampers used in ductwork have three mOl, the frames should be sub-divided or inter-
functions: mediate bearings used.
22. I.I Isolation 22.2.4 Iris dampers
To act as a shut off. Normally, the damper will Iris dampers are available (for circular duels
be fully open, or fully closed. In the fully-open only) in diameters up to 460 mOl. (It should be
position, the damper should have minimum remembered that the damper casing is approx-
resistance to air flow, and when closed, imately twice the diameter of the duct.)
maximum shut off. This type of damper is either 22.3 Constructional requirements
hand- or power-actuated.
22.3.1 Low- and medium-pressure integral
22.1.2 Balancing dampers
To achieve the required distribution of air in the The following recommendations apply to
ductwork system or at inlets and outlets. For dampers forming an integral part of low- and
this purpose, the damper is fixed manually in medium-pressure ductwork.
any required position between fully open and
fully closed. The dampers shall be constructed to prevent
distortion and jamming in operation. Damper
22.1.3 Control blades shall be without sharp edges. The blades
To secure dynamic control of the air flow in the shall be sufficiently rigid to eliminate movement
ductwork system. In this function, the damper when locked.
will always be power-actuated and may require
to be continuously or intermittently operated The blades shall be securely bolted to plated
from fully open to fully closed, and to be steel spindles, the ends of wllich shall be ex-
capable of taking up any position between these tended to the outside of the duct, with a groove
extremes. In thc fully·open position. the in line with the blade. Spindles shall be carried
damper should have a significant pressure drop. in non-ferrous or nylon plain bearings or in ball
In the fully-closed position, it will not neces- bearings. All control dampers shall have a lock-
sarily achieve a complete shut-off. ing device located on the outside of the duct and
shall give clear indication of the actual damper
22.2 Types of control damper position.
Control dampers of various types are available for 22.3.2 Control dampers in, high-pressure
specific purposes, as follows. systeins
22.2.1. Single-blade dampers single skin section Control dampers will not normally be posi-
Plain-blade dampers (single-skin section) shall tioned in high-pressure ducts: essential dampers
have a maximum width of 300 mm and maxi- should be confined to areas of relatively low
mum length of 300 mm for rectangular ducts; pressure.
and for circular ducts a maximum diameter of Control dampers used in high-pressure ducts
305mm. shall meet the constructional requirements
22.2.2 Single-blade damper's double·skln section specified in 22.3.1, shall preferably have ex-
Plain-blade dampers (double-skin section) are ternallinkages, and all penetrations of the duct
suitable for use in rectangular duets, and shall shall be fitted with suitable seals.
have a maximum width of 300 mm and a maxi- 22.3.3 Proprietary Iypes of control damper
mum length of 1200 mOl. Proprietary control dampers arc commonly
22.2.3 Multi-leaf dampers (single or double separate units rather than integral parts of the
skin) parallel and opposed blade ductwork. The use of any specific type of con-
There is no restriction on the size of duct in trol damper shall be confirmed with the
which multi-blade dampers may be used, but no designer. In all cases, proprietary dampers shall
individual damper blade should exceed 1200 meet the relevant requirements of this
mm in length or 175 mm in width. Where specification.
65
Part Seven - General - continued
,
\
an inherently corrosion-resistant material or
otherwise protected to inhibit corrosion. (Some
~ Hinged link
..
fire authorities make this a requirement). '----.../\ '- Damper blade
66
Fig. 165 Standard apP'::::;;;:;~hd-Fig.
of 166 Framing applicable to Figs. 161,
framing applicable to Fig. 164 162 and 163
This design was developed
in collaboration by HVCA . This method is also normally used for a
and the HEVAC Association multiple assembly of shulter-type fire dampers
and is approved by the
Greater London Council Expansion space
filled with
compressible
Space for fire resistant
expansion Damper packing
Close contact .~
between dumper Dnmper ~-~_=._x-_:._~ _
llnd frame "
"'-,,""",hi ~
Split frame
flsscmblcd Angle frames
.lround damper secured after
lind built into fire barrier
fire burrier is buill
r METAL
There are two types of these ducts: (a) metal
(including plastics-coated metal), which can be
bent but not repeatedly flexed; and (b) ducts in
24.3 Mallipulatlon
24.3.1 G~ner81
Bendable or flexible ducts made of aluminium
metal, which can be flexed a limited number of times (particularly in the larger di~meters) can be
without failure. bent and manipulated more readily' than those
Ducts of these types may require special cOllslder- made of steel, but are more easily distorted and
atlon ill relatlollto nrc hazards, and It Is thererore more susceptible to damage.
advlsllble that the requlremellt~of the relevant nrc Because of the spiral corrugation and lock
authority lire met berore Illstalllltioll. seam, care is necessary when cutting.
24.1 Types available 24.3.2 Bendable ducts - metal
24.1.1 Belldable dllels - metal Bends are made by closing the corrugations in
A lIumber of bendable ducts are available, the throat and slightly opening the corrugations
helically-wound with lock scam to form a corru- at the back of the bend. Some readjustment i.
gated duct capable of being bent or set by hand possible with large radius bends, but small
without spring back and without defomling the radius bends cannot be straightened without
circular section. The metals used are alumi- leaving some distortion of the corrugations.
nium, stainless steel, tin-coated steel or Repeated bending should be avoided. Care
aluminium-coated steel. Plastics-coated bend- must be taken to maintain the integrity of the
ablc ducts are also available. lock seam.
24. t.2 Flexible ducts - metal Elongation and' compression are limited, an~
Some proprietary ducts of this type, in various this must be taken into account with short con-
metals, are available, having single or multiple nections between fixed points.
layers of strip formed into corrugations and 24.3.3 Flexible ducts - metal
wound in helical or annular form, without any These ducts will withstand several bendings
obvious seam or joint. through 1800 and will accept sufficient linear
compression and re-expansion to facilitate
24.2 Performallee
installation between oppositely located spigots.
Bendable and flexible ductwork must meet the
standards of airtightness required by the specifica- 24;4 Joinling
tion and be within the frictional limits specified by Joints can be made with sealant or by enclosure
the designer. using heat-shrinkable band or strip or by chemical
67
Part Seven - General- colltinued
26 FLEXIBLE JOINTS
26.1 Gcncral properties 26.3 Length
The material (normally a treated canvas) used for Flexible joints shall be kept as short as practicable
flexible joints must meet any conditions of tem- above a minimum effective length of 50 mm. In no
perature, air pressure and fire resistance specified, case shall a flexible joint exceed 250 mm in length.
and shall comply with the standard of airtightness 26.4 Connections to reclangul.,· ducts
specified for the rest of the ductwork system of
With t1anged rectangular connections, the t1exible
which it forms part.
material shall be held in place with flat bar strips
26.2 Location attached to a mating flange (Fig. 167). For spigot
Flexible joints should normally be fitted at inlet connections, the flexible material shall be held in
and outlet connections to ,all fans. Any others place with flat bar strips (Fig. 168). Flat bar strips
required should be indicated on the design draw- shall be used with proprietary flexible material
ings. Care should be taken to maintain alignment having sheet metal attached along the edges. Flat
between the fan and the dnct connection. bar strips shall be not less than 3 mm thick.
68
- -
r
---n~H-n
I I 11 r ,
I .. I 11 I .. r
I I II I I
I I II I I
I I"' .. I
I 1 I( 1 I
I 1 II I I
rl j: j j: ::!
A
;1 ,, " v
+ ,, ""
,"
, ,,, """
f
+
+ J
~.
[ lIlt I I
-
: t : :: : • :
t
jl'=...~--:i:'_:,::J~l.~'~_~_~'- - - - - - - '
-- "
--
"
~J l~
-
----
......
FJg. 167 Flexlblejolnts-f1anged Fig. 168 Flexible joints - spigot
connection connection
26.5 Connection to circular aud nat oval ducts 27.5 Heat-shrinkable band and strip
Adaptors shall be used to provide plain circular A thermoplastic material, supplied as a continuous
ends for spirally-wound ducts. Alternatively. band or in strip form, coated on the inside with an
flanged connections may bc used, adapting the adhesive. When heated, the material shrinks to a
method set out in 26.4. A sealant in accordance light fit ovcr the joint. The shrinkage is maintained
with the requirements of Scctron 27 shall be used until the material is reheated.
between tbc duct and the flexible joint, and the 27.6 Self-adhesive lape
joint secured hy clip-bands with adjustable screw
or toggle fittings. PVC or other plastic self-adhesive tape, with or
without fabric or other reinforcement.
27 SEALANTS, GASKETS AND TAPES 27.7 Methodsofuse
For the purpose of this specification, sealing The: .mallufacturer's recommendations and pre-
materials and methods are classified as set out cautions relating to use must be strictly complied
below. with.
27. t General properties Any" form of sealant under compression is more
Sealants and the other materials covered by this likely to be successful than a sealing me
section, when used in connectio~. ",ilh d.~ct",~r~: as tape) applied over a joint. Therefo
shall··.~rll1ane~tly.·retain>adB~sioJ1>and>elastisity should, if possible, be applied so as to ensure that
through a temperature range of 0° to 70°C: the air.p'ressure within the duct system,will cause it
to be set into a possible source of leakage rather
27.2 Liquid and mastic sClllant. than be blown out of it.
Any form of sealing substance applied by brush,
trowel or injection gun to a joint fonned between 27.7. J Drying and/or curing period
two sheets of metal or between sheet and an Solvent based and chemical reaction types of
adjoining member. sealant require a period of between 24 and 72
hours for drying or curing, depending on condi-
27.3 Gaskets tions. The cure should be completed before the
Sealant in the form of a pre-formed roll, sheet or duct is pressurised; otherwise mpture of the'
strip applie9between opposing faces of flanged or joint is possible.
(l~hcr.j~illt~'81~s~et~~h~~~19~~~'~;t l.ess thap JII1~) 27.7.2 Self-adhesive tape
.tBi8~'lf?rir~sta.ngulard\lsts'lJ1P.\?!1?(){JJ11m.·Ig.pg~!! The lise of self-adhesive tape as a primary
~J~tt:()rcircu Inrducts· tip. to 1250m md illmctcr;J()f
sealant is deprecated. It is In practice extremely
larger ducts, tl'" gasket should be not less than 4
difficult to achieve the dry, dust-free and
mm thick.
grease-free surface necessary for the long-term
27.4 Chemleal reaction tape adhesion of such tapes. There is the further
A wrapping which sets through the interaction of disadvantage that where the air pressure in the
the activator material and the chemical substances ducts is above ambient, the air pressure is
in the tape, thereby sealing the joint. working against the seal.
69
~!'ml1G!.it':1~~~~ ....,,,,,,_.,,,_ _
70
Table 30 Protective finishes - supporting members, etc.
.
Paint system
Supporting members
and other section Exposure Primer Follow-on
coats
I
, 3
• ..
4
Indoors None None
Steel-.galvanized or ..
metal sprayed Outdoors Etch primer or Two
calcium plumbate
Steel-not galvanized or Indoors Zinc rich, zinc chromate One
metal sprayed Outdoors or red oxide Two
30 ACOUSTIC LININGS
applied ovcr the wholc of thc area to be Iincd. In
30.1 Where a lining to ductwork is required, it addition, fasteners must be used at: 450 mm maxj~
should preferably be fitted at works. Before manu- mum centres, and not morc than 75 rom from
facture, confirmation should be obtained that the joints, corner breaks, etc., with washers Of caps to
dimensions of the duct allow for the thickness of hold the lining. In some circumstances metal mesh
the lining. may be called for by the designer as an additional
30.2 The type of lining, normally glass fibre or precaution against displacement or break-up of
mineral wool slab and faced to minimise fragmen- the lining.
tation and ·fibre·fly', should be approved by the 30.4 The lining must be applied so as to provide
designer for type and thickness. Regard should in abutment at joints and edges, with ~ontinuity of
appropriate cases be had to the fire characteristics facing material. For protection prior to erection,
of the material. the edges of the lining should be sealed or encloscd
30.3 Duct surfaces must be thoroughly clean and by a light metal section mechanically fastcned to
the lining fixed by an approved type of adhesive the duct.
31 THERMAL INSULATION
31.1 Tbe provision and application of thermal
insulation to ductwork is not normally the respon- the dcsigncr.
sibility of the ductwork contractor. It should be 31.3 For detailed information on the thermal
borne in mind thaI the application of rigid slab
insulation of ductwork, reference should be made
insulation is more difficult if the duct panels have to BS 5422: 1977 - Specification for the use of
bccn stiffcned by cross-breaking or beading. thermal insulating materials; and BS 5970: 1981 -
t, 31.2 Where ductwork is required to bc prc- Code of practice for thcrmal insulation of
pipcwork.
insulated, the specification should be agreed with
71
Pari Eight - Appendices
73
Pari Eight- Appendix A - continued
2100 0,14
2200 0,15
2300 0.15
2400 0.16
2500 0.16
74
Fig. 169 Permitted leakage at various pressures
g 1.75
~
~ 15
i
i 1.25
E!
~
. ,. 1.0
'"
8-
~
!:l 0.5
J:l
'"
.S
f25
ml 21XI JIXJ
° 400 )(J() 600 7f}(J
i" 0.40
~ 0.35
I
i
~0.25
-1-
8-
'" 0.20
I2l. IJ.15
~{).IO
.S
r05
o 250 750 IlKXI 1250 150(J 1750 2000 2250 2500
Pressure difference In pascals
75
Part Eight - Appendix A - cofltiTlued
Fig. 170 Leakage as percentage of airflow
1= ~c :c_ .--, !.Q!!!! f--+-~-
-~- -,-- '- - ~ .. ~>--- b..- I'- ~
'OOO~
800 - ~- '--- - .~
00
I; ;/~- ;
600 I- 2000
200
I - - e-- -_. ...l,L: iL 1!!!!.. ~-f-~ ~-
4001-
/'
/' 1/ 1/
'00 - 1000 -
800 -
200
00
200 600 /'
60
,00 ~-
- .L l,-<:. -_. ".' ~ . ' .._- _.. . .. _., . hoo 40 2.. .'."'.-i-:Q - ..
. - .-. 00 -~-/ -- ~~, . - 17"
"-
~
'00
:l'-~
/'
00-
200 .
V - 3 "" 20 /1/ 1/ - ":,/-'--17
20 60-
.. _~ IJ!L
[,.L
l7~
10-
40
'00 >:.-
t/ /'
-
00- .0
8-
6
20- 60 r:;; /' I .-g 7
4_ 40
-
r~
- _.
--
~--
.- b..- I'-
'-10 «w
"'
«
"
"g
w
4 I.,£-
..
+- ..
,II-H-F--~:'F++ttH
10
0_ ..I ~
- --_.- -l.-C. --, '-~
w
u
«
" ,Vr-17
::>
~
0
.. I ~ -~- ~ ..
20- ~ :>
2 6
I - --'- "'::> 3: 1/
V "'::>>- 0~
4L I
U
~
IV
10
, , , , , I! , " ""'
U • < 200 " 400 GOO 800 1000
!
2000
CLASSA I
2 450'810
~ ~ ""~ CLASS 8 ,I I , ! ! , ,
u 234568
" CLASSC Js I t j 2
LEAKAGE (U&) MEAN DIFfERENTIAL PRESSURE (Ps: PEACENTAGELEAKAGE
76
APPENDIX B - AIR LEAKAGE TESTING PROCEDURE
77
Part Eight- Appendix B - continued
8.7 Test apparatus all joints which fall outside the scope of the
8.7.1 The accuracy of the test apparatus shall testing procedure, i.e., joints belween tesled
be within: seclions of ductwork and between ductwork
± 10 per cent Of the indicated flow rate, or and other units.
0.4 litres per second, whichever is the B.8.5 Due notice of tests shall be given, so that
greater; and arrangements for witne'ssing the tests, if
± 5 per cent at the indicated static pressure required, can be made.
in the duct under test. 11.9 Testing sequence
B.7.2 The test apparatus shall be inspected by The recommended sequence of testing is as
the user before use on site, and shall have a follows.
calibration certificate, chart or graph dated not 8.9.1 Complete Part I of the Test Sheet.
earlier than one year before the test for which it
is used. 8.9.2 Connect test apparatus to section of duct-
work to be tested.
B.7.3 A diagram of a suitable test apparatus is
given in Fig. 171. 11.9.3 Adjust test apparatus until the static
pressure differential is obtained.
8.8 Procedure 11.9.4 Check that the measured leakage is with-
in the permitted rate. (No addition shall be
8.8.1 T\1e section of ductwork to be tested for made to the permissible leakage rate for access
air leakage shall be sealed. Main ducts should doors, access panels or dampers where these are
be provided with flanged joints to enable blank- included in the ductwork.)
ing plates to be fitted, while small open ends
may be sealed with polythene or inflatable bags, 11.9.5 Maintain the test for fifteen minutes and
which should be left in position until final con- check that the leakage rate has not increased.
nections are made. 1l.9.6 Reduce pressure in section to zero by
8.8.2 On low-pressure systems, final grille switching off the fan; then immediately re-apply
spigots made as a second fix operation shall be test pressure to establish that the air leakage
excluded from the test. The joint shall, where rate is not greater than the previous reading.
practicable, be checked by external visual 1l.9.7 Record details on Part 2 of the Test Sheet
examination. and complete, including witnessing.
8.8.3 Sufficient time shall be allowed between 11.10 Airleakage test sheet
erection and leakage testing ~or sealants to cure. A specimen of a suitable Test Sheet is given on
8.8.4 Special care must be exercised in making page
Duct test
pressure gauge-.
Inclined gauge
,_,J
Attention is drawn to HVCA pu blication DW/143 - A Practical
Guide to Ductwork Leakage Testing - which gives detailed
advice on the actual procedure for ductwork le"kage tesling.
78
Specimen of al.. leakage test sheet
'Test No .
General
Name of job .
Building reference .
I e
f
Interpreted air now leakage rate
Duration oftest (normally 15 minutes)
.
.
tTOTAL
79
..'·w__.....,.
~".'iiiW'_' , _
Note
The infonnation given in this Appendix is for the
guidance of mechanical service contractors, con-
sulting engineers, etc, The identification of duct-
work does not form part of the work carried out by
the ductwork contractor unless called for in the job
specification.
C.I GENERAL
C.1.1 Introduction C.2.2 Identification symbols will be needed
With the increasing complexity of ventilation and mainly in the plant room. Symbols should occur
air conditioning systems, it is becoming more frequently enough to avoid the need for ducts to be
important to ensure ready identification of ducts traced back. Symbols should be placed at any ser-
for the purposes of commissioning, operation and vice and access points to the distribution system,
maintenance of systems, The purpose of these including points where the d,istribution system has
recommendations is to lead towards the use and reduced to a single ducl.
standardisation of a system of identification for C.Z.3 Colour coding
ducts for the benefit of designers, contractors and The choice of colours has been based on the need
clients. to provide:
C.1.2 Scope C.2,3.1 Strong contrasting colours which are
C.I.2.1 These recommendations deal with the recognisable even though covered with dust.
identification of ducts for ventilation, air condi- C.Z.3.2 Contrast between the symbol colour
tioning and simple industrial exhaust systems. and thc base colour ofthe ducl. Usually the base
They do not include piped gas systems such as colour metallic grey of galvanized or aluminium
are dealt with in as 1710, nor with ductwork sheet or foil sheathing, or the white, pale grey,
systems for industrial processes, although the or buff paint on the insulation is a neutral colour
general considerations and intentions could be against which the recommended symbol colours
extended with the agreement of the client to will stand out.
cover such systems.
C.2.4 The recommended colours are given in
C.I.I.1 The method is designed to identify the Table 33. The colour coding indicates the type of
air being conveyed, the direction of flow, the air being conveyed.
destination of the air and/or of the plant where,
the air was treated. With small or simple plants.
it may not be strictly necessary to provide iden-
tification because the function is apparent, but
it is considered advisable to do so because this
will increase familiarity with the labelling Table 33 Recommended duel identilication colours
system and also because the nature and direc-
tion of air flow may not always be apparent. Type Colour BS 4800
C.2 IDENTIFICATION J 2 3
C.2.1 Location
To be effective the identification must be placed Conditioned air Red and 04 E 53
Blue 18 E 53
where it can be easily seen and at positions where
identification will be required. To ensure that the Warm air Yellow 10 E 53
symbols are seen, the following points should be Fresh air Green 14 E 53
considered,
C.2.1.1 The symbols should be on the surfaces Exhaust/extract/
which face the positions of normal access to the
recirculated air Grey AA009
completed installation. Foul air Brown 06 C 39
C.2.1.2 The symbols should not be hidden Dual duct system-
from view by structural members, other ducts, hot supply air Red 04 E 53
plant, or other services distribution systems.
Dual duct system-
C.2.I.3 The symbols should be placed where cold supply air Blue 18 E 53
there is adequate natural or artificial light.
80
C.2.5 For conditioned air, two symbols (one red, of the plant. The plant itself must be clearly
one blue) may be used, or a single symbol coloured numbered to correspond. Letters for Supply,
part red, part blue. Flow, Extract, etc., should not be added be-
C.2.6 If a finer grading than that giver in Table 33 cause identification will be clear from the colour
is required, as for instance in a laboratOly with two symbol. Thus confusion between'S' for Supply
separate contaminated air exhaust systems, it is and'S' for South will be avoided.
recommended that the type colour be used with, Table 34 Examples DC further identification
say, a stripe of a second colour. Where the duct symbols
contents constitute a hazard, a symbol as given in
BS 1710 should be added to the type colour. Code Information given
C.2.7 Direction DC flow
9SW P2 9th Floor,
C.2.7.1 The form of symbol chosen indicates South-West Zone,
direction. It is an equilateral triangle (see Fig. Plant Two
172) with one apex pointing in ·the direction of
air flow. Where the boundaries of the duct are Camp 2 P2 Computer 2,
Plant Two
not visible, two triangles should be arranged in
line ahead to indicate direction of flow. 3 Lab 8 P4 3rd Floor,
C.2:T.2 The size of the symbol will depend on Laboratory 8,
the size of the duct and the viewing distance. Plant Four
The recommended minimum size for nannal 2 Op Th 2PI 2nd Floor,
use is 150 mm length of side. Operating Theatre 2,
Plant One
Bay 5 N P5 Bay 5, North end,
81
'Mf'!!i11¥ •. !!. '$
E. I Fire containment and fire hazards are factors 1'.2.2 If there is no duct opening into the COIll-
which influence the design and installation of duct- partment, fire dampers may be omitted at the
work systems. Information concerning the fire walls, provided the duct is enclosed by a structure
protection of ductwork can be found in CP 413 having the same fire resistance as the comp~lft~
published by the British Standards Institution and ment. In this context, it should be appreciated that
in the Technical Memorandum 1 published by the sheet metal alone offers only limited lire resistance
Chartered Institution of Building Services and is not a heat burrier.
(formerly the Institution of Heating and Venti-
lating Engineers). Notes on legislation relating to E.2.3 The amount of combustible and smokel
fire and services in buildings are given in ClBS fume producing materials used in the construction
Technical Memorandum 2. of ductwork should be limited. This requirement
E.2 The principles of fire protection in relation to includes in its scope sealants, gaskets and other
dnctwork are: jOinting materials; flexible ducts and joints, insula-
E.2.1 Fire dampers should be provided where ting and lining materials. The combustible content
ducts pass through fire compartment walls. Fire of construction material is assessed by the fire
dampers should be framed in sueh a way as to allow propagation test specified in BS 476, Part 6.
for expansion in the event of fire, and the design
must provide for the protection of any packing Standard types of fire dampers and frames are
material included. deselibed in Section 23 of this specification.
82
APPENDIX F -GAI.VANIZING AFTER MANUFACTURE
83
APPENDIX G - STAINLESS STEEL FOR DUCTWORK
84
G.5.2 If a mixture of metals is used, such as mild G.IO Fixings and fastenings
steel supports for stainless steel ductwork. the sur- The types of fastening and the maximum spacings
face of the mild steel must be adequately protected specified in Table 10 (rectangular) and Table 16
from the galvanic corrosion that might result from (circular) also apply to stainless steel ductwork.
the intimate contact between the two types of Fixings and fastenings should be of the appropriate
metal. (The appropriate protective finish in Table grade of stainless steel as used in the construction
29 (for outdoor applications) should be of the ductwork, or should be made equally resis-
employed.) tant to corrosion in relation to the environment in
which the ductwork is sitnated. TIle type of stain-
G.6 Construction
less steel fastening used should conform to the
G.6.1 Sheet thicknesses for stainless steel duct- appropriate, specification (e.g., BS 1768, 3692;
work should be the same as for galvanized steel ISO 3506 - Hexagon bolts, set screws and nuts).
(see Tables 4. 14 and 15). Where any additional
gauge allowance is made for corrosion resistance, G.1I Welding
this should be based on knowledge 'of the corrosive All the modern welding processes may be used to
inflnences present in the local environment. weld stainless steel, but tungsten inert gas (TIO)
(;.6.2 The forming of rectangular and circular and resistance welding are likely to be the most
ducts can be carried out by the use of conventional suitable for light-gauge materials. Attention is
press working and sheet metal forming machines. drawn to BS 4872: Part I when welding stainless
Some alteration in working practices may be steels; and to BS 2901 for the selection of filler rods
and wires.
necessary. however, depending on the type of
stainless steel being used. When welding dissimilar metals, e.g., mild steel to
stainless steel, the choice of the electrode is very
G.6.3 As a general rule. the 400 series of stainless important, as the effect of dilution of the weld
steels can be formed using normal mild steel set- metal by the base metal must be considered.
tings. The 300 series, however, because of the Reference should be made to BS 2901: Parts I and
higher yield point and the greater rate of work 2, and to BS 2926 for selection of welding
hardening, will require higher working pressures. electrodes.
G.6.3 Ductwork contractors who have experience G.12 I'iredampers
of the use of stainless steel report difficulty in
Stainless steel is an ideal material for use in the
forming Pittsburgh and button punch snap lock
construction of fire dampers, due to its high resis-
seams. As regards cross joints, socket and spigot
joints are recommended, and one or two of the tance both to heat and corrosion. It is therefore
most applicable where a fire authority makes cor-
slide-on flanges are snitable. In view of the fore-
rosion resistance a requirement.
going, it is recommended that trials be carried out
before starting on production. G .13 Sealants, gaskets and tapes
111e sealing materials and methods set out in this
G.7 Rectangular duct. specification are also applicable to stainless steel
The constructional requirements for rectangular ductwork. However, any chloride·hased material,
stainless steel ducts are the same as for galvanized such as polyvinyl chloride (PVC), should be
mild steel. avoided, as breakdown of such materials at certain
elevated temperatures could lead to corrosion of
G.B The constructionaJ requirements for circular the stainless steel.
stainless steel ducts are the same as for galvanized
mild steel. G.14 General design considerations
It is the designer's responsibility to indicate the
G.9 Stiffening type of stainless steel most suitable for the condi-
Wherever possible, the material used for stiffening tions in which the ductwork is to be exposed. If
should be of the same grade of stainless steel as users and designers are in doubt as to which
used for the construction of the ducts, or should be material is appropriate to a particular application,
made equally corrosion resistant to suit the technical advice may be obtained from the source
environment in which the ductwork is situated. noted below.
85
APPENDIX H - PRE-COATED STEEL
H.I Nature of the material H.S Ductwork "onstructlon from pre-coated steel
H.1.1 'Pre-coated' steel is sheet, coil or strip to H.S.I The type of pre-coated steel most suitable
which has been applied at the steel mills a coating for ductwork should be carduily considered,
having a decorative or protective function I or mainly from the point of view of the fabrication
both. properties of the coaling type. It is probable that a
H.l.2 The basis metal to which the coatings are plastisol coating will be found to be most suitahle
for ductwork, as this type of coating will withstand
applied are hot-dip galvanized sheet or coil,
uncoated steel or electro-galvanized steel (e.g., an 01 bend at nOl1oal ambient temperatures. It
also tolerates rougher handling during forming
Zintec). and erection than the much thinner paint coating
H.2 Range of coatings available types.
H.2.1 A number of different types of coating, in If.S.2 Careful consideration should be given to
various thicknesses, are available PVC Ihe constructional methods to be used for duct-
('plastisol' and 'organosol'); paint coatings of work to be made from pre-coated steel. The
several types, silicone enamels, etc. principle to be followed should be to make seams
H.2.2 A wide range of colours and surface finish- and joints as unobtrusive as possible. Some of the
ed are available, but there are minimum quantity conventional methods of seaming may be used.
requirements for some types of coating, finish and
but a number of others are not suitable. Wdding
colour. The characteristics of the particular type of with conventional equipment should not be
coating contemplated for a particular use should attempted. Mechanical fastenings should be
be investigated in respect of formability, fastness chosen with care having regard to appearance as
to light, chemical resistance and other relevant well as efficiency; and sealant should be applied
properties. with these factors in mind. Stiffening should be
carefully considered in relation to appearance.
H.2.3 The material can be supplied with one or
both sides treated. H.6 Handling, storage, transport and erection
H.6.1 Much mare care than usual is required in
H.3 Sizes available these respects, as the coatings are Hllto a greater or
H.3.1 Pre-coated steel is available in sheet or coil lesser qegrce susceptible to mechanical damage.
form - sheet in widths from 610 mm to 1370 mm For example, sheel should not be dragged off the
and in length up to 5486 mm. Coil is supplied in top of a pile but removed by 'turning' off the stack.
widths from 610 mm up to 1370 mm. The maxi- H.6.2 With sheet pre-coated on one side only, it
mum available width can vary also according to the may be found desirable to stack face to face.
steel thickess required. Availability varies accord-
ing to type of substrate and coating, so prospective H.6.3 The flexibility of coatings of the types used
purchasers should query the sizes available for the on prc'coated steel depends on temperature.
specific type required. Therefore, manipulation should be carried out at
temperatures above 16°C (60°F) in order to pre-
H A Som'ces of supply vent the film cracking on roll forming, etc. If the
HA.I Pre-coated steel is obtainable from major material has been stored outside at low temper-
steel stock-holders or direct from the British Steel ature, a warm-up period should be allowed before
Corporation. manipulation of the sheet is undertaken.
86
APPENDIX J-ALUMINIUM DUCTWORK
APPENDIX K- EUROVENT
~:
87
facture of equipment, the UK representative is the 'soft' one, and thus in the larger diameters there is
HEVAC Association. As regards ductwork, the a significant discrepancy between the nominal
Duct Work Group of HVCA during 1975 formally quoted dimensions and the actual ones. For this
affiliated to the HEVAC Association, thus giving reason, the nominal diameters of the circular ducts
the Group a direct voice in EUROVENT ductwork have been given separately in Table 13.
projects.
K.7 Possible ISO standard for duct sb.es
K.S EUROVENT publications In 1974 EUROVENTproposed to the International
EUROVENT has published a number of docu- Standards Organisation (ISO) that the standard
ments in the air handling field, and these include sizes specified in Document 2/3 be convertell into
Document 2/3 covering the standardisation of duct an International Standard.
sizes. Document 2/2 covers the procedure for test- The ISO. as in duty bound, referred thc proposal to
ing for air leakage in ductwork, and provides for the various national standardising bodies - in the
two levels of permissible air leakage for low- case of the UK the British Standards Institution.
pressure air distribution systems.
At the time of preparing this dllCtwork specifi-
K.6 EUROVENT Document 2/3 - standard sizes cation, a representative committee of the BSI
of ducts (including representatives of the HEV AC Associ-
This gives a range of standard sizes for both rectan- ation and 01 the Duct Work Group of HVCA) was
gular aud circular ducts. considering the matter.
As regards rectangular ducts, the Duct Work K.8 Air leakage
Group has adopted the EUROVENT recommenda- The hasis on which air leakage is calculated in
tions see Table 3 on page 13 of this sl'ecification. EUROVENT Document 2/2 has been adopted in
As regards circular ducts, most of the spirally- DW/142, with the exception that the leakage limits
wound circular ducts in the UK are made on form- in Document 2/2 relate to the pressure classes A, B
. ing heads based on Imperial measurements. It is and C (see Section 6 of DW/I42), while DW/l42
now common practice for these Imperial sizes to includes a limit for Class D - high-pressure duct-
be quoted in metric units, but the conversion is a work up to 2500 Pa.
Note - The extracts from BS 2989: 1982 have been Grade Name ofgrade Application
prepared by the HVCA and are included here by ZI Commercial Forming quality steel
courtesy of the British Standards Institution. quality suitable for simple
bending and forming
L.t GENERAL operations
L. I.l The BS 2989: 1975 ('Hot-dip zinc coated Z2 Bending and Forming quality steel
steel sheet and coil') summarised in DW/141 profiling quality suitable for the
has been superseded by the 1982 edition, which manufacture of most
is entitled 'Continuously hot-dip zinc coated profiles and more
and iron-zinc alloy coated steel: wide strip, difficult bending
sheet/plate and slit wide strip'.. operations
L.1.2 Comparison of the following with Z3 Drawing quality Forming quality steel
Appendix 0 of DW/141 will show changes in suitable for simple
type references. drawing operations
L.1.3 As before, the new British Standard sets and for more difficult
out requirements for the conventional gal- profilirtg operations
vanized sheet and coil (and now also strip) and Z4 Special drawing Forming quality steel
for iron-zinc coated steel. (Both these are in- quality suitable for deep
cluded in DW/142-see Section 7.) drawing and difficult
The type of steel normally used for ductwork is forming operations
Z2 G.275 (under the previous British Standard Z5 Special drawing Forming quality steel
designated as Z2, coating type C). quality, non- suitable for deep
ageing drawing and difficult
L.2 STEEL GRADES forming operations
L.2.t BS 2989: 1982 lists the grades of steel set out where a non-ageing
in the next column, among others: steel is required
88
1..3 COATING TYPES L,5 SURFACE PROTECTION
1..3.1 The types of zinc coating arc set out in 1,.5.1 All types of coating nOlmally receive a
Table 9 orBS 2989: 1982 (rcproduccd at the foot surface protection at the producer's plant.
of this pagc).
This may consist of chemical passivation; or
oiling; or chemical passivation and oiling. The
purchaser should state on his order the
1,.4 SURFACE FINISHES
treatment required.
1,.4.1 BS 2989 includes a descriptioo of the
various types of finish available: 1..4.2 Chemical passivation and/or oiling
Normal spangle (N). A zinc coating finish, protects the surface against humidity and
having a metallic lustre, that is thc rcsult of reduces the risk of formation 'of wet storage
unrestricted growth of the zinc crystals during stains (sa.-called 'white rust'). However, the
normal solidification. protection afforded is limitcd. If the purchaser
NOTE. Normal spangle is the type normally specifies non-protected products, the manu-
supplied for a wide variety of applications. facturer is not responsible for the formation of
any storage stains. (Chemical passivation may
Minimized spangle (M). A zinc coating finish,
cause slight discoloration of the surface that is
normally supplied with zinc coatings in the
not detrimental to the general performance of
range Gl00 to G350, that is obtained by
the product.)
restricting the normal zinc crystal formation.
Regular finish (R). The normal iron-zinc alloy 1,.6 FORMING
coating finish; it is grey matt in appearance and 1..6.1 The British Standard says that provided
shows no spangle. that the profiling machine is set to avoid exces-
sive stretching in the product, it is possible to
Smooth finish (S). A finish suitable for
decorative painting that is available for zinc form lock seams successfully with Z2 sheet up to
coatings up to G350 and iron-zinc alloy a thickness of 1.5 mm and Z3 sheet up to 2 mm;
and snap lock seams with Z2 up to 0.9 mm thick
coatings.
sheet and Z3 sheet up to 2 mm.
Extra smooth finish (XS). A coating finish,
produced by rolling processes after coating 1..7 WELDING
and available for zinc coatings up to G275 I.. 7.1 Care should be taken to use proper
and for iron-zinc aHoy coatings, suitable for methods and procedures. The iron-zinc coating
applications where a high gloss paintcd finish is more suitable for resistance welding than the
is required. conventional zinc coating.
g/m' g/m'
Zinc coatings (Gl
Light - for use where corrosion conditions are
GlOO 100 85
not severe and/or where forming
0200 200 170
operations preclude heavier coatings.
0275 275 235 Standard
G350 350 300
Heavy duty - for longer life relative to
0450 450 385
standard and light coatings.
0600 600 510
Iron-zinc alloy coatings (IZ)
Iron-zinc alloys - alloyed coatings of iron and zinc
IZIOO JOO 85
for easy painting and particularly
IZJ80 180 150
- ._- ... ~_ . resistance welding.
Note 1. The mass of zinc is not always evenly divided between the two surfaces of the sheet. However, it can
normally be expected that not less than 40% of the specified minimum coating mass, as determined
by the single spot test, will be found on each surface.
Note 2. The suggested applications included in the right-hand column of the above table are those put
forward by the British Steel Corporation.
89
APPENDIX M-'DESIGN NOTES FOR DUCTWORK'
(CIBS Technical Memorandum No.8)
M.I This manual brings together information on Duct siZing methods, including velocity, equal-
the design of ductwork systems. friction and static regain methods, and pressure
M.2 The contents have been drawn from the cur- loss calculations, with an example calculation.
rent relevant sections of the ClBS Guide and olher Heat loss from and gain to air in the duct; con-
recognised references, and include additional densation, noise control and fire,
material on good design practice. The Notes make Commissioning and testing,
frequent reference to DW/142, and an effort has Overseas work.
been made to ensure consistency between the two Drawing symbols in current usc.
pUblications. The Design Notes include chaptcrs
on: M.3 The fiow of heavily contaminated air in ducts
Pressure loss in ducts, including corrections for is not covered in detail in the Notes; nor are the
duct snrface type, air pressure, air density, tem- constructional aspects of ductwork, which are
perature and altitude, and loss factors for dealt with in DW/142.
fittings. M.4 The Notes are completed by references, a
Equivalent diameters of rectangular and fiat bibliography of over thirty titles and appendices
oval ducts. covering properties of air, ductwork support
Standard dimensions of circular. rectangular loads, velocity pressure for air fiow and conversion
and fiat oval ducts. to SI units.
These notes have 'been contributed by the House, 222 Balham High Road, London SW 12
Chartered Institution of Building Services, Delta 9BS (Telephone: 01-675 5211)
APPENDIX N - BIBLIOGRAPHY
Included in this Bibliography are technical publications which Series A Air Distribution Systems
may be of interest to ductwork designers. rabricators and erec- Series B Boiler Plant
tors, and to those in the heating, ventilating. air conditioning Series C Automatic Control Systems
industries generally. Enquiries should be made of the relevant
organisation. at the address quoted. Series R Refrigerating Systems
Series W Water Distribution Systems
HEATING AND VENTILATING T«hnlcal Memonnda
CONTRACTORS' ASSOCIATION No. 1 Recommendations relating lhe design of air-
34 Palace Court, London W2 4JG Telephone: handling systems to fire Ilnd smoke control in
buildings
01- 229 2488; Telex: 27929. Orders to HVCA Pub-
No.2 Notes on legislation relating to fire and services
lications, Old Mansion House, Eamont Bridge, in buildings
Penrith. Cumbria CAlO 2BX (Telephone: No. 3 Notes on legislation relating to the Health and
076864771 Telex: 64326) Safety at Work etc. Act, 1974
Ductwork No.4 Design Notes for the Middle East
DW/142 Specification for sheet metal ductwork (Iow--, No.5 The calculation and use of utilisation factors
medium- and high-pressure) (1982) No.6 Lighting for Visual Display Units
DW/l43 A practical guide to ductwork leakage testing No.7 Recommendations on the use of small program-
(t983) mable calculators
Other tcchnicul puhlicllUons No, 8 Design Notes for Ductwork
TR/5 Welding of carbon steel pipework (1980) - 'The No.9 Notes on Non-Statutory Codes and Standards,
Gn::y Book' relating to Fire and Services in Buildings
TR/3 Brazing and bronze weillillg of copper pipcwofk IlUILDING SEltVlCES RESEARCH AND
and sheet (1976) - 'The Copper Hook'
TRJ6 Guide to Good Practice for Site Pressure 'Testing INFORMATION ASSOCIATION
of Pipe work (1980) Old Bracknell Lane West, Bracknell, Berkshire
RGI24AH (Telephone: Bracknell (0344) 26511;
CHARTERED INSTITUTION OF nWLDlN(; Telex: 848288 BSRIAC 0)
SERVICES Application Guides
Delta Honse, 222 Balham High Road; AG.IJ74 Designing Variable Volume Systems for Room
London SW12 9BS (Telephone: 01-675 5211) Air Movement
CIBSGuide HEVAC ASSOCIATION
Volume A Design Data Unit3, Phoenix House, Phoenix Way,
VolumeB Installation and Equipment Data Heston, Middx. TW5 9ND (Telephone:
VolumeC Reference Data 01-8972848)
Fan Application Guide (Secolld Edition 1982)
CommlSllilonlng Codes
Guide to Air Diffusion
These Codes cover the prelimimiry"checks, setting to work and
regulation of various categories of plant. The Codes give a Guide to Central Station Air Handling Units
guide to design implication!>, Guide to Elimination of Noise in Fan Systems
90
Appendix N - continued
EUROVENT publications (enquiries to the HEVAC A.fsocation) BS 3533; 1962 Glossary of tcrms relating to thennal
1[1 Fan terminology insulation
2/1 Vocabulary relative to air distribution and air BS 4174; 1972 Self·tapping screws and metallic drive screws
diffusion AS 4342: 1968 Glossary 'of terms used in mechanised and
2/2 Air leakage rate in sheet metal air distribution handsheci metal work and melal box making
systems BS 4800; 1972 Paint colours for building purposes
2/3 Sheet metal air duets - standard for dimensions
BS 4848; Hot rolled structurnl steel sections
AG.InS Manual (or Regulating Air Conditioning
Installations Purt4; 1972 Equal and unequal angles
AG.l/77 Documents for Air System Regulation BS 5422;1977 Specification for the use of thennal insula-
AG.2175 Room Air Movement with Ceiling Mounted ting materials
Diffusers - Influence of Cold Windows BS5720·.1979 Code of practice for mechanical ventilating
and air conditioning in buildings
Laboratory Reports
LR.65 Air Movement in Rooms with Side-wall Mounted BS5971\;1981 Code of practice (or thennal insulation of
Grilles pipework
LR,71 Air Movement in Rooms with SilI·Mounted SHEET METAL AND AIR CONDITIONING
GrilleR - Design Procedure
CONTRACTORS' NATIONAL ASSOCIA·
LR. 75 Air Flow Generated Noise: Part 1: Grilles and
Dampers
TION INC, (SMACNA)
LR. 78 Air Flow Generated Noise: Part 2: Bends with 8224 Old Courthouse Road, Tyson's Comer,
'fuming Vanes Vienna, Virginia 22180, U.S.A. (Telephone: 703-
LIt.79 The Effect of Ceiling Beams and Light FiUingson 7909890)
Ventilating Jets Architectural sheet metal manual (1979)
LR.80 Air Movement in Rooms with Ceiling Mounted Architectural sheet metal spccificntions (1980)
Dirfu5Crs
Balancing and adju!itment or air distribution (1967)
LR,83 Air Movement in Rooms with Low Air Supply
Contractor's Handbook ror Air Pollution Control
Rates
Duclliner application standards (1975)
BRITISH STANDARDS INSTITUTION Fibrous glass duet construction standards (1979)
Sales Department, 101 Pentonville Road, London Fire Damper and Heat Stop Guide (1981)
N I 9ND (Telephone: 01-837 8801) Flexihle Duct Perfonnance and Installation Standard (1981)
Guidelines ror energy conservlltion in existing buildings (1974)
DD 5: 1971 Recommendations for mctric plate "l1d
Guidelines for energy conservation systems in new building
shcet thickness and width/length combin-
ations for metallic materials - (IY75)
Guidelines for Welding Sheet Metal (1977)
DO 24; 1973 Recommendations for methods or protec-
tion against corrosion 011 light section steel High-pressure duct construction standllrds (1975)
used in building HVAC DUCI Design Manual (1981)
BS38IC;1964 Colours (of ready-mixed paints) for specific Industrial ventilation - manual for recommended practices
purposes (19&J)
CP413;1973 Ducts for building services Low-velocity duct construction standards (1976)
Rectangular Industrial Duct Construction Standard (1980)
US 476: Fire tests on building materials and stntctures
Round Industrial Duct Construction Standard (1977)
Part 1;1953 (SuperJeded by Part 8)
Testing, balancing and adjusting of environmental systems
Pari 2: 1955 (Withdraw,,) (1974)
Parl3: 1975 External fire exposure roof test Thermoplastic duct (PVC) construction manual (1974)
Pari 4; 1971\ Non-combustibility test for materials
I'nrt 5: 196R Ignilahility test for materials DEI'ARTMENT OF THE ENVIRONMENT
Partt):1968 Fire propagation tcst for m:.lterials (Property Services Agency)
Part7:1971 Surface spread offiame tests for materi<lb H.M. Stationery Office, 49 High Holborn,
PartB:1972 1est methods and criteria for the fire London WC1Y 6HB (Telephone: 01-9281321) and
resistancc of building construction branches
BS 729; 1971 Hot dip galvanized coatings for iron and M & ENo.l WI2 Electrical installations in buildings
steel articles M & E No.2 1968 Electrical dishibution systems external to
BS 1449: St(',c! plnte, sheet and strip buildings
Pal'l 1:1972 Carbon steel plate. sheet and strip M & E No.3 1977 Heating. hot and cold water, steam and
BS 1471\; 1972 Wrought aluminium and aluminium..?lIoys gas installations ror buildings
for general engineering purposes - plate. M & E No.4 1970 Central heating and hot and cold water
sheet and strip installations ror dwellings
BS 1474; IY72 Wrought aluminium and aluminium alloys- M & E No.51969 Electrical installations in dwellings of
bars, 11lbes and sC'clions traditional construction
US 2569: Spfllycd metal contings M & E No.61971 Mechanical ventilation for buildings
Part I: 1%4 Prntcetiol1 of iron and sleel by aluminium TECHNICAl-INSTRUCTIONS (M&El MAINTENANC~;
and zinc agllillst atmospheric cmrosion 4 Maintenance of Diesel Engines (1970)
Pari 2; 1965 Protection of iron and sleel againsl 8 Planned Maintenance and Operation of
corrosion and oxidation at elevated Mechanical and Electrical Services (1968)
temperatures 14 Inspection and Testing of Electrical
BS 2989; IY82 Continuously hot-dip zinc coated and iron- Wiring Installations and Power Consum-
zinc aHoy coated stecl ing Apparatus (1968)
91
APPENDIX P
CONVERSION TABLES
Sheet thicknesses
Equivalents reproduced by courtesy of the Ml'IricaltOlJ Board
Area
Square inches to square miJlimetres 645.2 Square millimetres to square jilches 0.00155
Square reet to square metres U.0929 Squurc metres to square feet 10.764
Volume
Cubic feet to cubic metres 0.02832 Cubic metres to cubic feel 35.315
Cubic reet to Iitres 28.31 Litres lo cubic feet 0.0353
Gallons (UK) to Iitres 4.546 Litres to gallons (UK) 0.22
Mass
Ounces to grams 28.35 G rams to ounces 0.03527
Pounds to kilograms 0.4536 Kilograms to pounds 2.205
Tons to tannes 1.016 Tonnes to tons 0.9842
Volume flow .
Cubic reet per minute to cubic Cubic metres per second to cubic
metres per second 0.000472 reet per minute 2119
Cubic reet per minule to litres Lilres per second to cubic feet
per second 0.4719 per minute 2.119
Malian
Feet per minute to metres per second 0.00508 Metres per second to feel per minute 197
Pressure
Inches water gauge to millibars 2.491
Inches water gauge to pascals (Pa) 249.1
I Pa = 1 Newlon per square metre - )0- 2 millibar$
92
Length conversions The figure in the celltral column can be read as
either the metric or the British measure. For
example. I millimetre 0.03937 inch: or I inch ;=
254 millime(res..
0.794 :Jr
1.587 -,b
3.175 !
4,763 ,1;
6.350 l
7.938 ft,
9.525 I
11.112 ,1
12.700 I
Standard dimensions of steel 14.290 &,
15.876 ~
and aluminium sheet
-- 001 , ,
Steel
(black and galvanised)
• ll'l'" ...
17.462
19.050
20.636
22.222
Ji,
l
/1,
l
23.809 II.
Metric Equivalent 25.4 I 0,03937
50.8 2 0.07874
mm ft/in 76.2 3 0.11811
2000 x 1000 6' 6'/4" x 3' 3'1,' 101,6 4 0.15748
2500 x 1250 8' 2 7/16" x 4' 11/4" 127.0 5 0.19685
3000 x 1350 9' 10 'I." x 4' 5 1/1i" 152.4 6 0.23622
3000 x 1500' 9' 10 'I." x 4' 11 '/10" 177.8 7 0,27559
203.2 8 0.31496
... NOI readily ovailalJle 228.6 9 0.35433
254.0 10 0.39370
279.4 II 0.43307
304.8 12 0.47244
Aluminium 330.2 13 0.51181
(commercially pure and alloy) 355.6 14 0.55118
381.0 15 0.59055
Metric Equivalent 406.4 16 0.62992
431.8 17 0.66929
mm ftfin 457.2 18 0.70866
2000 x 1000 6' 6i" x 3' 3j" 482.6 19 0.74803
2500 x 1250 8' 211-" x 4' Ii" 508.0 20 0.78740
3750 x 1250' 12' 3 ~" x 4' It" 635.0 25 0.98425
762.0 30 1.18110
·Not available in nil gauges or all purities and alloys 889.0 35 1.37795
1016 40 1.57480
1143 45 1.77165
1270 50 1.96850
1397 55 2.16535
1524 60 2.36220
1651 65 2.55905
1778 70 2.75590
1905 75 2.95275
2032 80 3.14960
2159 85 3.34645
Weight of galvanized steel sheet 2286 90 3.54330
2413 95 3.74015
2540 100 3.9370
Weight per 3810
Thickness square lI/('tJ-c' 150 5.9055
5080 200 7.8740·
mm kg 6350 250 9.8425
0,5 3.921] 7620 300 11.8110
!l.6 4.7056 1\890 350 13.7795
0.7 5.41\91\ 10160 400 15.7480
0.1\ 6,2741 11430 450 17.7165
0.9 7.051\4 12700 500 19.685
1.0 7.1\426 15240 600 23.622
1.2 9.4111 1771\0 700 27.559
1.6 12.541\1 20320 800 31.496
2.0 15,61\52 221\60 900 35.433
2.5 19.6064 25400 WOO 39.370
93