Академический Документы
Профессиональный Документы
Культура Документы
11
Cabur offers three different technologies with the right performance and price
Which power supply unit to use
Switching Linear Filtered
Efficiency >87% < 50% 80% Switching - with highly variable line voltages (from 90 to 246 Vac)
Energy dissipated 14% > 50% 20% - with electronic loads
- when high Vdc stability is required
Mains var. tolerance 90-264 Vac 207-257 Vac 218-240 Vac - to reduce energy consumption, dissipated heat, weight, dimen-
Load var. stability > ± 50 mV > ± 200 mV > ± 2.5 V sions
Linear
Ripple @ 100 mVpp @ 100 mVpp ≥ 2 Vpp - with line voltages stable within +10%
Weight reduced high high - with electronic loads
Dimensions small high high Filtered - for applications requiring very low electromagnetic emissions
Cost lower huge huge - with very stable line voltages within +5%
EMI below standard limits low low
- with loads having high tolerance to high ripple
- with loads having high tolerance to variations of 25 Vdc
- to reduce costs
12
Power supply selection table
Switching power supply out 24 Vdc
Output Output Input Notes Type Cat. No. Page
voltage current Tipology Voltage
24 Vdc 0.6 A 1-phase: 90…264 Vac / 100...370 Vdc (1) CSD15C XCSD15C 15
24 Vdc 1.2 A 1-phase: 90…264 Vac / 100...370 Vdc (1) CSD30C XCSD30C 15
24 Vdc 1A 1-phase: 90…264 Vac / 100...370 Vdc (1) CS4 XAS4 16
24 Vdc 2A 1-phase: 90…264 Vac / 100...370 Vdc (1) CSD2 XCSD2 16
24 Vdc 2.5 A 1-phase: 90…264 Vac / 100...370 Vdc (1) CSD50C XCSD50C 17
24 Vdc 3A 1 or 2-phase: 185...550 Vac (3) CSW75C XCSW75C 21
24 Vdc 4A 1-phase: 90…264 Vac / 100...370 Vdc (1) CSF3 XCSF3 18
24 Vdc 4A 1-phase: 90…264 Vac / 100...370 Vdc (1) (7) CSF3P XCSF3P 18
24 Vdc 5A 36…72 Vdc (10) CS48245 XCS48245 50
24 Vdc 5A 1 or 2-phase: 185...550 Vac (3) CSW120C XCSW120C 21
24 Vdc 6A 1-phase: 90…264 Vac / 100...370 Vdc (1) CSF5 XCSF5 18
24 Vdc 6A 1-phase: 90…264 Vac / 100...370 Vdc (1) (7) CSF5P XCSF5P 18
24 Vdc 6A 2-phase: 340…550 Vac (4) CSB150C XCSB150C 23
24 Vdc 6A 3-phase: 340…550 Vac / 507…700 Vdc (5) CSG06 XCSG06 24
24 Vdc 6A 3-phase: 340…550 Vac / 507…700 Vdc (5) (8) CSG06P XCSG06P 24
24 Vdc 10 A 1-phase: 120 Vac / 230 Vac (2) CSF10 XCSF10 19
24 Vdc 10 A 1-phase: 120 Vac / 230 Vac (2) (7) CSF10P XCSF10P 19
24 Vdc 10 A 1 or 2-phase: 185...550 Vac (3) CSW240C XCSW240C 22
24 Vdc 10 A 3-phase: 340…550 Vac / 507…700 Vdc (5) CSG10 XCSG10 24
24 Vdc 10 A 3-phase: 340…550 Vac / 507…700 Vdc (5) (8) CSG10P XCSG10P 24
24 Vdc 20 A 1-phase: 120 Vac / 230 Vac (2) CSF20 XCSF20 19
24 Vdc 20 A 1-phase: 120 Vac / 230 Vac (2) (7) CSF20P XCSF20P 19
24 Vdc 20 A 1-phase: 120 Vac / 230 Vac (2) CSF500C XCSF500C 20
24 Vdc 20 A 1-phase: 120 Vac / 230 Vac (2) (8) CSF500CP XCSF500CP 20
24 Vdc 20 A 3-phase: 340…550 Vac / 507…700 Vdc (5) CSG20 XCSG20 25
24 Vdc 20 A 3-phase: 340…550 Vac / 507…700 Vdc (5) (8) CSG20P XCSG20P 25
24 Vdc 20 A 3-phase: 176…264 Vac (5) CSG20R XCSG20R 25
24 Vdc 20 A 3-phase: 340…550 Vac / 507…700 Vdc (5) CSG500C XCSG500C 26
24 Vdc 30 A 3-phase: 340…550 Vac / 507…700 Vdc (5) (8) CSG30P XCSG30P 27
24 Vdc 30 A 3-phase: 340…550 Vac / 507…700 Vdc (5) (8) CSG750C XCSG750C 27
24 Vdc 42 A 3-phase: 340…550 Vac / 507…700 Vdc (5) CSG42 XCSG42 28
24 Vdc 100 A 3-phase: 340…550 Vac / 507…700 Vdc (5) CSG2400C XCSG2400C 28
Switching power supply with input from trasformer and out 24 Vdc
Output Output Input Notes Type Cat. No. Page
voltage current Tipology Voltage
24 Vdc 3A From trasformer: 24 Vac (6) CSE3 XCSE3 44
24 Vdc 5A From trasformer: 24 Vac (6) CSE5 XCSE5 44
24 Vdc 10 A From trasformer: 24 Vac (6) CSE10 XCSE10 45
24 Vdc 12 A From trasformer: 24 Vac (6) CS1224/24 XAS12VC 45
Notes
(1) wide range single-phase input (6) input from a secondary of a transformer
(2) double range single-phase input (7) with failure contact (power good) and Oring diode for redundant parallel
(3) single-phase and two-phase input (8) with failure contact (power good)
(4) two-phase input (9) with adjustable output
(5) three-phase input (10) DC/DC converter
13
Power supply selection table
Switching power supply out 5 - 12 - 15 - 48 Vdc
Output Output Input Notes Type Cat. No. Page
voltage current Tipology Voltage
5…15 Vdc 3…1.5 A 1-phase: 90…264 Vac / 100...370 Vdc (1) (9) CS7 XAS7 41
5…15 Vdc 3…1.5 A 1-phase: 90…264 Vac / 100...370 Vdc (1) (9) CSD30E XCSD30E 41
±12…±15 Vdc 0.6 A 1-phase: 90…264 Vac / 100...370 Vdc (1) (9) CSD30F XCSD30F 42
12 Vdc 1.2 A 1-phase: 90…264 Vac / 100...370 Vdc (1) CSD15B XCSD15B 30
12…15 Vdc 3.5…3 A 1-phase: 90…264 Vac / 100...370 Vdc (1) (9) CSD50B XCSD50B 30
12…15 Vdc 6…5 A 1-phase: 90…264 Vac / 100...370 Vdc (1) (9) CSF3B XCSF3B 31
12…15 Vdc 8…7 A 1-phase: 90…264 Vac / 100...370 Vdc (1) (9) CSF5B XCSF5B 31
12…15 Vdc 8…7 A 1 or 2-phase: 185...550 Vac (3) (9) CSW120B XCSW120B 33
12…15 Vdc 8…7 A 2-phase: 340…550 Vac (4) (9) CSB150B XCSB150B 34
12…15 Vdc 16…15 A 1 or 2-phase: 185...550 Vac (3) (9) CSW240B XCSW240B 33
12…15 Vdc 16 A 1-phase: 120 Vac / 230 Vac (2) (9) CSF10B XCSF10B 32
12 Vdc 42 A 3-phase: 340…550 Vac / 507…700 Vdc (5) CSG20B XCSG20B 35
48 Vdc 0.4 A 1-phase: 90…264 Vac / 100...370 Vdc (1) CS0448/H-B XAS004YHB 36
48 Vdc 2A 1-phase: 90…264 Vac / 100...370 Vdc (1) (7) CS248/90-264P XAS02YHP 36
48 Vdc 2.5 A 1-phase: 90…264 Vac / 100...370 Vdc (1) CSF5D XCSF5D 37
48 Vdc 2.5 A 1-phase: 90…264 Vac / 100...370 Vdc (1) (7) CSF5DP XCSF5DP 37
48 Vdc 3A 2-phase: 340…550 Vac (4) CSB150D XCSB150D 39
48 Vdc 5A 1-phase: 120 Vac / 230 Vac (2) CSF10D XCSF10D 37
48 Vdc 5A 1 or 2-phase: 185...550 Vac (3) CSW240D XCSW240D 38
48 Vdc 50 A 3-phase: 340…550 Vac / 507…700 Vdc (5) CSG2400D XCSG2400D 40
Notes
(1) wide range single-phase input (5) three-phase input
(2) double range single-phase input (6) input from a secondary of a transformer
(3) single-phase and two-phase input (7) with failure contact (power good) and Oring diode for redundant parallel
(4) two-phase input (9) with adjustable output
14
Single-phase switching
power supply 120-230 Vac 90
regulated output 24 Vdc (3.54 in)
90
(3.54 in)
15
Single-phase switching
power supply 120-230 Vac
80
24 Vdc regulated output (3.15 in)
87
(3.43 in)
16
Single-phase switching
power supply 120-230 Vac 90
24 Vdc regulated output (3.54 in)
17
Single-phase switching
power supply 120-230 Vac 115 115
24 Vdc regulated output (4.53 in) (4.53 in)
18
Single-phase switching
power supply 120-230 Vac
24 Vdc regulated output 140
(5.51 in)
130
(5.12 in)
• Single-phase input 120 and 230 Vac
• Short circuit, overload, over temperature, input / output overvoltage
protection 137
(5.39 in) 220 90
• High outrush current for starting-up heavy loads and to guarantee 73
(8.67 in) (3.55 in)
the selectivity of the 24 V lines (2.87 in)
• High efficiency and low dissipated power
• Designed for use with SELV and PELV circuitry 24 Vdc 10 A @ 45°C - 240 W 24 Vdc 20 A @ 45°C - 480 W
19
Single-phase switching
power supply 120-230 Vac
24 Vdc regulated output 127
(5 in)
• Single-phase input, selectable, 120 or 230 Vac
• Short circuit, overload, over temperature, input / output over-
voltage protection 139
• High outrush current for starting-up heavy loads and to guaran- 80
(3.15 in) (5.47 in)
tee the reliability of the 24 Vdc output
• High efficiency (92%) and low dissipated power
• Designed for use with SELV and PELV circuitry 24 Vdc 21 A @ 45°C - 504 W
20
Single-phase / two-phase switching
power supply 230-400-500 Vac
115 115
24 Vdc regulated output (4.53 in) (4.53 in)
• High reliability and immunity against over voltage due to failures on AC line
• Both single-phase and two-phase 185...550 Vac 130 130
• Short circuit, overload, over temperature, input / output overvoltage protection (5.12 in) (5.12 in)
• High outrush current for starting-up heavy loads and to guarantee the reliability 55 55
of the 24 Vdc output (2.17 in) (2.17 in)
• High efficiency and low dissipated power
• Designed for use with SELV and PELV circuitry 24 Vdc 3.2 A @ 45°C - 77 W 24 Vdc 5 A @ 45°C - 120 W
• Pluggable connections
NOTES BLOCK DIAGRAM BLOCK DIAGRAM
The height dimension includes 35 mm DIN rail
(1) Version with Oring diode and failure contact for redundant parallel con-
nection
Version available upon request; for information call our sales department,
local agent or representative
(2) 550 Vdc max for UL508
21
Single-phase / two-phase switching
power supply 230-400-500 Vac
140
24 Vdc regulated output (5.52 in)
• High reliability and immunity against over voltage due to failures on AC line
• Both single-phase and two-phase 185...550 Vac
• Short circuit, overload, over temperature, input / output overvoltage protection 125
• High outrush current for starting-up heavy loads and to guarantee the 74 (4.93 in)
reliability of the 24 Vdc output (2.92 in)
• High efficiency and low dissipated power
• Designed for use with SELV and PELV circuitry 24 Vdc 10 A @ 50°C - 240 W
22
Two-phase switching
power supply 400-500 Vac
115
24 Vdc regulated output (4.53 in)
23
Three-phase switching
power supply 400-500 Vac
24 Vdc regulated output 130
(5.12 in)
130
(5.12 in)
• High efficiency and low dissipated power
• Can be supplied with two phases
• High outrush current for starting-up heavy loads and to guaran- 90 90
tee the reliability of the 24 Vdc output 90 (3.54 in) 90 (3.54 in)
• Short circuit, overload, over temperature, input / output over- (3.54 in) (3.54 in)
voltage protection
• Designed for use with SELV and PELV circuitry 24 Vdc 6 A @ 45°C - 144 W 24 Vdc 10 A @ 45°C - 240 W
24
Three-phase switching
power supply 400-500 Vac
24 Vdc regulated output 130
(5.12 in)
130
(5.12 in)
• High efficiency and low dissipated power
• Can be supplied with two phases
• High outrush current for starting-up heavy loads and to guaran-
tee the reliability of the 24 Vdc output 220 90 220 90
• Short circuit, overload, over temperature, input / output over- (8.67 in) (3.55 in) (8.67 in) (3.55 in)
voltage protection
• Designed for use with SELV and PELV circuitry 24 Vdc 20 A @ 45°C - 480 W 24 Vdc 20 A @ 45°C - 480 W
25
Three-phase switching
power supply 400-500 Vac
24 Vdc regulated output 127
(5.99 in)
• High efficiency (94.5%) and low dissipated power
• Space saving design
• Can be supplied with two phases 139
• High outrush current for starting-up heavy loads and to guaran- 80
tee the reliability of the 24 Vdc output (3.15 in) (5.47 in)
• Short circuit, overload, over temperature, input / output over-
voltage protection 24 Vdc 21 A @ 45°C - 504 W
• Designed for use with SELV and PELV circuitry
NOTES BLOCK DIAGRAM
The height dimension includes 35 mm DIN rail
(1) 550 Vdc max for UL 508c
(2) Hiccup output protection is preset into "Auto reset" mode; to prevent unwanted
restart of the machinery, acc. to EN61204, on front panel a jumper bridge allows to
select "Manual reset" output protection mode (or "fuse mode")
26
Three-phase switching
power supply 400-500 Vac
24 Vdc regulated output 127
(5.99 in)
130
(5.12 in)
• High efficiency and low dissipated power
• Can be supplied with two phases
• High outrush current for starting-up heavy loads and to guaran- 139
tee the reliability of the 24 Vdc output 80 220 90
(3.15 in) (5.47 in) (8.67 in) (3.55 in)
• Short circuit, overload, over temperature, input / output over-
voltage protection
• Designed for use with SELV and PELV circuitry 24 Vdc 30 A @ 45°C - 720 W 24 Vdc 30 A @ 45°C - 720 W
27
Three-phase switching
power supply 400-500 Vac
24 Vdc regulated output 130 170
(5.12 in) (6.69 in)
• High efficiency and low dissipated power
• Can be supplied with two phases
• High outrush current for starting-up heavy loads and to guaran-
tee the reliability of the 24 Vdc output 240 105 310 130
• Short circuit, overload, over temperature, input / output over- (9.45 in) (4.13 in) (12.2 in) (5.12 in)
voltage protection
• Designed for use with SELV and PELV circuitry 24 Vdc 42 A @ 45°C - 1000 W 24 Vdc 100 A @ 45°C - 2400 W
28
Single-phase switching
power supply 120-230 Vac
5 Vdc regulated output 115
(4.53 in)
• Single-phase input 90…264 Vac and DC 100…370 Vdc
• Short circuit, overload, over temperature, input / output overvoltage
protection 130
• Designed for use with SELV and PELV circuitry 55 (5.12 in)
• Pluggable connections (2.17 in)
5 Vdc 8 A @ 45°C - 40 W
29
Single-phase switching
power supply 120-230 Vac 90 90
12…15 Vdc regulated output (3.54 in) (3.54 in)
30
Single-phase switching
power supply 120-230 Vac
12…15 Vdc regulated output 115
(4.53 in)
115
(4.53 in)
31
Single-phase switching
power supply 120-230 Vac
12…15 Vdc regulated output 140
(5.51 in)
• Single-phase input 120 and 230 Vac
• Short circuit, overload, over temperature, input / output over-
voltage protection
• High outrush current for starting-up heavy loads and to guaran- 137
tee the reliability of the 24 Vdc output 73 (5.39 in)
• High efficiency and low dissipated power (2.87 in)
• Designed for use with SELV and PELV circuitry 12 Vdc 16 A @ 45°C - 240 W
• Pluggable connections 15 Vdc 16 A @ 45°C - 240 W
NOTES BLOCK DIAGRAM
The height dimension includes 35 mm DIN rail
(1) Version available upon request; for information call our sales department, local
agent or representative
32
Single-phase / two-phase switching
power supply 230-400-500 Vac 115 140
12…15 Vdc regulated output (4.53 in) (5.51 in)
• High reliability and immunity against over voltage due to failures on AC line
• Both single-phase and two-phase 185...550 Vac 130
• Short circuit, overload, over temperature, input / output overvoltage protection 125
55 (5.12 in) 74 (4.92 in)
• High outrush current for starting-up heavy loads and to guarantee the reliability
of the 24 Vdc output (2.17 in) (2.91 in)
• High efficiency and low dissipated power 12 Vdc 8 A @ 45°C - 105 W 12 Vdc 16 A @ 45°C - 225 W
• Designed for use with SELV and PELV circuitry 15 Vdc 7 A @ 45°C - 105 W 15 Vdc 15 A @ 45°C - 225 W
• Pluggable connections
NOTES BLOCK DIAGRAM BLOCK DIAGRAM
The height dimension includes 35 mm DIN rail
(1) Version with Oring diode and failure contact for redundant parallel
connection
(2) Version available upon request; for information call our sales depart-
ment, local agent or representative
(3) 550 Vdc max per UL508
33
Two-phase switching
power supply 400-500 Vac
115
12…15 Vdc regulated output (4.53 in)
34
Three-phase switching
power supply 400-500 Vac
12 Vdc regulated output 125
(4.93 in)
• High efficiency and low dissipated power
• Can be supplied with two phases
• High outrush current for starting-up heavy loads and to guaran- 245 135
tee the reliability of the 24 Vdc output (9.65 in)
• Short circuit, overload, over temperature, input / output overvolt- (3.32 in)
age protection 12...15 Vdc 42 A @ 45°C - 630 W
• Designed for use with SELV and PELV circuitry
NOTES BLOCK DIAGRAM
The height dimension includes 35 mm DIN rail
35
Single-phase switching
power supply 120-230 Vac 125
48 Vdc regulated output 130 (4.92 in)
(5.12 in)
• Single-phase input 90…264 Vac and DC 100…370 Vdc
• Short circuit, overload, over temperature, input / output over-
voltage protection 130
80 55
• Low noise 40 (5.12 in)
(3.15 in) (2.17 in)
• Hold up time up to 300 ms (CS0448/H-B) (1.58 in)
• Designed for use with SELV and PELV circuitry and telecom
applications 48 Vdc 0.4 A @ 45°C - 19 W 8 Vdc 2 A @ 45°C - 96 W
APPROVALS
GENERAL TECHNICAL DATA
Efficiency > 78% > 85% @ 120 Vac
Dissipated power 5.5 W 17 W
Operating temperature -10...50°C -10...50°C -0.1 A/°C over 45 °C
Input / output isolation 3 KVac / 60 s 3 KVac / 60 s
Input / ground isolation 1.5 KVac / 60 s 1.7 KVac / 60 s
Output / ground isolation 0.5 KVac / 60 s 0.5 KVac / 60 s
Protection degree IP 20 IP 20
Standard / approvals EN50178, EN61558, EN60950 EN50178, EN61558, EN60950
EMC Standards EN61000-6-2, EN61000-6-4, EN55011,EN61000-4-2, EN61000-4-3, EN61000-6-2, EN61000-6-4, EN55011,EN61000-4-2, EN61000-4-3,
EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-11 EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-11
Connection terminal 2.5 mm2, screw type pluggable (24-12 AWG) 2.5 mm2, screw type pluggable (24-12 AWG)
Housing material aluminium aluminium
Approx. weight 400 g (0.88 lbs) 600 g (1.32 lbs)
Mounting information vertical on rail, allow 20 mm spacing between adjacent vertical on rail, allow 20 mm spacing between adjacent
components components
Mounting rail type PR/3/AC - PR/3/AS PR/3/AC - PR/3/AS
according to IEC60715/TH35
36
Single-phase switching
power supply 120-230 Vac
48 Vdc regulated output 115
(4.53 in)
140
(5.51 in)
37
Single-phase / two-phase switching
power supply 230-400-500 Vac
48 Vdc regulated output 140
(5.52 in)
• High reliability and immunity against over voltage due to failures on AC line
• Both single-phase and two-phase 185...550 Vac
• Short circuit, overload, over temperature, input / output overvoltage protection 125
• High outrush current for starting-up heavy loads and to guarantee the reliability 74 (4.93 in)
of the 24 Vdc output (2.92 in)
• High efficiency and low dissipated power
• Designed for use with SELV and PELV circuitry 48 Vdc 5 A @ 50°C - 240 W
• Pluggable connections
NOTES BLOCK DIAGRAM
The height dimension includes 35 mm DIN rail
(1) Version with Oring diode and failure contact for redundant parallel
connection
(2) 550 Vdc max for UL508
(3) Can be achieved 110 Vdc output voltage, with the series connection
of the output of two p.s. adjusted at 55 Vdc
(4) Version available upon request; for information call our sales depart-
ment, local agent or representative
38
Two-phase switching
power supply 400-500 Vac
48 Vdc regulated output 115
(4.53 in)
• Two-phase input 340…550 Vac
• Using 2 legs of a 3 phase circuit will save cabling costs and line
protection costs. 130
• Short circuit, overload, over temperature, input / output over- 55 (5.12 in)
voltage protection (2.17 in)
• High efficiency and low dissipated power
• Designed for use with SELV and PELV circuitry 48 Vdc 3 A @ 60°C - 144 W
39
Three-phase switching
power supply 400-500 Vac
48 Vdc regulated output 170
(6.7 in)
• Regulated switching power supply
• Three-phase input 340…360 Vac
• Short circuit, overload, over temperature protection 310 130
(12.21 in) (5.12 in)
48 Vdc 50 A @ 45°C - 240 W
40
Single-phase switching
power supply 120-230 Vac 80
adjustable output 5…15 Vdc (3.15 in)
90
(3.54 in)
41
Single phase switching power
supply 120-230 Vac dual
90
voltage output ±12…±15 Vdc (3.54 in)
42
IP65 Single-phase
switching power supply
120-230 Vac 120
(4.72 in)
120
(4.72 in)
43
Switching power supply
24 Vac input 118 118
24 Vdc regulated output (4.64 in) (4.64 in)
44
Switching power supply
24 Vac input 150
24 Vdc regulated output (5.5 in)
115
“ P r e l i m i n a r y ” (4.53 in)
APPROVALS
GENERAL TECHNICAL DATA
Efficiency ≥ 90% ≥ 90%
Dissipated power < 32 W 26 W max
Operating temperature -10...50°C, -0.5 A/°C over 45°C -10...+45°C; over 45°C derating -0.5 A/°C
Input / output isolation — —
Input / ground isolation — —
Output / ground isolation 0.5 KVac / 60 s 0.5 KVac / 60 s
Protection degree IP 20 IP 20 IEC529, EN60529
Standard / approvals — —
EMC Standards EN 50081-1, EN61000-6-4 EN55011; EN55022
Surge immunity varistor - 4.5 KA 8/20 in input varistor - 4.5 KA 8/20 in input
Connection terminal 2.5 mm2, screw type pluggable (24-12 AWG) 2.5 mm2, screw type pluggable (24-12 AWG)
Housing material aluminium aluminium
Approx. weight 900 g (1.98 lbs) 600 g (1.32 lbs)
Mounting information vertical on rail, allow 20 mm spacing between adjacent vertical on rail, allow 20 mm spacing between adjacent
components components
Mounting rail type PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB
according to IEC60715/TH35-7.5
45
Adjustable
linear
power supply 130 118
(5.1 in) (4.6 in)
• Adjustable output from 1.2 to 24 Vdc
• Output current 1.5 and 4 A max
• Short circuit, overload, over temperature protection
• DIN rail mounting 43 74 37 115
(1.7 in) (2.9 in) (1.5 in) (4.5 in)
1.2...24 Vdc 1.5 A @ 25°C - 36 W 1.2...24 Vdc 5 A @ 25°C - 120 W
Tab. 1 Tab. 2
INPUT OUTPUT I OUT max (A) I OUT max (A) INPUT OUTPUT I OUT max (A) I OUT max (A)
( Vac) (Vdc) XCL1R XCL5R ( Vac) (Vdc) XCL1R XCL5R
24 - 27 24 1.5 5 24 24 1.5 5
16 - 18 15 1.5 5 24 15 0.8 2.5
14 - 16 12 1.5 5 24 12 0.7 2
12 - 14 10 1.5 5 24 10 0.5 1.5
12 9 1.5 5 24 9 0.45 1.3
9 5 1.5 5 24 5 0.3 0.8
46
Filtered power supplies
without transformer with
non regulated output 77 93
(3.1 in) (3.7 in)
• DIN rail mounting
• Suitable for rectifying 6....20 Vac
• Voutput = Vac input x1.41 (-1V)
12 70
(0.5 in) 45 (2.7 in) 60
(1.8 in) (2.4 in)
Tab. 1 Tab. 1
INPUT OUTPUT OUTPUT INPUT OUTPUT OUTPUT
without load full load without load full load
( Vac) (Vdc) (Vdc) ( Vac) (Vdc) (Vdc)
47
Filtered power supplies
without transformer with
non regulated output 93 93
(3.7 in) (3.7 in)
• DIN rail mounting
• Suitable for rectifying 6....20 Vac
• Voutput = Vac input x1.41 (-1V)
70 70
(2.7 in) 60 (2.7 in) 60
(2.4 in) (2.4 in)
Tab. 1 Tab. 1
INPUT OUTPUT OUTPUT INPUT OUTPUT OUTPUT
without load full load without load full load
( Vac) (Vdc) (Vdc) ( Vac) (Vdc) (Vdc)
48
Filtered power supply
without transformer with
non regulated output 130 130
(5.12 in) (5.12 in)
• DIN rail mounting
• Suitable for rectifying 6....20 Vac
• Voutput = Vac input x1.41 (-1V)
140 140
(5.5 in) 110 (5.5 in) 110
(4.3 in) (4.3 in)
Tab. 1 Tab. 1
INPUT OUTPUT OUTPUT INPUT OUTPUT OUTPUT
without load full load without load full load
( Vac) (Vdc) (Vdc) ( Vac) (Vdc) (Vdc)
49
DC/DC Converter
48 Vdc input
24 Vdc regulated output 80
(3.15 in)
PE
50
Accessory
for charging
buffer batteries 93
(3.66)
• Battery charger
• Allows to connect in redundant parallel two power
supplies
• Suitable for power supplies up to 10 A 26
• Battery protection fuse (1.02 in)
• Battery feedback protection diode 80
• Current charge limiting resistor (3.15 in)
BATTERY
L AC + + +
GND (A) – +
(C)
CSBC
+ –
N AC – – –
IN OUT
+
(B)
BATTERY
–
GENERAL TECHNICAL DATA
(A) Power supply Power supply rated voltage 6...30 Vdc
(B) Battery Power supply rated current >3A
(C) CS-UPS1 Load rated voltage 6...29.5 Vdc
Load max current 10 A
Parallel connection of power supplies Charge current limitation 0.6 A (1)
It is possible to use this module also to connect two power supplies in paral- Battery disconnecting voltage —
lel, not provided with output decoupling diode, eliminating "Fuse 2" in series I/O drop voltage 0.5 V
to charging current limiting resistor. Battery protection fuse F1 = T 6.3 A / F2 = T 1 A
The next picture shows the connections. Protections short circuit / battery overload
L AC + + + Alarm signal —
GND (A) – + Connection terminal 2.5 mm2, screw type (24-12 AWG)
(C)
CSBC
+ – Operating temperature -10°C - +50°C
N AC – – – Housing material polyamide UL94V-0
IN OUT Approx. weight 80 g (0.18 lbs)
AC + Mounting information vertical on rail without spacing
GND (A) Mounting rail type PR/3/AC - PR/3/AS
IEC60715/TH35-7.5
AC – Mounting rail type PR/DIN/AC - PR/DIN/AS - PR/DIN/AL
according to IEC60715/G32
(A) Power supply
(C) CSBC
51
Accessory for charging
and controlling buffer
batteries 113
(4.45 in)
• Suitable for power supplies with Vout = 24...28.5
• Suitable for lead batteries
• Suitable for charging batteries while feeding loads 130
• Battery protection fuse 55 (5.12 in)
• "Deep discharge" battery protection (2.17 in)
• Status diplay LED and failure contact
(B)
52
Accessory for power
supplies redundant
parallel connections 130
(5.12 in)
• Suitable for power supplies without Oring diodes
• Compact dimensions
• 3 selectable voltages 12, 24 and 48 Vdc
• 2 status relays/contacts 43
• Power supplied status LED (1.69 in)
85
(3.35 in)
AC
OUT
GND (A)
(B)
AC
AC
ALARM
GND (A)
GENERAL TECHNICAL DATA
AC
IN OUT Input rated voltage (from power supply) 12–24–48 Vdc to select
Rated current 15 A max @ 45°C
Voltage drop 15 A and 0.7 V
Operating temperature -10…+50°C
(A) Power supply Housing material polyamide UL94V-0
(B) CS-UPS1 Connection terminal 2.5 mm2, screw type (24-12 AWG)
Approx. weight 120 g (0.26 lbs)
Mounting information vertical on rail without spacing
Mounting rail type PR/3/AC – PR/3/AC/ZB – PR/3/AS – PR/3/AS/ZB
IEC60715/TH35-7.5
Mounting rail type PR/DIN/AC – PR/DIN/AS – PR/DIN/AL
according to IEC60715/G32
53
Surge Protection
Devices
Surge Protection Devices
The MA3000 Series surge protection devices prevent surges and transient overvoltages
conducted through AC power distribution boards from damaging electronic systems such
as instrumentation control panels, telemetry substations and fire and security alarm
installations. The JVS operates by limiting excess voltages to suitable lower levels for the
equipment previewed for employment in Overvoltage Category II (2.5 KV), in Class C
overvoltage security zone, like requested by the Standards IEC 1024, IEC 1312-1, EN
50083-1.
JVS Series
The surge protection device is made of a DIN rail mounted socket
equipped with double connection terminal blocks and a pluggable
module containing the overvoltage protection circuitry. This feature
makes it easy to remove the protection device during isolation tests and
for quick replacement. The MA 3000 can withstand a 20 times 10 kA
discharge current (waveform 8/20), and a single 40 kA (JVS1-C1P) and
70 kA (JVS1-E1P) peak current. As required by industry surge protection
device standards, the MA3000 series is provided with a disconnection
device that removes the SPD from the line in case of internal damage or short circuit, giving Lightning protection zones
a visible failure display on the front panel of the unit (picture no. 2). After a great number of Zone 0 - Zone where items are subject to direct lightning strikes
discharges and continued long service the module will lose protection capacity and can be or where an unattenuated electromagnetic field occurs as a result
replaced without disconnecting the circuit wiring. of the strike.
Zone 1 - Zone where items are subject to low level direct
Fuse and protection devices lightning strikes. The conducted impulse lightning currents and/or
The MA3000 Series surge protective devices are not designed with a built-in thermal switching surges are reduced compared with Zone 0.
disconnector, therefore they must be equipped with upstream protection against short-circuit Zone 2 - Remnants of lightning impulse currents and/or
currents and with a differential protection element for protection against indirect contact switching surges are reduced compared with Zone 1.
(generally already present in the installation). The MA3000 Series must not be installed Zone 3 - Surges, caused by oscillation effects, magnetic field
downstream of high sensitivity differential protection devices. couplings and internal switching surges are reduced compared
with Zone 2.
Connections A - Sub Station
The surge protection devices MA3000 series can be employed in these types of connections: B - Main distribution board
C - Heavy machinery
D - Local distribution board
E - Light machinery
F - Workstation
G - Equipment
picture no. 2
54
Surge protection device
90 90
(3.55 in) (3.55 in)
• Rugged contacts
• Pluggable protection
• Efficiency status indicator on front panel 68 68
• Rugged metal parallel connection bridges 18 (2.68 in) 18 (2.68 in)
(0.71 in) (0.71 in)
55