1 Mapping from BMK signals to rotary single codes for EU, AP and ZLA
BMK BMK Signal Importance Switch Activation Occurrence Lift or I/O Type Interface Zone Description
Signal Name Type Level Group to
Code
0001 DC normal NO High - 24V multiple Lift Input/Output User All World Zones Push Button / Lamp Car Call
0002 JDC normal NO High - 24V multiple Lift Input/Output User All World Zones Key Switch / Lamp Car Call
0003 DGSC normal NO High - 24V single Lift Input/Output User Europe Asia Push Button Guest Control Car
0004 DFDC normal NO High - 24V single Lift Input/Output User Europe Asia Push Button / Lamp Release Push Button Car Call
0005 DCH normal NO High - 24V multiple Lift Input/Output User Europe Asia Push Button / Lamp Car Call Handicapped
0006 DDF normal NO High - 24V single Lift Input/Output User All World Zones Push Button / Lamp Direct Travel
0007 DCW-U normal NO High - 24V single Lift Input/Output User All World Zones Push Button / Lamp Car Selection Up
0008 DCW-D normal NO High - 24V single Lift Input/Output User All World Zones Push Button / Lamp Car Selection Down
0009 JDFDC normal NO High - 24V single Lift Input/Output User Europe Asia Key Switch / Lamp Release Push Button Car Call
000A JDNF normal NO High - 24V single Lift Input/Output User All World Zones Switch / Lamp Emergency Floor Call
000B KL-V normal NC Low - 0V single Lift Input System All World Zones Contact Full Load
000C KL-X safety NC Low - 0V single Lift Input System All World Zones Contact Overload
000D KL-M normal NO High - 24V single Lift Input System All World Zones Contact Minimal Load
000E RESIL1 normal NO High - 24V single Lift Input/Output User All World Zones Reserve Lift Input / Output 1
000F RESIL2 normal NO High - 24V single Lift Input/Output User All World Zones Reserve Lift Input / Output 2
0010 RESIL3 normal NO High - 24V single Lift Input/Output User All World Zones Reserve Lift Input / Output 3
0011 DE-U normal NO High - 24V single Group Input/Output User All World Zones Push Button / Lamp Floor Call Up
0012 DE-D normal NO High - 24V single Group Input/Output User All World Zones Push Button / Lamp Floor Call Down
0013 JDE-U normal NO High - 24V single Group Input/Output User All World Zones Key Switch / Lamp Floor Call Up
0014 JDE-D normal NO High - 24V single Group Input/Output User All World Zones Key Switch / Lamp Floor Call Down
0015 JDNFG normal NO High - 24V single Group Input/Output User All World Zones Switch / Lamp Emergency Floor Call Group
0016 KTTC normal NC High - 24V single Lift Input User Europe Asia Switch Car Partition Door
0017 JBFFG critical NC Low - 0V double Group Input User All World Zones Switch Fire Service - Firefighting Elevators
0018 JBFFGH1 critical NC Low - 0V double Group Input User All World Zones Switch Fire Service with Alternative Recall Floor 1 - Firefighting Elevators
0019 JBFFGH2 critical NC Low - 0V double Group Input User All World Zones Switch Fire Service with Alternative Recall Floor 2 - Firefighting Elevators
001A JBFH1 critical NC Low - 0V double Group Input User All World Zones Switch Fire Service with Alternative Recall Floor 1