PROJECT : HIGH ALTITUDE BOXING RING AT HIMACHAL PRADESH

CONSULTANT : POORNA ENGINEERING CONSULTANTS


13/7/2019
SUBJECT : BILL OF QUANTITIES FOR ELECTRICAL WORKS

Sl.No. DESCRIPTION Amount (Rs.)

A. M.V. PANELS & DISTRIBUTION BOARDS

B. WIRING SYSTEM

C. SUPPLY & INSTALLATION OF LIGHT & FAN


FIXTURES

D. EARTHING SYSTEM

E. MISCELLANEOUS WORKS

TOTAL

Exclusions :

1.0 Incoming cable for Meter board from existing point of power supply
2.0 Supply of 15W LED surface / suspended light fixture

Poorna Engineering Consultants


1 of 10
Sl. No. DESCRIPTION UNIT QTY RATE AMOUNT

A. M.V. PANELS & DISTRIBUTION BOARDS :

1.0 Supply, installation, testing and commissioning of M.V.


panels and switch gears suitable for 415V, 3phase, 4
wire, 50Hz power distribution system. The panel shall
be free standing floor mounting type sheet steel
enclosed, flush front with aluminium bus bars and
seperate earth bus to be provided through out the
length of the panel. The incoming and out going feeders
breakers, change over switches, fuses, indicating lamps
shall be accomodated in a modular multitier
arrangement. Minimum clearance of 400mm shall be
provided from the floor level to the bottom most
termination point. Adequate size cable alley and bus
bar chamber shall be provided all round the panel and it
shall be connected through solid bus bars. Flexible
cable links are not acceptable .

Bus bars shall be provided with sleeves or heat


resistant insulated paint. The panel shall be suitable for
both top/bottom entry. The minimum fault rupturing
capacity of all incoming and out going breakers /
switches shall be as per SLD only. The panel shall be
powder coated with 90micron thick seimens grey colour
with the relevant IS code. The panel shall be fabricated
only after obtaining approval of the GA drawings. The
rate shall also include cost of civil works including fixing
accessories etc., all complete as required.

1.1 METER BOARD (OUTDOOR)


(As per dwg no. HAB/PECS-1922/EL-01)
Supply set 1
Installation set 1

Poorna Engineering Consultants


2 of 10
Sl. No. DESCRIPTION UNIT QTY RATE AMOUNT
2.0 MCB DISTRIBUTION BOARD
Supply, installation, testing and commissioning of the
following cubicle type 1.2 mm thick CRCA sheet steel
enclosed powder coated with approved shade and
partitions to segregate phase with approved covers,
double door, factory made recessed in wall or surface
mounted final distribution boards of the following
description. All final DB's shall have outgoing with
internal wiring brought upto terminal block for external
cable connections.

NOTE : 1) Surface mounted DB's on walls shall be


provided with suitable size frame work and neatly
grouted on to wall and DB shall be fixed on to the frame
work using bolts & nuts and other fixing accessories.

2) DB's conceald in wall shall include cut of necessary


civil works and other fixing accessories.
3) The DB's shall be horizontal / vertical / phase
seggregated /Flexi type as per configuration of
incoming/outgoing feeders.
4) The DB's shall be factory made of approved make
and necessary available higher size configured DB's
shall be used.

2.1 DB
Incomer:
1 No. 40A TPN MCB
Sub incomer
3 nos. 40A DP RCBO (0-30mA)
Outgoing:
18 Nos. of 6/10/16/20 A SP MCBs
Supply Set 1
Installation Set 1

TOTAL

Poorna Engineering Consultants


3 of 10
Sl. No. DESCRIPTION UNIT QTY RATE AMOUNT
B. WIRING SYSTEM

1.0 Supply and wiring for lights, ceiling fans, exhaust fans
and 6A socket outlet using 1.5sqmm (point wiring),
flexible copper conductor 1100Volts grade PVC
insulated, FRLS wires drawn through 2mm thick,
suitable size FR PVC conduit in a concealed manner
using necessary conduit accessories like junction
boxes switch boxes, bends collars, clamps ceiling roses
6A switches, fan regulator and hook boxes, etc. shall be
flush mounted in brick wall or in the built up furnitures or
on the surface of wall for surface installation as
required. The rate for point wiring shall include the
wiring from distribution /switch board up to first light /
fan/ control fan/6A socket outlets etc., Also the rate
shall include earthing of each light, fan outlet boxes,
switch control boxes 6A sockets using 1.0 sqmm,
flexible copper, PVC insulated wires. (switches &
sockets shall be of Anchor roma make /equivalent).
The rate shall also include cost of civil works involved in
fixing of boxes, replastering of walls chased.

a) Single light point controlled by a 6A, SP switch. Nos 7

b) Two light point controlled by a 6A SP switch. Nos 5

c) One light point controlled by 2 Nos 6A SP, two way


switch. Nos R.O

d) Three light points controlled by a 6A SP switch. Nos 2

e) Four light points controlled by a 6A SP switch. Nos 6

f) Five light points controlled by a 6A SP switch. Nos R.O

g) Ceiling fan point controlled by a 6A SP switch and


stepped fan regulator. The rate shall include cost of
electronic fan regulator fan hook switch outlet box etc.
all complete as required. Nos 2

h) Exhaust fan point (Single phase) controlled by a 6A SP


switch and 6A Socket outlet near the exhaust fan. Nos 2

i) Supply and wiring for 6A dependent three pin switched


sockets outlet box including providing 6A switched
sockets & interconnection as required. Nos R.O

j) Supply and wiring for 6A independent three pin


switched socket outlet installed in a switch outlet box
including providing 6A switched socket as required. Nos R.O

Poorna Engineering Consultants


4 of 10
Sl. No. DESCRIPTION UNIT QTY RATE AMOUNT
2.0 Supply & Wiring for Lights, Ceiling fans, exhaust fan
and 6A socket outlets using 2.5 sqmm flexible copper,
1100 volts grade PVC insulated FRLS wires drawn
through 2mm thick, suitable size FR PVC conduit in
concealed manner using necessary conduit accessories
like junction boxes, bends, collars, clamps, ceiling
roses etc., and shall be flush mounted in brick wall or
on the surface of wall for surface installation as
required. The rate for point wiring shall include the
wiring from distribution board to light points. Also the
rate shall include earthing of each light point using
1.5sqmm, flexible, copper conductor, PVC insulated
wires. The rate shall include chasing of walls / floors
and plastering the chased portion as required.

Note : 1) MCB's shall be measured separately.


2) The additional length of
point wiring shall be measured separately as lighting
circuit.
a) 6 Lights controled by 10A, SP MCB
(Avg. length = 21.0 M) Nos R.O

b) 7 Lights controled by 10A, SP MCB (Avg. length = 23.0


M) Nos R.O

c) 8 Lights controled by 10A, SP MCB (Avg. length = 26.0


M) Nos 2

d) 9 Lights controlled by 10A, SP MCB (Avg. length = 30.0


M) Nos R.O

e) 10 Lights controled by 10A, SP MCB (Avg. length =


33.0 M) Nos R.O

Poorna Engineering Consultants


5 of 10
Sl. No. DESCRIPTION UNIT QTY RATE AMOUNT
3.0 LIGHTING WIRING / SUB MAINS :
Supply and wiring for circuit mains using flexible,
copper, 1100 V grade, PVC insulated FRLS wires
drawn through 2mm thick suitable size FR PVC conduit
with all necessary accessories, like, bends, elbows,
junction boxes etc., (The light circuit mains will be
measured in running meters from distribution boards
upto the first light/switch point or fan or 5A first socket
outlet point whichever nearer, then onwards it will be
included in point wiring)

a) 2 Nos. 1.5sq.mm + 1No.1.0 q.mm copper wires in


20mm dia PVC conduit. Rmtr. 50

b) 2 Nos. 2.5sq.mm + 1No.1.5 q.mm copper wires in


20mm dia PVC conduit. Rmtr. 250

c) 4 Nos. 2.5sq.mm + 2Nos. 1.5 sq.mm copper wires in


25mm dia PVC conduit. Rmtr. 50

4.0 POWER WIRING / SUB MAINS :


Supply and drawing power wiring circuits /sub main
using stranded copper conductor, 1100 volts Grade,
FRLS PVC insulated wires drawn in 2mm thick suitable
size FR PVC conduit. The rate shall also include
running of PVC insulated copper conductor as earth
wire. The rate shall also include list of civil works such
as wall chasing, replastering after laying of conduits.

a) 2 Nos. 2.5sq.mm + 1No. 1.5 q.mm copper wires in


20mm dia PVC conduit. Rmtr. R.O

b) 2 Nos.4.0 sq.mm+ 1No. 2.5 sq.mm Copper wires in


20mm dia PVC conduit. Rmtr. 210

c) 4 Nos. 4.0sq.mm + 2 Nos.2.5 sqmm Copper wires in


25mm dia PVC conduit. Rmtr. R.O

d) 2 Nos. 6.0sqmm + 1No. 4.0 sqmm Copper wires in


25mm dia PVC conduit. Rmtr. R.O

e) 4 Nos. 6.0 sq.mm + 2 Nos. 4.0 sq.mm Copper wires in


32mm dia PVC conduit. Rmtr. R.O

f) 2 Nos. 10.0 sq.mm + 1No 6.0 sq.mm Copper wires in


32mm dia PVC conduit. Rmtr. R.O

Poorna Engineering Consultants


6 of 10
Sl. No. DESCRIPTION UNIT QTY RATE AMOUNT
g) 4 Nos.10.0 sq.mm + 2Nos. 6.0 sq.mm Copper wires in
38mm dia PVC conduit. Rmtr. 25

5.0 POWER RECEPTACLES


5.1 DOMESTIC TYPE:

Supply & fixing of 3/5 pin, commerical combination type


socket outlet with indicator mounted on a outlet box
with necessary interconnection. The box shall be flush
mounted in brick/stone wall (switches & sockets shall
be of Anchor roma make /equivalent) . The rate shall
also include cost of civil works involved in fixing of
boxes, replastering of walls chased.

a) 6A socket outlet controlled by 6A SP Switch Nos. 2

b) 2Nos. 6A socket outlet controlled by 6A SP Switch Nos. R.O

c) 6/16A socket outlet controlled by 1 Nos. 16A SP Switch


with indicator Nos. 14

d) 16A, socket outlet Nos. 1

e) 16A, switch with indicator Nos. 1

f) 6/16A Weather proof socket outlet controlled by 1 No.


16A SP Switch Nos. R.O

TOTAL

Poorna Engineering Consultants


7 of 10
Sl. No. DESCRIPTION UNIT QTY RATE AMOUNT
C. SUPPLY & INSTALLATION OF LIGHT & FAN FIXTURES

1.0 Supply, installation, testing and commissioning of


following type light and fan fixtures with tubes and all
other necessary fixing accessories all complete as
required.

2.1 40W LED suspension Linear batten light fixture of type


LL24-541-XXX-57-CD of wipro make/equivalent.
Supply Nos. 30
Installation Nos. 30

2.2 11W LED recess mounted light fixture of type LD71-


111-SML-65-XX of Wipro make/equivalent.
Supply Nos. 6
Installation Nos. 6

2.3 15W LED recess mounted light fixture of type LD71-


161-SML-65-XX of Wipro make/equivalent.
Supply Nos. 7
Installation Nos. 7

2.4 6W LED recess mounted light fixture of type


CRDL11R008HP57* of Wipro make/equivalent.
Supply Nos. 4
Installation Nos. 4

2.5 15W LED surface / suspended light fixture


(Installation only)
Installation Nos. 16

2.6 1200mm sweep, ceiling fan without fan regulator and


shall be of crompton /equivalent.
Supply Nos 2
Installation Nos 2

2.7 225/300mm dia. light duty, single phase. exhaust fan


with necessary angle iron bracket.
Supply Nos 2
Installation Nos 2

TOTAL

Poorna Engineering Consultants


8 of 10
Sl. No. DESCRIPTION UNIT QTY RATE AMOUNT
D. EARTHING SYSTEM

1.0 Supply & installation of 38mm dia, 2.5 Mtr. Long


G.I.pipe electrode earthing station complete with
manholes, brick masonry chamber, covers, funnel etc.,
The cost shall also include providing of salt and
charcoal layer by layer, excavation and back filling etc.,
all complete as required and shall confirm to IS - 3043.

Set 2

2.0 Supply & installation of 600 x 600 x 3 mm, copper plate


earthing station complete with GI pipe, manholes, brick
masonary chamber, covers, funnel, etc., The cost shall
also include providing of salt and charcoal layer by
layer, excavation and back filling etc., all complete as
required and shall confirm to IS - 3043.

Set R.O

3.0 Supply, installation & connecting of G.I.tape /wire being


clamped to walls, cable trays, ladders, run in pipes, laid
underground etc.,as required including interconnection
between the earth stations etc., all complete as
required. The rate shall include the cost of insulating
supports.

a) 25 x 6mm G.I. tape M R.O

b) 25 x 3mm GI tape M 25

c) 8 swg. G.I. wire M 25

d) 14 swg. copper wire M 25

TOTAL

Poorna Engineering Consultants


9 of 10
Sl. No. DESCRIPTION UNIT QTY RATE AMOUNT
E. MISCELLANEOUS WORKS :

1.0 Supply & laying of 2mm thick, FR PVC conduit with all
conduit accessories, G.I.fish wire, fixing accessories
etc., as required. The rate shall include chasing of walls
/ floors and plastering the chased portion as required.

a) 20mm dia M 25

b) 25mm dia M 25

c) 32mm dia M R.O

2.0 Supply & Fixing of DANGER / NO ADDMISSION. / NO


SMOKING / Board made out of MS sheet metal with 2
coats of non-corrosive enamelled paint of approved
shape and size as specified by local electrical
authorities written in English, Hindi and local
language.
Nos 1

3.0 Supply & Laying of rubber mats of 11kv grade, 1.8mtr.


x 0.9mtr. and of sufficient thickness as required by the
Electrical Inspectorate and confirming to IS 15652
Nos R.O

4.0 Supplying of first Aid box containing medicines for 50


persons to give first aid treatment. Nos 1

5.0 Supplying rubber gloves of electrical quality tested to 22


KV. Pair 1

6.0 Supply and fixing of conduit / structural steel support


ceiling suspended type / wall bracket type clamps with
necessary saddles for fixing of conduits / cables, cable
trays and where ever necessary. The detail of supports
shall be made as per the site condition and duly
approved by architect/ consultant before erection. (The
contractor shall submit the GA drawing for the supports
and shall be executed after getting approval from
consultant)
Kgs. 300

TOTAL

Poorna Engineering Consultants


10 of 10