Seismic Force
Direction of
L= 25.00 m tw= 0.35 m HL= 3.20 m Hw= 3.60 m
γL= 10.0 KN/m3
B= 50.00 m
Rectangular Tank Plan Rectangular Tank Elevation
2-Calculation the Height of center of gravity for impulsive hi & convective hc components:
3-Calculation the fundamental period of oscillation of the tank for impulsive Ti & convective Tc components:
= = ,∴ =( ) ∗ = 1535.9 KN/m
4-Calculation the total lateral impulsive force Pi & convective force Pc :
= 4.3 KN/m2
7- Load Cominations:
Note that, the Calculated Seismic Force E above is based on Strength-level Forces (ultimate loads).
For allowable stresses Design (ASD) Method (service loads), the design seismic forces shall be reduced by a factor of 1.4
ACI 350.3-06, Appendix B, Clause B.5
For Ultimate Strength Design method (factored loads), follow ACI 350-06, Clause 9.2.1 load combinations.