VT Sizing Calculation for

11kV O/G Feeder

Page 1 of 16
Larsen & Toubro Limited,
ECC Division - EDRC

Summary of Voltage Transformer Parameter for 11 KV Outgoing Feeder - BC-2 S/S (Adopted Parameters)

Project :GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Rev: A
Class of
Burden Provided
Sl No Description Core Nos. Ratio proposed Function accuracy as per Remarks
(VA)
60044-1
IEC 60044 1

C 11kV Outgoing Feeder VT

1 Outgoing Feeder VT Core-1 11 KV/√3 / 110 V/√3 Protection & Metering CL 1.0 / 3P 50

Page 2 of 16
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION - Doc No.: PH10-XX-XX-XX-XXXX Rev. A
PROJECT
PHASE X - SUBSTATIONS PRPD CHKD APPD DATE

TITLE VT Sizing calculation for BC-2 S/S - 11 kV Outgoing Feeder VT MM SMS AKS 10/11/2011

A. VT Sizing Calculation for 11kV Outgoing Feeder VT : A306 To A2006

Core Details Device Connected & Purpose


Core-1 : A306 To A2006 Metering (BCU)
1.1 Basic System Data

a. Nominal system voltage V : 11 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA (Short Circuit Rating of 11kV bus)

1.2 VT Details

a. VT : A306 To A2006

b. Voltage Rating : 11 KV/3 / 110 V/3

c. VA Rating : 50 VA

d. Class : CL.1.0 / 3P

1.3 VT Secondary Cable details

a. Size of the calble : 4 sq.mm

b. Material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistance R2lead : 2*L*Rcable/1000

: 2*100*5.52/1000

: 1.1040 Ohm/km

f. Max current to be carried by the lead : 50/63.51

: 0.8 A

g. Two way lead burden : 0.8*0.8*1.104

: 0.71 VA

1.4 Connected Burden Particulars - Core 1

BCU (C264) : 0.10 VA (Refer ANNEXURE - R4)

Lead Burden : 0.71 VA

Total Burden : 0.81 VA

With 20% Design margin : 1.0 VA

Rated VA Burden of the VT : 50 VA

The rated burden of the VT provided is more than the actual requirement. Hence the selected rated burden of the VT core is
adequate.

1.5 Summary

SL.No Core Ratio Burden Accuracy

1 Core-1 11 KV/√3 / 110 V/√3 50 VA CL.1.0 / 3P

Page 3 of 16
VT Sizing Calculation for
11kV Future Cap. Feeder

Page 4 of 16
Larsen & Toubro Limited,
ECC Division - EDRC

Summary of Voltage Transformer Parameter for 11 KV Future Cap. Feeder - BC-2 S/S (Adopted Parameters)

Project :GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Rev: A
Class of
Burden Provided
Sl No Description Core Nos. Ratio proposed Function accuracy as per Remarks
(VA)
60044-1
IEC 60044 1

C 11kV Future Capacitor Feeder VT

1 Outgoing Feeder VT Core-1 11 KV/√3 / 110 V/√3 Protection & Metering CL 1.0 / 3P 50

Page 5 of 16
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION - Doc No.: PH10-XX-XX-XX-XXXX Rev. A
PROJECT
PHASE X - SUBSTATIONS PRPD CHKD APPD DATE

TITLE VT Sizing calculation for BC-2 S/S - 11 kV Future Cap. Feeder VT MM SMS AKS 10/11/2011

A. VT Sizing Calculation for 11kV Future capcitor Feeder VT : A2106 To A2206

Core Details Device Connected & Purpose


Core-1 : A2106 To A2206 Metering (BCU)
1.1 Basic System Data

a. Nominal system voltage V : 11 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA (Short Circuit Rating of 11kV bus)

1.2 VT Details

a. VT : A2106 To A2206

b. Voltage Rating : 11 KV/3 / 110 V/3

c. VA Rating : 50 VA

d. Class : CL.1.0 / 3P

1.3 VT Secondary Cable details

a. Size of the calble : 4 sq.mm

b. Material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistance R2lead : 2*L*Rcable/1000

: 2*100*5.52/1000

: 1.1040 Ohm/km

f. Max current to be carried by the lead : 50/63.51

: 0.8 A

g. Two way lead burden : 0.8*0.8*1.104

: 0.71 VA

1.4 Connected Burden Particulars - Core 1

BCU (C264) : 0.10 VA (Refer ANNEXURE - R4)

Lead Burden : 0.71 VA

Total Burden : 0.81 VA

With 20% Design margin : 1.0 VA

Rated VA Burden of the VT : 50 VA

The rated burden of the VT provided is more than the actual requirement. Hence the selected rated burden of the VT core is
adequate.

1.5 Summary

SL.No Core Ratio Burden Accuracy

1 Core-1 11 KV/√3 / 110 V/√3 50 VA CL.1.0 / 3P

Page 6 of 16
VT Sizing Calculation for
11kV Incomer

Page 7 of 16
Larsen & Toubro Limited,
ECC Division - EDRC

Summary of Voltage Transformer Parameter for 132/11 KV Inter Bus Transformer - 11 KV side - BC-2 S/S (Adopted Parameters)

Project :GTC - 371A - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Rev: A
Class of
Burden Provided
Sl No Description Core Nos. Ratio proposed Function accuracy as per Remarks
(VA)
60044-1
IEC 60044 1

A 11kV Incomer VT

1 Incomer VT Core-1 11 KV/√3 / 110 V/√3 Protection & Metering CL 1.0 / 3P 100

Page 8 of 16
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION - Doc No.: PH10-XX-XX-XX-XXXX Rev. A
PROJECT
PHASE X - SUBSTATIONS PRPD CHKD APPD DATE
VT Sizing calculation for BC-2 S/S - 132/11 kV Interbus Transformer - 11
TITLE MM SMS AKS 10/11/2011
KV Side VT

A. VT Sizing Calculation for 132/11 kV Interbus Transformer - 11 kV Side VT (Typical) : A186 & A286

Core Details Device Connected & Purpose


Core-1 : A186 & A286 Metering (BCU)
1.1 Basic System Data

a. Nominal system voltage V : 11 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA (Short Circuit Rating of 11kV bus)

1.2 VT Details

a. VT : A186 & A286

b. Voltage Rating : 11 KV/3 / 110 V/3

c. VA Rating : 100 VA

d. Class : CL.1.0 / 3P

1.3 VT Secondary Cable details

a. Size of the calble : 4 sq.mm

b
b. Material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistance R2lead : 2*L*Rcable/1000

: 2*100*5.52/1000

: 1.1040 Ohm/km

f. Max current to be carried by the lead : 100/63.51

: 1.6 A

g. Two way lead burden : 1.6*1.6*1.104

: 2.83 VA

Page 9 of 16
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION - Doc No.: PH10-XX-XX-XX-XXXX Rev. A
PROJECT
PHASE X - SUBSTATIONS PRPD CHKD APPD DATE
VT Sizing calculation for BC-2 S/S - 132/11 kV Interbus Transformer - 11
TITLE MM SMS AKS 10/11/2011
KV Side VT
1.4 Connected Burden Particulars - Core 1

Synchro check relay (P143) : 0.02 VA (Refer ANNEXURE - R5)

BCU (C264) : 0.10 VA (Refer ANNEXURE - R4)

P141 : 0.02 VA (Refer ANNEXURE - R3)


Lead Burden : 2.83 VA

Total Burden : 2.97 VA

With 20% Design margin : 3.6 VA

Rated VA Burden of the VT : 100 VA

The rated burden of the VT provided is more than the actual requirement. Hence the selected rated burden of the VT core is
adequate.

1.5 Summary

SL.No Core Ratio Burden Accuracy

1 Core-1 11 KV/√3 / 110 V/√3 100 VA CL.1.0 / 3P

Page 10 of 16
VT Sizing Calculation for
11kV Bus Section

Page 11 of 16
Larsen & Toubro Limited,
ECC Division - EDRC

Summary of Voltage Transformer Parameter for 11 KV Bus - BC-2 S/S (Adopted Parameters)

Project :GTC - 371A -2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Rev: A
Class of
Burden Provided
Sl No Description Core Nos. Ratio proposed Function accuracy as per Remarks
((VA))
60044 1
IEC 60044-1

B 11kV Bus VT

1 Bus VT Core-1 11 KV/√3 / 110 V/√3 Protection & Metering CL 1.0 / 3P 100

Page 12 of 16
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION - Doc No.: PH10-XX-XX-XX-XXXX Rev. A
PROJECT
PHASE X - SUBSTATIONS PRPD CHKD APPD DATE

TITLE VT Sizing calculation for BC-2 S/S - 11 kV Bus VT MM SMS AKS 10/11/2011

A. VT Sizing Calculation for 11kV Bus VT : A166 & A266

Core Details Device Connected & Purpose


Core-1 : A166 & A266 Metering (BCU)
1.1 Basic System Data

a. Nominal system voltage V : 11 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA (Short Circuit Rating of 11kV bus)

1.2 VT Details

a. VT : A166 & A266

b. Voltage Rating : 11 KV/3 / 110 V/3

c. VA Rating : 100 VA

d. Class : CL.1.0 / 3P

1.3 VT Secondary Cable details

a. Size of the calble : 4 sq.mm

b. Material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d
d. Oneway length of the lead L : 100 m

e. Two-way lead resistance R2lead : 2*L*Rcable/1000

: 2*100*5.52/1000

: 1.1040 Ohm/km

f. Max current to be carried by the lead : 100/63.51

: 1.6 A

g. Two way lead burden : 1.6*1.6*1.104

: 2.83 VA

1.4 Connected Burden Particulars - Core 1

Synchro check relay (P143) - 11 KV Incomer (A18) : 0.02 VA (Refer ANNEXURE - R5)

Synchro check relay (P143) - 11 KV Bus Section (A12) : 0.02 VA (Refer ANNEXURE - R5)

BCU (C264) - 11 KV Incomer (A18) : 0.10 VA (Refer ANNEXURE - R5)

BCU (C264) - 11 KV Bus Section (A12) : 0.10 VA (Refer ANNEXURE - R5)

Voltage Relay (P923) : 0.25 VA (Refer ANNEXURE - R6)

Lead Burden : 2.83 VA

Total Burden : 3.32 VA

With 20% Design margin : 4.0 VA

Rated VA Burden of the VT : 100 VA

The rated burden of the VT provided is more than the actual requirement. Hence the selected rated burden of the VT core is adequate.

1.5 Summary

SL.No Core Ratio Burden Accuracy

1 Core-1 11 KV/√3 / 110 V/√3 100 VA CL.1.0 / 3P

Page 13 of 16
VT Sizing Calculation for
Station Transformer

Page 14 of 16
Larsen & Toubro Limited,
ECC Division - EDRC

Summary of Voltage Transformer Parameter for 11/0.415 KV Aux. Trans. Feeder - BC-2 S/S (Adopted Parameters)

Project :GTC - 371A - 2010 - QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE X - SUBSTATIONS Rev: A
Class of
Burden Provided
Sl No Description Core Nos. Ratio proposed Function accuracy as per Remarks
(VA)
60044-1
IEC 60044 1

C 11kV Outgoing Feeder VT

1 Outgoing Feeder VT Core-1 11 KV/√3 / 110 V/√3 Protection & Metering CL 1.0 / 3P 50

Page 15 of 16
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

GTC/371A/2010 QATAR POWER TRANSMISSION SYSTEM EXPANSION - Doc No.: PH10-XX-XX-XX-XXXX Rev. A
PROJECT
PHASE X - SUBSTATIONS PRPD CHKD APPD DATE

TITLE VT Sizing calculation for BC-2 S/S - 11/0.415 kV Aux. Trans. Feeder VT MM SMS AKS 10/11/2011

A. VT Sizing Calculation for 11/0.415 kV Aux. transfomer Feeder VT : A106 & A206

Core Details Device Connected & Purpose


Core-1 : A106 & A206 Metering (BCU)
1.1 Basic System Data

a. Nominal system voltage V : 11 kV

b. System frequency fn : 50 Hz

c. Maximum fault current If : 40 kA (Short Circuit Rating of 11kV bus)

1.2 VT Details

a. VT : A106 & A206

b. Voltage Rating : 11 KV/3 / 110 V/3

c. VA Rating : 50 VA

d. Class : CL.1.0 / 3P

1.3 VT Secondary Cable details

a. Size of the calble : 4 sq.mm

b. Material of the cable : Copper

c. Unit resistance of the cable Rcable : 5.52 Ohm/km (Refer ANNEXURE - C1)

d. Oneway length of the lead L : 100 m

e. Two-way lead resistance R2lead : 2*L*Rcable/1000

: 2*100*5.52/1000

: 1.1040 Ohm/km

f. Max current to be carried by the lead : 50/63.51

: 0.8 A

g. Two way lead burden : 0.8*0.8*1.104

: 0.71 VA

1.4 Connected Burden Particulars - Core 1

BCU (C264) : 0.10 VA (Refer ANNEXURE - R4)

Lead Burden : 0.71 VA

Total Burden : 0.81 VA

With 20% Design margin : 1.0 VA

Rated VA Burden of the VT : 50 VA

The rated burden of the VT provided is more than the actual requirement. Hence the selected rated burden of the VT core is
adequate.

1.5 Summary

SL.No Core Ratio Burden Accuracy

1 Core-1 11 KV/√3 / 110 V/√3 50 VA CL.1.0 / 3P

Page 16 of 16