Вы находитесь на странице: 1из 2

Tech Tips

Telecommunications
and the Single Point Ground
by Jeff Jowett
Megger

F
or effective grounding of a telecommunications facility, the most essential Absorbers of overvoltages are ele-
element is the master ground bar (MGB). This is the means by which the ments such as the central office
grounding electrode or ground field
site becomes protected as a single point ground.1 The utilization of a single and the metallic water pipe system. The
point ground is recommended practice in order to eliminate voltage gradients nonisolated zone is the connection point
around the electrical system. During electrical disturbances, sensitive equipment for equipment with exposed metal
surfaces that could become energized.
that has been randomly connected at various physically convenient points around This includes the frames of equipment
the grounding system can experience damaging current flow through signal and racks, MDF, power room frames
cables as potential differences develop. This problem is minimized or eliminated not grounded with green cables, bat-
tery racks, and the bus for battery
by terminating all grounding elements at a common point. return (positive). Connections are
The MGB provides this function and can be augmented by auxiliary ground made in this zone to prevent voltage
bars at convenient locations provided they are connected at sufficiently low imped- gradients between all cabinets outside
ance to the MGB. The MGB is a copper bar at least 18 by 3 inches and ¼ inch the isolated ground zone.
thick. Typically, it is wall-mounted directly above the grounding conductor (the Finally, the isolated zone is the
conductor to the grounding electrode) in the central office. The bar is mounted point of connection of a separate
on a bracket by means of an insulator. Terminations are attached by exothermic grounding bar, the ground window
welds or compression clamps. bar (GWB). This is an isolated cop-
The grounding system must be implemented with the goal of eliminating ex- per bar similar to and installed like
traneous current flow that might go unnoticed in another facility but is injurious the MGB. Equipment in the isolated
to sensitive telecomm switching. Accordingly, the sequence of connections to zone is not connected to other grounds
the MGB is critical and must be carefully observed. From left to right across the but bears a unique connection to the
grounding bar, the sequence is generators of overvoltages, absorbers, nonisolated GWB. Typically, this zone has the
zone, and isolated zone. least voltage variation. This allows all
Generators of overvoltages are conductive metallic paths offering minimal im- the equipment to float to a potential
pedance for atmospheric discharges or transients. These include components such equal to the GWB, because the GWB
as radio and microwave towers and cable shields. Connection within this zone is a single point ground. With sensi-
is a necessary step in eliminating radio frequency noise. Auxiliary ground bars tive electronics operating at the same
such as those for the main distribution frame (MDF) and entrance cables are potential, there are no overcurrents.
connected in this section of the MGB. Various auxiliary bars can be established All equipment must be isolated from
to protect discrete groups of equipment. So long as they in turn are connected floor, walls, and ceiling, taking care to
only to the MGB, the single point concept is maintained. Also connected are include bolts that hold items to the
the generator ground frame, emergency generator chassis, telephone protector floor. The GWB in turn is connected
terminals, and window entrance of wave guides. Multicoupler receptors must
each have their own connection.

www.netaworld.org Winter 2008-2009 NETA WORLD 43


to the MGB by a 2/0 AWG or larger connector, following An additional word on lightning protection is in order.
the shortest route. Also, two conductors in parallel may be Antennae on towers must be grounded. The National Elec-
used. trical Code® (NEC®) calls for two down conductors. The
The isolated zone includes equipment such as multi- tower structure can serve as one of these. If ungrounded,
plexors, inverters, digital switches, fiber optic transmission an antenna can develop an arc between the central conduc-
equipment, digital telephone equipment, and cable racks. tor and shield of coaxial cable. The propagation difference
Inverters, used to convert dc to ac power, must be physi- creates destructive high frequency noise that will circulate
cally located within this zone and connected to ground. toward equipment. If the antenna is mounted on a build-
Equipment such as teletypes, printers, modems and video ing, a #2 AWG conductor can be extended down to the
terminals, requiring ac current but connected to equipment grounding electrode, and building steel can serve as a parallel
within the isolated zone, must operate from receptacles fed connection.
by inverters. The MGB and MDF bar are not to be physi- Prevailing standards are in effect for the required re-
cally located in the isolated zone. sistances of the key elements in such a system. The buried
Separate requirements exist for equipment in the non- electrode, whether it be ring ground, grid, or several such
isolated zone. All cabinets are isolated from all grounds structures connected in parallel, should be no more than five
except the connection to the designated section of the MGB. ohms. However, the telecommunications industry prefers a
The main distribution frame is grounded to the generators one ohm ground. The resistance of the grounding conductor
of overvoltage section (left side) of the MGB. Entrance from the MGB to the central office grounding electrode
cables are connected to their own auxiliary copper bar, cable should be less than 0.005 ohm, as should the conductor to
entrance ground bar (CEGB), again similar to the MGB. the ac power ground, which is typically 2/0 AWG or greater.
The shields are grounded to this bar so that the individual The connection between the GWB and the MGB must also
grounding conductor for the shield is as short and direct as be no more than 0.005 ohm.
possible. The CEGB also connects to the generator section Careless ground connections made principally on the
of the MGB. basis of physical proximity can establish voltage gradients
The single point ground is only as effective as its termi- that damage sensitive telecommunications equipment.
nation in the earth. Careful attention must be paid to the Studious attention to the specific requirements of the single
grounding electrode, the point of final contact with earth. point concept will eliminate this problem.
Towers and buildings will have an exterior ground ring
buried around the structure, interconnected, and supple-
mented by ground rods. The MGB is connected to this Grounding for Electrical Distribution Systems, ALLTEC®
1

system, and also may connect to the ac power ground or Corp., Cohasset, MA
to building steel.
Additionally, an interior ring, called a halo, may be ex-
tended within the building, elevated or around the walls Jeffrey R. Jowett is Senior Applications Engineer for Megger in Valley
(15 cm below interior ceiling is recommended). This Forge, Pennsylvania, serving the manufacturing lines of Biddle®, Meg-
provides an equipotential ground plane protecting against ger®, and Multi-Amp® for electrical test and measurement instrumenta-
tion. He holds a BS in Biology and Chemistry from Ursinus College.
electromagnetic pulses of high frequencies. It connects He was employed for 22 years with James G. Biddle Co. which became
noncritical metallic parts and inactive elements like the Biddle Instruments and is now Megger.
frames of metallic doors and HVAC ductwork. Properly
connected to the exterior ground ring at the four corners
of the structure, the halo functions as a faraday shield.
Only inactive metallic parts should be connected to the
halo. Electrical equipment should never be connected to
the halo. Such practice interferes with the goal of diverting
currents developed by electromagnetic voltages through the
shortest path to earth. Offering an alternate path around
the halo can lead to potential differences between cabinets
and promote equipment damage. Accordingly, equipment
is grounded directly to the MGB, and the halo is not par-
alleled between the MGB and the exterior ground. If the
halo were connected to both the building ground and the
MGB, a parallel condition would exist and the single point
concept would be violated If the halo is connected to the
MGB without parallel connection to the exterior ground,
the single point ground is maintained.

44 NETA WORLD Winter 2008-2009 www.netaworld.org

Вам также может понравиться