DSE5310
DIAGRAM.
ELECTRICAL INTERLOCK

LOAD

DSE5320 ONLY

CTs MUST BE 5 AMP


SECONDARY

P1 P2
L1 L1
S1 S2

FROM
GENERATOR FROM
MAINS

N N

2 AMP 2 AMP
FUSES FUSES

ELECTRICAL INTERLOCK

G M

39 40 41 42 35 36 37 38 29 30 27 28 31 32 33 34 16 17 18

CT1 CT2 CT3 COM L1 L2 L3 N L1 L2 L3 N

GEN CURRENT GEN VOLTS GENERATOR MAINS LOADING BUS VOLTS


LOADING RELAY RELAY

P810
MODULE 5310/5320
SENDER COMMON
CRANK
FUEL

157
BATTERY OUTPUTS CANBUS
CHG ALT

PLANT +VE
WATER

IMPUTS
FUEL

COM

L
-VE

+VE

OIL

1 2 3 4 5 9 44 45 46 47 10 11 12 13 14 15 6 7 8 20 21 22
USER CONFIGURABLE +VE INPUT

USER CONFIGURABLE +VE INPUT

USER CONFIGURABLE +VE INPUT


EMERGENCY STOP

LOW OIL PRESSURE

HIGH COOLANT TEMP

FUEL LEVEL SERVER

USER CONFIGURABLE -VE INPUT 5


USER CONFIGURABLE -VE INPUT 1

USER CONFIGURABLE -VE INPUT 6


MIN 2 AMP MAX 20 AMP
ANIT-SURGE FUSE

UPTO 32 AMPS
FUSE

USER CONFIGURABLE -VE INPUT 2

USER CONFIGURABLE -VE INPUT 3

NOTE 1
USER CONFIGURABLE -VE INPUT 4

WL
BATTERY

CHARGE
FUEL ALT

CRANK

BATTERY NEGATIVE MUST BE GROUNDED


NOTE 2. 120 R TERMINATING RESISTOR
MAY BE REQUIRED EXTERNALLY SEE ENGINE
TERMINALS SUITABLE FOR 22-16 AWG (0.6mm - 1.3mm ) MANUFACTURERS LITERATURE
FIELD WIRING

TIGHTENING TORQUE = 0.8Nm (7lb-in)

NOTE 1

THESE GROUND CONNECTIONS MUST BE ON THE


ENGINE BLOCK, AND MUST BE TO THE SENDER BODIES.
THE GROUND WIRE TO TERMINAL 47 MUST NOT BE
USED TO PROVIDE A GROUND CONNECTION TO ANY
OTHER DEVICE