ChilcaUno Power Station Add-on Project / Water Treatment System

1.14 PLC Panel


VENDOR PRINT FOR TOTAL 311 PAGE
PLC PANEL (Including Cover)

Purpose

□ For Information
● PROJECT CODE : A90207EA
□ For Review
● PROJECT NAME : CHILCAUNO POWER STATION ADD-ON PROJECT

● DOCUMENT No. : 0-WD910-EJ460-00002 □ For Approval

● TITLE : VENDOR PRINT FOR PLC PANEL □ For Construction

● OWNER : EnerSur S.A. □ For ( )

FOR FINAL

2 Apr.19.2012 K.N.Kim S.H.Choi G.M.Choi FOR FINAL J.W. Gwon J.H.Yoon

1 Nov.30.2011 K.N.Kim S.H.Choi G.M.Choi FOR CONSTRUCTION J.W. Gwon J.H.Yoon

0 Aug.24.2011 K.N.Kim S.H.Choi G.M.Choi FOR CONSTRUCTION J.W. Gwon J.H.Yoon

PREP REVIEW APPR REVIEW APPR


Rev.
DATE DESCRIPTION
No.
DEC POSCO E&C
Owner

EnerSur S.A.
Contractor Subcontractor
Page
TECHNICAL SPECIFICATION

CONTENTS

1.0 GENERAL
1.1 General Information
1.2 Language and Units
1.3 Design, Standardization and Interchangeability
1.4 Site Condition

2.0 SCOPE OF SUPPLY


2.1 General
2.2 Scope of supply
2.3 Vendor Responsibility

3.0 CODES AND STANDARDS

4.0 DESIGN REQUIREMENT


4.1 General Requirement
4.2 Hardware Requirement

5.0 DESIGN REQUIREMENT FOR PLC


5.1 General
5.2 System Software

6.0 TEST AND INSPECTION


6.1 Shop Test
6.2 Acceptance Test
Page
TECHNICAL SPECIFICATION

7.0 IDENTIFICATION, PAINTING AND HANDLING


7.1 Painting and Cleaning
7.2 Nameplates and Tagging
7.3 Packing, Shipping and Storage

8.0 QUALITY ASSURANCE PROGRAM

9.0 PERFORMANCE GUARANTEE

10.0 INFORMATION TO BE SUBMITTED


10.1 With Bid
10.2 After Award
10.3 Drawings and Documents Requirements

11.0 ATTACHMENTS
11.1 I/O Summary List
11.2 System Configuration Diagram
11.3 Control Room Layout
11.4 Solenoid Panel Drawing
11.5 Equip Ment For Hmi System
Page
TECHNICAL SPECIFICATION

1.0 GENERAL

1.1 General Information

1.1.1 Introduction

This specification covers the requirements for design, programming,


engineering analysis, warranty, debugging, documentation, manufacturing,
assembly, testing, inspections, delivery and technical direction of installation,
start-up service and training for the PLC System.

It is not the intent of this specification to specify all details of design for
construction. However, it shall be the responsibility of Vendor to supply all
equipment that are in accordance with standards of engineering, design and
workmanship, suitable for the intended service as described herein, and
consistent with generally accepted standards and practices in the power
station service plant.

The Vendor will note that this is, in part, a functional specification.
Equipment configurations and other detailed hardware descriptions are
provided as a guide to the intent.

1.1.2 Definitions

Owner : ENERSUR S.A.


Vendor : The person or persons, firm or company whose tender has been
accepted by the Contractor/Engineer and includes the Contractor's
duly appointed representatives, successors and permitted assigns.

1.2 Language and Units

1.2.1 Language

All commercial and contractual matters shall be communicated in English or


Korean. All drawings showing layouts, arrangements, as well as overall
drawings of equipment shall be lettered in English and Korean.

1.2.2 Units
Page
TECHNICAL SPECIFICATION

The metric system shall be used for this project.


Only nominal diameters of piping may be given in inches. The following
units shall apply;
A. Length : m ; ㎜
B. Time : s ; h
C. Temperature : ℃
D. Weight ; mass : ㎏ ; t
E. Pressure : ㎏/㎠ ; abs
F. Thermal Energy : Kcal ; Gcal
G. Electric Power : KW ; MW
H. Voltage : V ; KV
I. Current : A ; mA
Additional units can be formed by combining the above units and/or adding
metric prefixes.

1.3 Design, Standardization and Interchangeability

All equipment is to be designed and manufactured in accordance with the


latest acceptable degree of workmanship and modern engineering practice.
Unless otherwise specified, all equipment must be suitable in every respect for
continuous operation under the climatic and operation conditions peculiar to
the erection site.

The equipment shall be designed to facilitate inspection, cleaning,


maintenance and repair. The design shall incorporate every reasonable
precaution and provision for the safety of all those concerned in the operation
and maintenance of the equipment.

The equipment shall be designed, manufactured and arranged in such a way


that is functional and pleasant in appearance. It is expected that all parts of
the equipment shall be adequately and generously dimensioned and shall
process a reserve of a least 10% in relation to its normal capacity.

For the equipment only those designs which have been tested in at least
two(2) years of continuous operation shall be offered. Innovations or proto
type cannot be accepted.

Equipment subject to wear shall be easily accessible and removable. Whenever


Page
TECHNICAL SPECIFICATION

possible, adjustment shall be provided for taking up wear. If during the first
twelve months of operation, moving parts show excessive wear, they shall be
replaced free of charge. Corresponding parts shall be interchangeable
whenever possible.

All equipment performing similar duties shall be of the same type and
manufacture, in order to limit the stock of spare parts and/or maintain
uniformity of equipment to be installed. Owner reserves the right to ask for
coordination of standardization to the extent reasonable possible and no price
variation will be allowed for this procedure.

1.4 Site Condition

A. Air temperature : Max. 28.2 ℃(Design 32℃)


Mmin. -3.3 ℃(Design -15.6℃)
Avg. 12.9 ℃
B. Relative humidity : Max. 79.4 %
Min. 50.4 %
Avg. 63.4 %
C. Barometric pressure : 760 ㎜Hg
D. Wind : Max. 3.6m/s(Design 40m/s)
Page
TECHNICAL SPECIFICATION

2.0 SCOPE OF SUPPLY

2.1 General

The Vendor shall provide all necessary and supplementary equipment in his
proposal to complete his system and equipment and to make them work
fully and properly according to, but not necessarily limited to, the
following section unless otherwise specified in this specification.

PLC system shall be delivered as a system base in which the system includes,
but not necessarily limited to, the follows ;

- Complete engineering and documentation of the delivery


- Mounting with materials
- Supervision of Installation at site
- System start-up and commissioning

The delivery shall include all devices and performances mentioned in this
technical specification and all accessories and performances which are
necessary for complete function of the control and monitoring system, even
though not mentioned in this specification.

2.2 Scope of Supply

The Vendor shall provide major equipment as listed belows for Water
Treatment System and auxiliaries.

2.2.1 Programmable Logic Controller

1) PLC Processor : 2 Set


- CPU Module : 32Bit Single Processor
- Battery Form : Lithium
- Total I/O Points : Min 3,000 point
- Execution Time : 0.1ms/min

2) Data Interface : 2 Set


- PROFIBUS 100Mbps
Page
TECHNICAL SPECIFICATION

3) Communication module : 1 Set


- Profibus

4) I/O module As Required

a) Analog Input Card


- Points/Unit : 8Points/Unit
- Signal Isolation : Optical Isolation
- Input : 4-20mA, DC

b) Digital Input Card


- Points/Unit : 32Points/Unit
- Signal Isolation : Optical Isolation
- Input : Voltage or Dry Contact

c) Digital Output Card


- Points/Unit : 32Points/Unit
- Signal Isolation : Optical Isolation
- Output : Transistor or relay Output

5) Software Package : 1 Lot


6) Software program diskettes for Maintenace & Operation : 1 Set

2.2.2 Operator Station

1) Operator Station : 2Set


- CPU : Pentium4 3.16GHz/6MB
- Memory : MAX.8GB
- HDD : 500GB
- FDD : 1.44MB
- CD-ROM(RW) : 54X
- Sound Card : 16Bit
- VDU : 24 inch
- Resolution : 1,920 x 1,080
- Color : Min. 256
- Input Pointing Device : Mouse
- Keyboard : Engineering korean/English
Page
TECHNICAL SPECIFICATION

- OS : Microsoft Windows 7
- Communication processor : 10/100Mbps
- Power : AC120V, 60Hz
2) Printer(A4 Color Ink Jet/A3 Black Laserjet) 1 Set
- Speed : 16 ppm
- Resolution : 600dpi over
- Function : Fail Over
- Power : AC 120V, 60Hz

3) Desk for Operator Station & Printer 2 Set

2.2.3 Interposing Relay Panel with Terminal Panel 1 Lot

2.2.4 Spare parts for Commissioning 1 Lot

2.2.5 Consumable Material for start-up operation : 1 Lot

2.2.6 System Cable and prefabricated cable : 1 Lot

2.2.7 profibus DP Communication module, cable, connection jack for DCS


(siemens) interface : 1 Lot

2.2.8 Local Solenoid Valve Panel

Solenoid Panel-1
- Q'ty : 1 LOT
- Type : Self Standing Enclosure
- Dimension : LATER
- Material : Steel 2.3t (RAL 7032)
- Thickness : M.F.R ST

2.3 Vendor Responsibility

2.3.1 General

The Vendor shall provide a complete process instrumentation system with the
latest version in his system, fully programmed and configured to perform all
the functions listed.
Page
TECHNICAL SPECIFICATION

2.3.2 The Vendor shall provide software program and data for plant calculation
and consumption calculations, maintenance scheduling etc.

2.3.3 The Vendor implement all functions of the specification, using his standard
commercially available equipment and software packages.

2.3.4 The proposal should include detailed description of all equipment offered,
supplemented by descriptive litterature and technical performance data and
leaflets.

2.3.5 The Vendor provide software package(with Backup) but not be limited to the
followings ;

1) License program with back up


2) Software program list
3) Application program with back up
4) Simulation program with backup
5) Etc.
Page
TECHNICAL SPECIFICATION

3.0 CODES AND STANDARDS

The industry codes and standards referenced in and/or applicable to this


document are listed below. The latest revision of each referenced industry
code or standard is relevant.

3.1 American National Standards Institute (ANSI)

- ANSI C39.5 (1974) "Safety Requirements for Electrical and Electronic


Measuring and Controlling Instrumentation ".
- ANSI C37.90 (1989) "Relays and Relay Systems associated with Power
Apparatus".
- ANSI X3.9 (1989) "Programming Language FORTRAN".
- ANSI X3.113 (1987) "Information System-Programming Language Full
BASIC".

3.2 National Electrical Manufacturers Association (NEMA)

- NEMA ICS 2 (1993) "Industrial Control and Systems, Controllers, Contacts,


and Overload Relays rated not more than 2000 Volts AC
or 750 Volts DC".
- NEMA ICS 6 (1993) "Industrial Controls and Systems Enclosures".

3.3 Institute of Electrical and Electronic Engineers (IEEE)

- IEEE 472 (1989) "Surge Withstand Capability(SWC) Tests" (Same as


ANSI/IEEE C37.90.1)
- ANSI/IEEE 770 X3.160 (1990) "Programming Language Extended Pascal".

3.4 National Fire Protection Association (NFPA)

- No. 70 (1984) "National Electrical Code".


- No. 75 (1981) "protection of electronic Computer/Data Processing
Equipment".
- No. 493(1978) "Intrinsically Safe Apparatus in Devision I Hazardous
Locations".
Page
TECHNICAL SPECIFICATION

3.5 Scientific Apparatus Makers Association (SAMA)

- SAMA PMC 33.1 (1978) "Electromagnetic Susceptibility of Process Control


Instrumentation".

3.6 Insulated Power Cable Engineers Association (IPCEA)

- IPCEA S66.524 (1977) "Insulated Power Cable engineer Association


cross-linked-thermosetting-polyethylene-insulated wire and cable for
transmission and distribution of electrical energy"

3.7 Instrument Society of America (ISA)

- ISA S5.1 (1984) "Instrumentation Symbols and Identification".


- ISA S5.2 (1981) "Binary Logic Diagrams for Process Operations".
- ISA S5.3 (1982) "Graphic Symbols for Distributed Control/Shared Display
Instrumentation, Logic and Computer Systems".

- ISA S5.4 (1981) "Instrument Loop Diagram".


- ISA S5.5 (1986) "Graphic Symbols for Process Displays".
- ISA S12.12 (1984) "Electrical Equipment for use in Class I,Division
2 Hazardous(Classified) Locations".
- ISA S71.01 (1985) "Environmental Conditions for Process Measurement
and Control systems : Temperature and Humidity"
- ISA S71.04 (1985) "Environmental Conditions for Process measurement
and Control Systems : Airborne contaminants"
- ISA RP12.6 (1977) "Installation of Instrinsically Safe Instrument
Systems in Class I Hazardous Locations".
- ISA RP55.1 (1983) "Hardware Testing of Digital Process Computers".
- ISA RP60.3 (1988) "Human Engineering for Control Centers".
- ISA RP60.6 (1984) "Nameplates, Labels and Tags for Control Centers".
- ISA RP60.8 (1978) "Electrical Guide for Control Centers".

3.8 Factory Mutual System (FM)

- FM-Data Sheet 5-10/14-10 (1984) "Protective Grounding of Electrical


Power Systems and Equipment"
- FM-Data Sheet 5-32 (1978) "Electronic Computer Systems".
Page
TECHNICAL SPECIFICATION

3.9 Underwriters Laboratories (UL)

- UL 913 (1988) "Standard for Intrinsically safe Apparatus and Associated


apparatus for Use in Class I, II, and III, Division I,
Hazardous(classified) Locations".
Page
TECHNICAL SPECIFICATION

4.0 DESIGN REQUIREMENT

4.1 General Requirement

4.1.1 General

The Plant Computer System shall consist of a "state of the art" high speed
digital computer, computer software, and peripheral computer hardware.

4.1.2 The System shall be capable of

1) High speed calculation


2) Bulk Storage of Data
3) Operator, System Operator interface.

4.1.3 Operator Interface

Operator interfaces shall have one (1) visual display unit (VDU) which have
a operator keyboard and mouse.

4.1.4 Engineer Interface

Engineer interface shall be provided for system configuration, graphic


development, log generation and report generation, diagram building.

4.1.5 Power System

AC120V 60Hz UPS system shall be provided for the safe and independant
operation of all Vendor's plant computer system.

4.1.6 System Grounding

1) The Vendor shall provide an installation layout of the grounding plan for
the proposed system

2) The Vendor shall consult the relevant electrical codes for specifics on
the grounding requirements and adhere to local installation codes and
regulations.
Page
TECHNICAL SPECIFICATION

3) The system may be geographically located throughout the plant area, it


is important that the system shall be designed to eliminate ground loops,
electrical noise, and other grounding-related problems.

The following are some recommendations regarding the design of the


power and packaging system :

a) The power system must have a provision for an equipment safety


ground conductor to be connected at the power entry point. The
cabinet structure is connected to this ground point through the power
system within the cabinet.

b) If a power subsystem in one cabinet also provides power to


components in other cabinets, there must be a mechanism for
connecting the structures of the latter cabinets to the safety ground
point in the former cabinet.

c) Within each cabinet, a separate grounding system (system common)


must be provided to allow the common terminals of the DC power
supplies, the shields of the process I/O signal wiring, and the signal
grounding points to be tied together at a common ground bus. It
must be possible to connect this bus to site ground through a single
conductor that is separated from the safety ground connection. In the
case of multiple cabinets powered by a single electrical supply, there
must be a means to interconnect the common bus in each of the
cabinets and in such a manner so as to maintain single point ground
integrity.

4.1.7 Local Solenoid Panel

1) Control panel shall be of free standing type with hinged access door.
The panel shall be fabricated from 2.3mm steel

2) All panel mounted instrument and other devices shall have their
identification stenciled or permanently marked on the panel structure.

3) 4-way Solenoid valve shall be the continuous duty type equipped with a
minimum of class H encapsulated coils. The power shall be DC24V.
Page
TECHNICAL SPECIFICATION

4.2 Hardware Requirement

4.2.1 PLC Processor shall have a single CPU with back-up program (on EPROM
or disk) which shall be expandable for more generating sets.

4.2.2 The computer shall be a real time multitasking digital computer with a
minimum 32 bit length and capable of preforming a minimum of 25 MIPS.

4.2.3 The system shall be equipped with a memory system of adequate capacity
and suitability for short term and long term storage of data.
The Vendor shall be solely responsible for sizing of memory to perform all
functions within performance standards as stated in this specification.

4.2.4 Power failure protection and automatic restart after power restoration shall
be provided.

4.2.5 The Vendor shall specify the main memory to meet the following guidelines ;

1) Minimum of 32 megabyte of 32 bit high speed memory


2) Capacity for expansion up
3) Scan Time 2m/3ms per K instruction

4.2.6 Printer

The Ink Jet printer shall be provided for alarm reports, logs, and system
diagnostics printing in English and Korean Language.

4.2.7 Visual display unit, keyboard and mouse

VDU shall have the following capacity :

1) a minimum of 256 color


2) a minimum 1920 x 1080 Pixel screen resolution

4.2.8 Communications Requirements

1) The communication system shall be based on a industrial grade digital


communication link, utilizing a coaxial cable, twisted pair conductors or
Page
TECHNICAL SPECIFICATION

fiber optics, to provide a high speed data transfer between PLC I/O
modules, control modules, operating stations and the Plant Computer
System.

2) The Vendor shall specify with his proposal the maximum number of
devices the communications system can support without affecting the
total system scan time and performance or requiring and additional
highway memory expansion capability.

3) The Vendor shall specify with his proposal the geographical distance
limitations between main devices and sub-devices.

4) The Vendor shall provide with his proposal a full description of the
standard communication system, including the network topology (star,
ring, multi drop), I/O speed and scan cycle time, the communication
protocol, structure, security checking, and access method (broadcast,
baton passing, polling, etc.).

4.2.9 Functional Requirements

The system shall include all necessary hardware and software so as to be


capable of the following functions.

All operator interface information shall be displaied or printed in English and


Korean Language.

1) Process value recording and reading incomming analog-digital signal and


logic signal.
2) Showing on the VDU the reading tabulated as programmed and showing
another set of readings if asked through keyboard.
3) Showing another set of reading if asked through keyboard.
4) Checking for correctness the instruction given through keyboard and
acknowledging accordingly.
5) Printing according to the instruction given through the keyboard at
regular interval or on demand as follows ;

- The reading every hour


- The reading every 24 hour together with the average or total, as
Page
TECHNICAL SPECIFICATION

applicable, for the previous 24 hour period or privious 30 days period.


- Any current reading or set of readings at any time, on demand.
Also on demand and for specific time of day or for specific generating
set load a set of readings or average value or totals for the period of
the preceeding 30 days or another interval within this period of 30
days.

6) Checking continuously its operation and the associated equipment's


location and fault in the system.

7) Saving the data readings at every regular interval in disk for further data
processing by means of the P.C.

8) Operating as a complete alarm system ;

- Reading all incomming signal


- Comparing readings to preprogrammed alarm settings and event that
the limit are exceeded. (the alarm settings can be easily changed by
means a subroutine of the main program)
- Printer shall show the alarm informations, the variable description, the
preset limit, the current reading, the time and date, the unit load etc.
- VDU shall also show above data in red.
- Audible alarm equipment shall also energized.

9) Graphic software for creating custom display and additional storage


media for archiving data shall be provided.

- Reading all incomming signal


Page
TECHNICAL SPECIFICATION

5.0 DESIGN REQUIREMENT FOR PLC

5.1 General

5.1.1 The Main Processor shall be programmable logic controller of


microprocessorbased system that will accommodate discrete I/O and a
wide range of analog I/O from field devices located throughout the plant.

5.1.2 The system shall be capable of storing instructions to implement control


functions such as sequencing, timing, counting, arithmetics, data
manipulation and communication to control industrial machines and
processes.

5.1.3 The system shall utilize a modular architecture to permit a wide range of
system configuration and facilitate system flexibility and expansibility along
with future plant growth.

5.1.4 The system shall monitor all possible failure of its components. The
diagnostic tests shall be executed at system startup, during operation and
on a periodic basis. Once a failure detected, a descriptive alarm is
generated on display unit and printer.

5.1.5 The system shall have communication channel which permit transferring
data between PLC and Plant computer system(DCS).

5.1.6 The operation software of the PLC shall be governed by the operating
system running in a real time and event motivated mode.

5.1.7 The operating system shall permit expansion of I/O data files without
requiring program revisions, reorganization, regeneration, or reassembly up
to the limits defined at the time of system generation.

5.1.8 The Vendor shall provide an operating system which consists of :

1) Process interface cabinets with I/O cards and power supply system.
2) System Peripherals such as programmer's station, remote operator
station, printer, etc.
3) All operation software.
Page
TECHNICAL SPECIFICATION

5.2 System Software

5.2.1 General

1) The Vendor shall list and describe in the proposal all of the available
software packages and their application of the system.

2) The programming language shall offer ease of use and implementation.


It shall permit the user to configure the system interactively via keyboard
or mouse and VDU. The configuration software shall be run in the
Vendor provided programming device.

3) The programming language shall use the logic symbol language which
incorporates symbolic instructions, such as pushbuttons, limit switches,
normally open/closed contacts, output coils, etc., to create control
diagrams. It shall also include a basic instruction set and function
blocks which can perform the following essential functions :

a) Basic relay instructions for coil and NO/NC contacts.


b) Timer and counter instructions.
c) Program flow instructions, functions are used for directing the flows of
operations and executions of instructions within the ladder diagram
such as Go To, Go Subroutine, Label, Return, End, etc..
d) Arithmetic instructions, function blocks are used to perform calculations
of internal registers such as Addition, Subtraction, Multiplication, and
Division.
e) Data manipulation instructions, function blocks are used to manipulate
the content of registers such as Comparison, Complement, Inversion,
etc..
Page
TECHNICAL SPECIFICATION

6.0 TEST AND INSPECTION

6.1 Shop Test

Shop test shall be performed in accordance with the relevant approved


standard and, in addition, any test required by owner to ensure that the
equipment provided fulfills the requirement of the specification. Shop test
including, but not limited to, those in the following, shall be performed.

(1) Calibration test on all important instruments.


(2) System program test.
(3) Diagnostic test.
(4) Simulation test.

6.2 Acceptance test

6.2.1 All equipments shall be checked before and after test to ensure that they
give accurate indication and calibrations have not altered during test.

6.2.2 The automatic and manual controls of the equipment provided under this
contract shall be checked to ensure that they operate satisfactorily
throughout the load change.

6.2.3 The Supplier shall state in his proposal the availability demonstration test of
his equipment to be performed on the field.
Page
TECHNICAL SPECIFICATION

7.0 IDENTIFICATION, PAINTING AND HANDLING

7.1 Painting and Cleaning

All metal surface shall be free of sharp edges, burrs and weld splatter by
grinding sandblasting, or abrasive cloth.

Preparatory to painting, all scratches, dents and other imperfections shall be


filled with putty and sanded smooth.

All surfaces shall be cleaned to remove all oil, dirt, and grease, and then
be given a rust-resistant primary coat.

Two or more finish coats of paints shall be applied to exterior surfaces for
dry film thickness not less than 3.5 mil.

7.2 Nameplates and Tagging

All instruments shall be supplied with permanently affixed stainless steel tag
engraved with the complete instrument item identifying tag number. The
nameplate shall include the following information as a minimum ;

1) Manufacturer's name
2) Manufacturer's serial number
3) Input and output signal data

Other tagging detail and nameplate size will be informed by Owner later.

7.3 Packing, Shipping and Storage

The instrument shall be cleaned, prior to packing for shipment, to remove


all accumulated dust and manufacturing debris.

When the instrument is disassembled, all interconnecting cable connectors


shall be protected and identified properly.

Cables shall be packaged individually and identified clearly on the outside of


the package.
The instrument shall be crated to allow movement by forklift, rollers, crane
slings and/or skidding.
Page
TECHNICAL SPECIFICATION

The packing and boxing procedures shall be designed to provide proper


instrument protection, with consideration given for site environments :
conditions, at the time of the year the shipment is made.

All cartes shall be clearly marked with purchase order number and item
numbers.

The boxed shall be marked to indicate the balance point. The weight of
each box shall be marked on at lease two sides in painted numberals at
least three inches in height.

Final shipping instructions will be delivered to the Vendor as required prior


to shipment.

Prior to delivery Vendor shall identify to Owner in writing all special storage
and preventive maintenance requirement to be applied after receipt of
equipment at the construction site.
Page
TECHNICAL SPECIFICATION

8.0 QUALITY ASSURANCE PROGRAM

The Vendor shall work to define Quality Assurance Programmes Compliant


with ISO9001 or equivalent.

The Vendor shall list the quality level proposal for his scope of supply.

The Vendor shall submit for approval, within 30 days of the contract award,
a quality plan(inspection and test plan) defining the program of quality
control and inspection activities which he will perform in order to ensure that
the manufacture and completion of the plant complies with the specified
requirements.

And also Vendor shall consider that all materials and equipment be subject to
inspection by the engineer as determined by the Quality Plan.

The Vendor shall extend applicable requirements of this purchase documents,


including the quality assurance program requirements, to sub-vendor ( If
applicable)

The Vendor shall make objective evidence of conformance readily avaliable to


ENERSUR S.A. and ENERSUR S.A.'s customer.

ENERSUR S.A. requires the right of access for ENERSUR S.A. representatives
and ENERSUR S.A.'s customer representatives to the Vendor's and
sub-Vendor's shop.

ENERSUR S.A. source verification activitied do not relieve the vendor of the
vendor's responsibility of verification of quality achievement.

9.0 PERFORMANCE GUARANTEE

All instrument and component parts shall be guaranteed against fault in


design, defective or improper materials, poor workmanship and failure form
acceptance for two(2) years.
Page
TECHNICAL SPECIFICATION

10.0 INFORMATION TO BE SUBMITTED

10.1 With Bid

PLC Vendor shall submit information with the Bid in sufficient detail to permit
owner to fully understand and evaluate the equipment being offered. After
acceptance by owner, the data will become part of this specification for the
distributed control system.
PLC vendor shall provide a description of its quality control and inspection
department and that of its major subvendors. PLC vendor shall provide the
following information, data and drawing included as part of the Bid ;
- System configuration for overall
- System layout drawings
- Desk layout drawings.
- Specification & catalogue for process station CPU
- Specification & catalogue for input and output module
- Specification & catalogue for monitor and peripheral devices.
- I/O counts to be proposed.
- A list of systems of similar scope of herein specified, identifying customers,
type and size of plant, scope and status of system, along with contract
award date, delivery date, and startup date.
- Description and application of microprocessors/computers used in the
system.
- Description of hardware and software offered.
- Heat dissipated by the system in the control and electronic room.
- State the year the first vendor's application of this equipment went into
operation and the projected date of the next change in this "line" to a newer
"line".

PLC vendor shall state the type and size of electrical wiring required between
the equipments as well as the need for cable shielding. PLC vendor shall
define power requirements and tolerances with respect to voltage, frequency,
harmonic distortion, and in-rush current which his proposed system requires
from uninterrupted power supply furnished by owner to meet specified
performance.
Page
TECHNICAL SPECIFICATION

10.2 After Award


Twelve(12) sets of drawings and manual shall be submitted for approval or for
information in accordance with the timing specified.

10.2.1 Schedule for Approval


An overall schedule in sufficient detail to demonstrate ability to perform the
work within the specified time limit. The schedule shall be in the critical path
method(CPM) format. A detailed schedule showing the submittal date of each
document. A detailed schedule showing the delivery date of each piece of
equipment to job site.

10.2.2 List of drawings to be submitted for approval

1) PLC vendor shall provide the following drawing and document.


- System configuration
- System block diagram for power distribution panel

- System layout drawings


- Control, input/output module system cabinet assignments drawings
- Desk layout drawings
- Control loop connection diagram and cable schedule
- Detailed dimensional drawings of rack, desk, cabinet, etc.
- Plant colour and finish specification
- Factory and field test procedure
- Test report format and records
- Operation & maintenance manuals
- Recommended consumable and spare part
- Equipment mounting and installation requirements.

2) System engineering's drawings development.

PLC vendor shall submit his implementation logic/loop diagrams to be


prepared on the base of his PLC function, symbol & legends by converting
engineer's logic/loop diagrams. PLC vendor shall design and develop, but
not be limited to, the followings ;
- Graphic displays
- Process I/O list
Page
TECHNICAL SPECIFICATION

- Alarm set point list

Control loop connection diagrams shall be of physical type and shall show
all hardware, terminal blocks and connectors with internal and external
interconnecting wiring with sufficient detail to trace connections. The
diagrams shall show general physical arrangement of hardware with
connections drawn point-to-point including connections to terminal blocks
and connectors for external connections by owner. These diagrams will be
reviewed, but not checked in detail, and it shall be the responsibility of
vendor to make certain that all functioning and wiring is in strict agreement
with the intent of this specification and the details shown on the functional
control schematics and logic diagrams.

10.2.3 Data for Information


- Storage and handling procedure
- Recommendations on interconnection wiring
- Certified shop test reports
- Certified calibration data
- Manuals
O/M manuals shall be included system description, flow chart and functional
description for operator's education. Installation, operation and maintenance
manuals including a complete list of replacement parts. The manuals shall
include a written description of the entire system operation, with logic, and
SAMA Drawings.

11.0 ATTACHMENTS

11.1 I/O Summary List


11.2 Control System Configuration Diagram
11.3 PLC ‘Panel Drawing
11.4 Local Solenoid Panel Drawing
11.5 Equipment For Hmi System
NO. ITEM CONTENTS NO. ITEM CONTENTS
11 CABLE SIZE POWER
1 STANDARD ■ KS □ JIS □ JEC ■ IEC ■ OTHERS( AWG ) ■ 14 □ 16 □ 18
(MINIMUM CIRCUIT
2 POWERSUPPLY SIZE)AWG ULTRAVIOLET
RECEIVING ■ AC120V □ AC210V □ AC220V □ AC400V□ AC440V □ AC380V □ 14 □ 16 □ 18
CIRCUIT
VOLTAGE
□ AC100V □ AC110V □ AC120V □ OTHERS GROUNDING ■ 14 □ 16 □ 18
CONTROL
PHASE □ 3φ3W □ 3φ4W ■ 1φ2W □ OTHERS ■ 14 □ 16 □ 18 □ 20 □ 22
(MAIN)
AC/DC CIRCUIT
FREQUENCY □ 50Hz ■ 60Hz □ OTHERS □ 16 □ 18 ■ 20 □ 22 □ OTHERS( )
(PLC DI/DO)
3 DISTRIBUTIO POWER ■ AC120V □ AC208V □ AC220V □ AC380V□ AC400V □ AC440V SIGNAL □ 16 □ 18 ■ 20 ■ OTHERS(AWG20), W/SHIELD, WHITE(+)BLACK(-)
N 12 CABLE COLOR CONTROL
ULTRA VIOLET□ AC200V □ AC208V □ AC220V □ AC120V□ AC100V □ OTHERS POWER ■BLACK(P),WHITE(N) ■ RED(+) ■ BLACK(-) □ OTHERS
VOLTAGE CIRCUIT(DC)
CONTROL □ AC100V □ AC110V ■ AC120V ■ DC24V□ AC200V □ AC220V AC CIRCUIT ■BLACK(P),WHITE(N) EARTH GROUND □ BLACK ■ GREEN □ OTHERS

4 CIRCUIT MAIN ■ MOLDED-CASE CIRCUIT BREAKER □ EARTH LEAKAGE CIRCUIT BREAKER □ OTHERS INTER LOCK ■AC:BLACK(P),WHITE(N) ■DC:RED(+) ,BLACK(-)
PROTECTION SHORT 13 STRUCTURE
■ MOLDED-CASE CIRCUIT BREAKER □ EARTH LEAKAGE CIRCUIT BREAKER □ OTHERS CONTROL □ OUTDOOR ■ INDOOR ■ VERTICAL SELF-STANDING TYPE □ WALL MOUNT TYPE
CIRCUIT
OVER LOAD ■ MOLDED-CASE CIRCUIT BREAKER □ EARTH LEAKAGE CIRCUIT BREAKER □ OTHERS ■ OTHERS(FUSE) PANEL □ DUST-PROOF/WATER-TIGHT TYPE ■ DUST-PROOF/WEATHER-PROF TYPE

5 BUTTON AUTO RUN □BLACK □GREEN ■RED □OTHERS(WHITE ) LAMP TEST □BLACK □GREEN □RED ■OTHERS(YELLOW) BOX ■ SPCC 2.3t ■ SPCC 3.2t □ SUS 2t
CONTROL
COLOR INTERLOCK
STOP □BLACK ■GREEN □RED □OTHERS( ) □BLACK □GREEN □RED □OTHERS(WHITE) PANEL INSIDE PLATE ■ SPCC 2.3t □ SPCC 3.2t □ SPCC 4.5t
RESET
BUZZER STOP □BLACK □GREEN ■RED □OTHERS(YELLOW) □BLACK □GREEN □RED □OTHERS( ) DOOR □ SINGLE FRONT TYPE ■ DOUBLE FRONT TYPE

6 SIGNAL RUN/OPEN □BLACK □GREEN ■RED □OTHERS(WHITE) STOP/CLOSE □WHITE □GREEN □RED □OTHERS( ) SEA WATER SYSTEM ■ BUTTOM □ TOP □ RIGHT SIDE □ LEFT SIDE □ OTHERS
LAMP INCOMING
POWER □BLACK □GREEN □RED ■OTHERS(WHITE ) WARNING POINT □WHITE □GREEN ■RED □OTHERS(AMBER) DEMI&INDUSTRIAL WASTE SYSTEM □ BUTTOM ■ TOP □ RIGHT SIDE □ LEFT SIDE □ OTHERS

7 NAME TRANSPARENC GROUND ■ WHITE


MATERIAL■ □ OTHERS( ) LTTERS ■ GOTHIC □ OTHERS( ) INCOMING HOLE ■ OPEN □ NON
PLATES Y. ALUMINIUM COLOR □ OTHERS
LETTERS ■ BLACK ■ FRONT 14 OTHERS
CARVING INSTALLATION□ TAPE ■ BOLT □ OTHERS ( )
COLOR □ OTHERS(RED) □ BACK
8 PAINTING OUTSIDE VIEW □ MUNSELL 5Y7/1 HALF □ MUNSELL 2.5Y8/2 HALF■ OTHERS (MUNSELL RAL7032)

INSIDE VIEW □ MUNSELL 5Y7/1 HALF □ MUNSELL 2.5Y8/2 HALF■ OTHERS (MUNSELL RAL7032)

OTHERS □ STAND SALT COATING □ STAND ACID COATING □ OTHERS

9 SOLDERLESS POWER CIRCUIT ■ R-TYPE TERMINAL □ Y-TAPE TERMINAL □ OTHERS ( ) (END CAP WHITE, BLACK & WIRE MARK WITH PVC TUBE) 15 WIRE MARK WIRE MARK (LINE TURN) DIRECTION
TERMINALS
CONTROL CIRCUIT ■ R-TYPE TERMINAL □ Y-TAPE TERMINAL □ OTHERS ( ) (WIRE MARK WITH PVC TUBE) ■ □ □ OTHERS
10 WIRING KIND POWER/CT □IV □ K I V ■ AWG □ G V □ OTHERS ( )

ULTRA VIOLET □ I V □ K I V ■ AWG □ G V □ OTHERS ( )

GROUNDING □ I V □ K I V ■ AWG □ G V □ OTHERS ( )

AC-CONTROL □ I V □ K I V ■ AWG □ G V □ OTHERS ( )

DC-CONTROL □ I V □ K I V ■ AWG □ G V □ OTHERS ( )

SIGNAL □ MVVS ■ SPECIAL CABLE ■ OTHERS (AWG )

Project Name:
CHILCA UNO POWER STATION ADD-ON PROJECT

1 Apr. 19,2011 AS BUILT K.C.H K.N.K G.M.C Title : PLC PANEL(WATER TREATMENT SYSTEM)
0 Aug. 16,2011 FOR CONSTRUCTION K.C.H K.N.K G.M.C SPECIFICATION
Project No. REFERENCE No. Document No Rev.No.
REV DATE REVISION DESCRIPTION DRN CHK APP
A90207EA 0-WD910-EJ451-00001 A
INDEX

1. LEGEND

2. ABBREVIATION

3. INPUT OUTPUT SUMMARY LIST

4. INPUT OUTPUT LIST


DCS I/O LIST
PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECT

1. RULE FOR FILLING IN OF THE COLUMNS

REFERENCE DRWING
INPUT/OUTPUT SIGNAL ENGINEERING DATA FUNCTION ALARM
LOCATION
NO. TAG NO. SERVICE LOGIC/LOOP REMARK
LOOP FROM/TO P&ID
I/O SIGNAL RANGE UNIT DCS LCP OTHER SET DWG.
POWER
NOTE1 NOTE2 NOTE3 NOTE4 NOTE5 NOTE6 NOTE7 NOTE8 NOTE9 NOTE9 NOTE9 NOTE10 NOTE11 NOTE12 NOTE13

NOTE1 : SERIAL NO.


NOTE2 : TAG NO.
NOTE3 : DESCRIPTION OF SERVICE
NOTE4 : INPUT/OUTPUT OF MODULE (AI, AO, DI, DOI, DOII, DOIII, PI)
NOTE5 : KIND OR ELEMENT OF SIGNAL (4-20mA, 1-5V, RTD, T/C, PI/O, D/L, S/W(1=LOW))
NOTE6 : POWER SOURCE (INT. : INTERNAL(24V), EXT.: EXTERNAL(24V), DRY : DRY Contact, 24V , 120V AC
NOTE7 : ENGINEERING RANGE OF SIGNAL
NOTE8 : ENGINEERING UNIT OF SIGNAL (mmH2O, bar, 'C, %, m3/hr, T/hr, Nm3/hr, mmHg, mmHgV, mm/s, rpm, pH, ppb)
NOTE9 : FUNCTIONS IN THE SYSTEM (A, C, I, SOE)
NOTE10: LOCATION OF SOURCE OF SIGNAL (DCS, MarkVIe, SWGR, LOCAL, MCC, LCP, etc)
NOTE11: ALARM SET (HH/H/L/LL)
NOTE12: REFERENCE DRAWING NO. OF LOGIC/LOOP DIAGRAM
NOTE13: REFERENCE DRAWING NO. OF P&ID

2. ABBREVIATIONS

PI-DCS: PLANT DISTRIBUTED CONTROL SYSTEM (FOR BOP) A: ALARM TCP : TURBINE CONTROL PANEL (GE)
PII-DCS: PLANT DISTRIBUTED CONTROL SYSTEM (FOR HRSG) C: CONTROL ESP : EMERGENCY SHUT-DOWN PUSH BUTTON
S-DCS: S/T DISTRIBUTED CONTROL SYSTEM (GE-MarkVIe) I: INDICATION
AI: ANALOG INPUT SOE: SEQUENCE OF EVENT 120V : AC 120V UPS
AO: ANALOG OUTPUT LOCAL: LOCAL INSTRUMENT DRY : DRY CONTACT (DC24V)
DI: DISCRETE INPUT VALVE: VALVE ACTUATOR
DOI: DISCRETE OUTPUT(SOLENOID VALVE, with AC120V) MP: MARSHALLING PANEL
DOII: DISCRETE OUTPUT(SWGR, MCC, DRIVE (Dry contact)) IRP : INTERPOSING RELAY PANEL
PI: PULSE INPUT L/C: 480V LOAD CENTER
RTD: RESISTANCE TEMPERATURE DETECTOR MCC: 480V MOTOR CONTROL CENTER
T/C: THERMOCOUPLE (Type K) SWGR R-I/O : SWITCH GEAR REMOTE INPUT/OUTPUT CABINET
D/L: DATA LINK HRSG R-I/O : HRSG REMOTE INPUT/OUTPUT CABINET
S/W: SOFTWARE LOGIC BOP R-I/O : BOP SYSTEM REMOTE INPUT/OUTPUT CABINET
GPP : GENERATOR PROTECTION PANEL (GE)

DAEWOO ENGINEERING COMPANY


DCS I/O LIST
PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECT

3. KKS NUMBERING STRUCTURE DEFINITION

TOTAL PLANT
SYSTEM CODE (LEVEL 1)
SEQUENCE UNIT CODE (SERIAL NO.)
EQUIPMENT UNIT CODE (LEVEL 2)
COMPONENT CODE (SERIAL NO.)
SIGNAL CODE (LEVEL 3)
COMPONENT CODE FOR SIGNAL (SERIAL NO.)

NOTE)
1) LEVEL 0,1 AND 2 SHALL BE REFER TO PROCEDURE FOR PLANT IDENTIFICATION (KKS)
2) LEVEL 3 SHALL BE REFER TO ITEM NO. 13 (KKS CODE APPLICATION FOR LEVEL 3)
EX) 01 ENA 02 AA 201 XB 01 (MOV OPENED STATUS)

4. KKS CODE APPLICATION FOR LEVEL 3

1) SWGR/MCC FOR PUMP/FAN


(1) STATUS FEED BACK
- RUNNING / ON STATUS : nnaaannaannnXB01
- STOPPED / OFF STATUS : nnaaannaannnXB02
- RUNNING (LOW) : nnaaannaannnXB03
- REMOTE (LOCAL) : nnaaannaannnXB27
- FAULT : nnaaannaannnXB28

(2) LOCAL SWITCH BOX for MCC/SWGR ONLY


- START : nnaaannaannnXB11
- STOP : nnaaannaannnXB12
- LSB REMOTE SELECTED : nnaaannaannnXG11
(3) AUTO (DCS) COMMAND
- START / ON (or Start/Stop, On/Off) : nnaaannaaaYB01
- STOP / OFF : nnaaannaaaYB02
- START (LOW) : nnaaannaaaYB03

DAEWOO ENGINEERING COMPANY


DCS I/O LIST
PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECT

2) ON/OFF, INCHING DRIVE - SOV or MOV


(1) STATUS FEED BACK
- POSITION TRANSMITTER - MOV only : nnaaannaannnXQ01
- POSITION OPEN STATUS : nnaaannaannnXB01
- POSITION CLOSE STATUS : nnaaannaannnXB02
- REMOTE / LOCAL - MOV only : nnaaannaannnXB03
- TORQUE OPEN STATUS (MOV SHUT-OFF) : nnaaannaannnXB04
- TORQUE CLOSE STATUS(MOV SHUT-OFF) : nnaaannaannnXB05
- FAULT - MOV only : nnaaannaannnXB28
(2) AUTO (DCS) COMMAND
- OPEN COMMAND : nnaaannaannnYB01
- CLOSE COMMAND : nnaaannaannnYB02

3) MOV (MODULATING DRIVE)


(1) STATUS FEED BACK
- POSITION TRANSMITTER : nnaaannaannnXQ01
- POSITION OPEN STATUS : nnaaannaannnXB01
- POSITION CLOSE STATUS : nnaaannaannnXB02
- REMOTE / LOCAL : nnaaannaannnXB03
- FAULT : nnaaannaannnXB28
(2) AUTO (DCS) COMMAND
- ANALOG OUTPUT COMMAND : nnaaannaannnYQ01

4) PNEMATIC CONTROL VALVE


(1) STATUS FEED BACK
- POSITION TRANSMITTER : nnaaannaannnXQ01
- POSITION OPEN STATUS : nnaaannaannnXB01
- POSITION CLOSE STATUS : nnaaannaannnXB02
(2) AUTO (DCS) COMMAND
- ANALOG OUTPUT COMMAND : nnaaannaannnYQ01

5) PACKAGE CONTROL
(1) STATUS FEED BACK
- RUNNING / ON : nnaaannaannnXJ01
- STOPPED / OFF : nnaaannaannnXJ02
- LOCAL / REMOTE : nnaaannaannnXJ03
- COMMON ALARM (If any) : nnaaannaannnXJ28
- FAULT : nnaaannaannnXJ29
- CONTACT from PACKAGE SYSTEM (If any) : nnaaannaannnXJ10 ~ XJ20

DAEWOO ENGINEERING COMPANY


DCS I/O LIST
PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECT

(2) SIGNAL TRANSMITTION OF FIELD INSTRUMENT FROM LCP TO DCS


- FIELD INSTRUMENT (Contact via LCP) : nnaaannaannnXJ01 ~ 40
- CLOSE COMMAND (4~20mA via LCP) : nnaaannaannnXJ40 ~ 90
(3) SIGNAL TRANSMITTION OF FIELD INSTRUMENT DCS TO LCP
- FIELD INSTRUMENT (Contact via LCP) : nnaaannaannnYJ01 ~ 40
- CLOSE COMMAND (4~20mA via LCP) : nnaaannaannnYJ40 ~ 90
(4) GROUP AUTO (DCS) COMMAND (TO PACKAGE SYSTEM)
- START / ON : nnaaannaannnYB01
- STOP / OFF : nnaaannaannnYB02
(4) INDIVIDUAL DRIVE CONTROL FOR PACAKGE SYSTEM FROM DCS
- BASE ON LEVEL 3

6) SET POINT
THIS KKS NUMBER SHOWS THE SOFTWARE. THESE VALUE ARE ANALOG INPUT FOR ALARM OR INTERLOCK PURPOSE.
HH : HIGH-HIGH ALARMING XH03
H : HIGH ALARMING XH01
L : LOW ALARMING XH02
LL : LOW-LOW ALARMING XH04

5. NOTES

1) DETAILD DESIGN OF THE DCS I/O ASSIGNMENT AND CONTROLLER ASSIGNMENT SHALL BE PROVIDED BY DCS VENDOR.

2) MISSING DATA LIKE TAG NO, REFERENCE DRAWING FOR INPUT / OUTPUT POINT, SET POINT WILL BE FILLED ACCORDING TO DESIGN DEVELOPMENT

DAEWOO ENGINEERING COMPANY


ABBREVIATION
PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECTProject

ABBREVIATION SERVICE DESCRIPTION ABBREVIATION SERVICE DESCRIPTION ABBREVIATION SERVICE DESCRIPTION

AUX AUXILIARY D/P DIFFERENCE PRESSURE S/O SHUT-OFF

BFP BOILER FEED WATER PUMP DE DRIVE END S/V SOLENOID VALVE

BLDG BUILDING DISCH DISCHARGE SC SPECIFIC CONDUCTIVITY

BLWR BLOWER DS DE-SUPERHEATER STG STEAM TURBINE GENERATOR

BP BYPASS FWP FEED WATER PUMP STM STEAM

BRG BEARING GT GAS TURBINE TBN TURBINE

blank H HIGH TEMP. TEMPERATURE

C/V CONTROL VALVE HDR HEADER TR TRANSFORMER

CC CATION CONDUCTIVITY HP HIGH PRESSURE VIB VIBRATION

CCCW COLSED CYCLE COOLING WATER HRH HOT REHEAT STEAM VLV VALVE

CCW CLOSED COOLING WATER HRSG#1 DCS HRSG#1 DISTRIBUTED CONTROL SYSTEM WTR WATER

CCWP CLOSED COOLING WATER PUMP HRSG#2 DCS HRSG#2 DISTRIBUTED CONTROL SYSTEM EQ EQUALIZING

CLG COOLING HRSG#3 DCS HRSG#3 DISTRIBUTED CONTROL SYSTEM BFW BOILER FEED WATER

CLR COOLER LP LOW PRESSURE HTR HEATER

CMD COMMEND LS LEVEL SWITCH SWP SERVICE WATER PUMP

COM COMMON MOV MOTOR OPERATED VALVE

COMPR COMPRESSOR MP MAIN STEAM PRESSURE

COND CONDENSER NDE NON DRIVE END

CRH COLD REHEAT STEAM P-DCS PLANT(BOP) DISTRIBUTED CONTROL SYSTEM

CTRL CONTROL P/P PUMP

CW COOLING WATER PPC POWER CONTROL CENTER

D.W DEMI WATER PRESS PRESSURE

DAEWOO ENGINEERING COMPANY


PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECT DCS IN/OUT SUMMARY LIST

SIGNAL COMM. DCS


PCS
REV AREA SERVICE PCS TOTAL POINTS GRAPHIC REMARK
LOCATION PCS DOI PCS DOII DCS DOIII
AI RTD AO T/C(K) DI PI SOE (w/Others) PAGE
(SOV.T/SW) (IRP) (24V DC)

SEA
0 PCS-101 WTP (Supplied by DAEWOO ENGINEERING at SEA WTR 63 6 - 347 - 0 0 - 416 - LATER
WATER

합 계 63 6 347 0 0 416

NOTES

1. The IRP shall be installed in DCS system panels.

2. DO to MV SWGR, LV SWGR, MCC AND STG CONTROL SYSTEM ; Buffer Relay shall be applied.

3. DI from STG CONTROL SYSTEM ; Buffer Relay shall be applied. SIEMENS shall supply DC 125V loop power.

4. Total Input & Output signal quantity can be changed in detail design development.

5. Communication Points will be changed according to Vendor Prints.


6. This document is based on BOP P&ID Rev.0 and Vendor prints (HRSG, ACC, Bypass stack etc.)

modbus@dweng.co.kr
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : AI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
ALARM
SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-EM103-
SEA WATER PIT LEVEL TRANS. AI 4 ~ 20 mA INT 0~7000 mm I.C.A I.C.A I.A FILED SEA PLC LATER
00001
0-WD510-EM103-
SEA WATER PUMP A PRESS. TRANS AI 4 ~ 20 mA EXT 0~35 Bar.g I.C.A I.C.A I.A FILED SEA PLC LATER
00001
0-WD510-EM103-
SEA WATER PUMP B PRESS. TRANS AI 4 ~ 20 mA EXT 0~35 Bar.g I.C.A I.C.A I.A FILED SEA PLC LATER
00001
0-WD510-EM103-
SEA WATER PUMP C PRESS. TRANS AI 4 ~ 20 mA EXT 0~35 Bar.g I.C.A I.C.A I.A FILED SEA PLC LATER
00001
0-WD510-EM103-
SEA WATER PUMP A/B/C OUTLET FLOW(MAG.) AI 4 ~ 20 mA INT 0~150 m3/h I.Q.R I.C I FILED SEA PLC LATER
00001
0-WD510-EM103-
RETURN PUMP OUTLET FLOW(MAG.) AI 4 ~ 20 mA INT 0~150 m3/h I.Q.R I.C I FILED SEA PLC LATER
00001
0-WD510-EM103-
WASTE PIT LEVEL TRANS. AI 4 ~ 20 mA INT 0~5000 mm I.C.A I.C.A I.A FILED SEA PLC LATER
00001
0-WD510-EM103-
WASTE PIT (Cℓ₂) AI 4 ~ 20 mA INT 0~45 'C I.C I.C I FILED SEA PLC LATER
00001
0-WD510-EM103-
NEUTRALIZATION PIT LEVEL TRANS. AI 4 ~ 20 mA INT 0~5000 mm I.C.A I.C.A I.A FILED SEA PLC LATER
00001
-1000 0-WD510-EM103-
NEUTRALIZATION PIT ORP AI 4 ~ 20 mA INT
~1000
pH I.C I.C I FILED SEA PLC LATER
00001
0-WD510-EM103-
PRIMERY FILTER A (DIFF.PRESS) AI 4 ~ 20 mA EXT 0~4 Bar I.C.A I.C.A I.A FILED SEA PLC LATER
00002
0-WD510-EM103-
PRIMERY FILTER B (DIFF.PRESS) AI 4 ~ 20 mA EXT 0~4 Bar I.C.A I.C.A I.A FILED SEA PLC LATER
00002
0-WD510-EM103-
PRIMERY FILTER C (DIFF.PRESS) AI 4 ~ 20 mA EXT 0~4 Bar I.C.A I.C.A I.A FILED SEA PLC LATER
00002
0-WD510-EM103-
UF UNIT "A" OUTLET FLOW(MAG.) AI 4 ~ 20 mA INT 0~100 m3/h I.C.A I.C.A I.A FILED SEA PLC LATER
00003
0-WD510-EM103-
UF UNIT "A" INLET(WATER) PRESS. TRANS. AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C.A I.C.A I.A FILED SEA PLC LATER
00003
0-WD510-EM103-
UF UNIT "A" INLET(INST.AIR) PRESS. TRANS. AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C.A I.C.A I.A FILED SEA PLC LATER
00003
0-WD510-EM103-
UF UNIT "A" OUTLET TUR AI 4 ~ 20 mA INT 0~100 pH I.C I.C I FILED SEA PLC LATER
00003
0-WD510-EM103-
UF UNIT "A" BACK WASH PRESS. TRANS. AI 4 ~ 20 mA INT 0~35 Kg/cm2g I.C I.C I FILED SEA PLC LATER
00003
0-WD510-EM103-
UF UNIT "B" OUTLET FLOW(MAG.) AI 4 ~ 20 mA INT 0~100 m3/h I.C.A I.C.A I.A FILED SEA PLC LATER
00003
0-WD510-EM103-
UF UNIT "B" INLET(WATER) PRESS. TRANS. AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C.A I.C.A I.A FILED SEA PLC LATER
00003
0-WD510-EM103-
UF UNIT "B" INLET(INST.AIR) PRESS. TRANS. AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C.A I.C.A I.A FILED SEA PLC LATER
00003
0-WD510-EM103-
UF UNIT "B" BACK WASH PRESS. TRANS. AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C.A I.C.A I.A FILED SEA PLC LATER
00003
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : AI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
ALARM
SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-EM103-
FILTERED WATER TANK LEVEL TRANS. AI 4 ~ 20 mA EXT 0~10 m I.C I.C I FILED SEA PLC LATER
00004
0-WD510-EM103-
FILTERED WATER FEED PUMP A/B DSCH. PRESS.TRANS AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C.A I.C.A I.A FILED SEA PLC LATER
00004
0-WD510-EM103-
SWRO MICRO FILTER "A/B" OUTLET PRESS.TRANS. AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C.A I.C.A I.A FILED SEA PLC LATER
00004
0~100,00 0-WD510-EM103-
SWRO MICRO FILTER "A/B" INLET COND AI 4 ~ 20 mA INT
0
㎲/㎝ I.C I.C I FILED SEA PLC LATER
00004
0-WD510-EM103-
SWRO MICRO FILTER "A/B" OUTLET ORP AI 4 ~ 20 mA INT 0~35 pH I.C I.C I FILED SEA PLC LATER
00004
0-WD510-EM103-
SWRO MICRO FILTER "A/B" OUTLET PH AI 4 ~ 20 mA INT 0~35 pH I.C I.C I FILED SEA PLC LATER
00004
0-WD510-EM103-
SWRO UNIT "A" OUTLET FLOW(MAG.) AI 4 ~ 20 mA INT 0~60 m3/h I.C I.C I FILED SEA PLC LATER
00005
0-WD510-EM103-
SWRO UNIT "A" CIRCULATION PRESS. TRANS. AI 4 ~ 20 mA EXT 0~210 Kg/cm2g I.C I.C I FILED SEA PLC LATER
00005
0-WD510-EM103-
SWRO HIGH PRESS. PUMP A PRESS. TRANS. AI 4 ~ 20 mA EXT 0~210 Kg/cm2g I.C I.C I FILED SEA PLC LATER
00005
0-WD510-EM103-
SWRO UNIT "A" OUTLET (COUND) AI 4 ~ 20 mA INT 0~2000 ㎲/㎝ I.C I.C I FILED SEA PLC LATER
00005
0-WD510-EM103-
SWRO UNIT "A" OUTLET (HZ) AI 4 ~ 20 mA INT 0~60 Hz I I I MCC SEA PLC LATER
00005
0-WD510-EM103-
SWRO UNIT "A" OUTLET (AMPARE) AI 4 ~ 20 mA INT HOLD A I I I MCC SEA PLC LATER
00005
0-WD510-EM103-
SWRO UNIT "B" OUTLET FLOW(MAG.) AI 4 ~ 20 mA INT 0~60 m3/h I.C I.C I FILED SEA PLC LATER
00006
0-WD510-EM103-
SWRO UNIT "B" CIRCULATION PRESS. TRANS. AI 4 ~ 20 mA EXT 0~210 Kg/cm2g I.C I.C I FILED SEA PLC LATER
00006
0-WD510-EM103-
SWRO HIGH PRESS. PUMP B PRESS.TRANS. AI 4 ~ 20 mA EXT 0~210 Kg/cm2g I.C I.C I FILED SEA PLC LATER
00006
0-WD510-EM103-
SWRO UNIT "B" OUTLET (COND) AI 4 ~ 20 mA INT 0~2000 ㎲/㎝ I.C I.C I FILED SEA PLC LATER
00006
0-WD510-EM103-
SWRO UNIT "B" OUTLET (HZ) AI 4 ~ 20 mA INT 0~60 Hz I I I MCC SEA PLC LATER
00006
0-WD510-EM103-
SWRO UNIT "B" OUTLET (AMPARE) AI 4 ~ 20 mA INT HOLD A I I I MCC SEA PLC LATER
00006
0-WD510-EM103-
SWRO PRODUCT WATER TANK LEVEL TRANS. AI 4 ~ 20 mA EXT 0~10,000 mmH20 I.C.A I.C.A I.A FILED SEA PLC LATER
00007
0-WD510-EM103-
SWRO PRODUCT WATER TANK INLET AI 4 ~ 20 mA INT pH I.C.A I.C.A I.A FILED SEA PLC LATER
00007
0-WD510-EM103-
CHEMICAL CLEANING TANK LEVEL TRANS. AI 4 ~ 20 mA EXT 0~10,000 mmH20 I.C.A I.C.A I.A FILED SEA PLC LATER
00007
0-WD510-EM103-
BWRO MICRO FILTER "A" OUTLET PRESS. TRANS AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I I I FILED SEA PLC LATER
00008
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : AI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
ALARM
SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-EM103-
BWRO UNIT "A/B" INLET PRESS. TRANS AI 4 ~ 20 mA EXT I.A I.A I.A FILED SEA PLC LATER
00008
0-WD510-EM103-
BWRO UNIT "A" OUTLET FLOW(TURBINE) AI 4 ~ 20 mA INT 5~50 ㎥/Hr I.C I.C I FILED SEA PLC LATER
00008
0-WD510-EM103-
BWRO HIGH PRESS. PUMP "A" OUTLET PRESS.TRANS. AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C I.C I FILED SEA PLC LATER
00008
0-WD510-EM103-
BWRO HIGH PRESS. PUMP A PRESS.TRANS. AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.A I.A I.A FILED SEA PLC LATER
00008
0-WD510-EM103-
BWRO UNIT "A" OUTLET (COND) AI 4 ~ 20 mA INT 0~500 ㎲/㎝ I.C I.C I FILED SEA PLC LATER
00008
0-WD510-EM103-
BWRO UNIT "A" OUTLET (HZ) AI 4 ~ 20 mA INT 0~60 Hz I I I MCC SEA PLC LATER
00008
0-WD510-EM103-
BWRO UNIT "A" OUTLET (AMPARE) AI 4 ~ 20 mA INT HOLD A I I I MCC SEA PLC LATER
00008
0-WD510-EM103-
BWRO MICRO FILTER "B" OUTLET PRESS. TRANS AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.A I.A I.A FILED SEA PLC LATER
00008
0-WD510-EM103-
BWRO UNIT "B" OUTLET FLOW(TURBINE) AI 4 ~ 20 mA INT 3~30 ㎥/Hr I.C I.C I FILED SEA PLC LATER
00008
0-WD510-EM103-
BWRO HIGH PRESS. PUMP "B" OUTLET PRESS.TRANS AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C I.C I FILED SEA PLC LATER
00008
0-WD510-EM103-
BWRO HIGH PRESS. PUMP B PRESS.TRANS AI 4 ~ 20 mA INT 0~35 Kg/cm2g I.C.A I.C.A I.A FILED SEA PLC LATER
00008
0-WD510-EM103-
BWRO UNIT "B" OUTLET (COND) AI 4 ~ 20 mA INT 0~500 ㎲/㎝ I.C I.C I FILED SEA PLC LATER
00008
0-WD510-EM103-
BWRO UNIT "B" OUTLET (HZ) AI 4 ~ 20 mA INT 0~60 Hz I I I MCC SEA PLC LATER
00008
0-WD510-EM103-
BWRO UNIT "B" OUTLET (AMPARE) AI 4 ~ 20 mA INT HOLD A I I I MCC SEA PLC LATER
00008
0-WD510-EM103-
BUFFER TANK LEVEL TRANS. AI 4 ~ 20 mA EXT 0~10,000 mmH20 I.A I.A I.A FILED SEA PLC LATER
00009
0-WD510-EM103-
DESALINATED WATER OUTLET PRESS. TRANS AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C I.C I FILED SEA PLC LATER
00009
0-WD510-EM103-
DESALINATED WATER PUMP A/B/C DISCH. FLOW(ORIFFICE)AI 4 ~ 20 mA EXT 0~1250 mmH20 I.C I.C I FILED SEA PLC LATER
00009
0-WD510-EM103-
DAF PAKAGE PH TRANS. AI 4 ~ 20 mA EXT 0~14 pH I.C I.C I FILED SEA PLC LATER
00009
0-WD510-EM103-
AIR RECEIVER TANK OUTLET PRESS. TRANS. AI 4 ~ 20 mA EXT 0~35 Kg/cm2g I.C I.C I FILED SEA PLC LATER
00009
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : AO
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE LOOP HMI REMARKS
. SET LOGIC/LOOP
I/O SIGNAL POWE RANGE UNIT DEMI SEA DCS FROM TO P & ID
DWG
R WTP WTP
0-WD510-EM103-
1 0 FCV-00GDR21AA071UF UNIT "A" INLET CONTROL V/V (PID) AO 4~20mA INT 0-100 % I.C I.C - SEA PLC FILED LATER
00003
0-WD510-EM103-
2 0 FCV-00GDR22AA071UF UNIT "B" INLET CONTROL V/V (PID) AO 4~20mA INT 0-100 % I.C I.C - SEA PLC FILED LATER
00003
0-WD510-EM103-
3 0 00GDF21AP001 SWRO HIGH PRESS. PUMP A INV AO 4~20mA INT 0-100 % I.C I.C - SEA PLC MCC LATER
00005
0-WD510-EM103-
4 0 00GDF22AP001 SWRO HIGH PRESS. PUMP B INV AO 4~20mA INT 0-100 % I.C I.C - SEA PLC MCC LATER
00006
0-WD510-EM103-
5 0 00GDF70AP001 BWRO HIGH PRESS. PUMP A INV AO 4~20mA INT 0-100 % I.C I.C - SEA PLC MCC LATER
00008
0-WD510-EM103-
6 0 00GDF71AP001 BWRO HIGH PRESS. PUMP B INV AO 4~20mA INT 0-100 % I.C I.C - SEA PLC MCC LATER
00008
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
1 0 XV-00GDP20AA061 VACCUUM TANK OUTLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00001
0-WD510-
2 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00001
0-WD510-
3 0 XV-00GDP20AA062 VACCUUM TANK INLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00001
0-WD510-
4 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00001
0-WD510-
5 0 LS-00GDP20CL201 VACCUM TANK LEVEL SWITCH DI 1_HAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00001
0-WD510-
6 0 MOP(SKID-S001) VACUUM PUMP A DI 1_START DRY I.C I I SKID-S001 DEMI PLC LATER
EM103-00001
0-WD510-
7 0 DI 1_FAULT DRY I.C I I SKID-S001 DEMI PLC LATER
EM103-00001
0-WD510-
8 0 VACUUM PUMP B DI 1_START DRY I.C I I SKID-S001 DEMI PLC LATER
EM103-00001
0-WD510-
9 0 DI 1_FAULT DRY I.C I I SKID-S001 DEMI PLC LATER
EM103-00001
0-WD510-
10 0 00GDR60AN001 AIR COMPRESSOR PAKAGE PANEL DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
11 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
12 0 00GDP40AP001 POTABLE DREDGING PUMP DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
13 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
14 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
15 0 LS-00GDP30CL201 SEA WATER TANK LEVEL SWITCH DI 1_LAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00001
0-WD510-
16 0 LS-00GDP30CL202 SEA WATER TANK LEVEL SWITCH DI 1_LAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00001
0-WD510-
17 0 00GDP30AP001 SEA WATER PUMP A DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
18 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
19 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
20 0 00GDP30AP002 SEA WATER PUMP B DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
21 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
22 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
23 0 00GDP30AP003 SEA WATER PUMP C DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
24 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00001
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
25 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
26 0 XV-00GDP30AA061 SEA WATER PUMP A OUTLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00001
0-WD510-
27 0 XV-00GDP30AA062 SEA WATER PUMP B OUTLET V/VLIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00001
0-WD510-
28 0 XV-00GDP30AA063 SEA WATER PUMP C OUTLET V/VLIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00001
0-WD510-
29 0 FIT-00GDP30CF101 SEA WATER PUMP A/B/C OUTLET FLOW(MAG.) DI 1_PULSE DRY I.C I I FILED DEMI PLC LATER
EM103-00001
0-WD510-
30 0 FIT-00GDK80CF101 RETURN PUMP OUTLET FLOW(MAG.) DI 1_PULSE DRY I.C I I FILED DEMI PLC LATER
EM103-00001
0-WD510-
31 0 00GDK80AP001 RETURN PUMP DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
32 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
33 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
34 0 00GDE40AM001 NEUTRALIZATION PIT AGITATOR DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
35 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
36 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
37 0 00GDE40AP001 NEUTRALIZATION PUMP A DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
38 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
39 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
40 0 00GDE40AP002 NEUTRALIZATION PUMP B DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
41 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
42 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00001
0-WD510-
43 0 MOP(DAF PACKAGE) TREATED WATER TANK LEVEL SWITCH DI 1_HAL DRY I.C.A I.A I.A DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
44 0 DI 1_LL DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
45 0 POLYMER STORAGE TANK LEVEL SWITCH DI 1_LAL DRY I.C.A I.A I.A DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
46 0 RECIRCULATION PUMP A DI 1_START DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
47 0 DI 1_FAULT DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
48 0 RECIRCULATION PUMP B DI 1_START DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
49 0 DI 1_FAULT DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
50 0 AUGER DI 1_START DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
51 0 DI 1_FAULT DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
52 0 SKIMMER DI 1_START DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
53 0 DI 1_FAULT DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
54 0 AIR COMPRESSOR A DI 1_START DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
55 0 DI 1_FAULT DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
56 0 AIR COMPRESSOR B DI 1_START DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
57 0 DI 1_FAULT DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
58 0 POLYMER AGITATOR DI 1_START DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
59 0 DI 1_FAULT DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
60 0 POLYMER DOSING PUMP A DI 1_START DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
61 0 DI 1_FAULT DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
62 0 POLYMER DOSING PUMP B DI 1_START DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
63 0 DI 1_FAULT DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
64 0 BOOSTER PUMP DI 1_START DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
65 0 DI 1_FAULT DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
66 0 AIGTATOR STORAGE LEVEL SWITCH DI 1_HAL DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
67 0 DI 1_LAL DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
68 0 REMOTE MODE DI 1_REMOTE DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
69 0 NOMAL MODE DI 1_NOMAL DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
70 0 TOTAL ALARAM DI 1_TOTAL AL DRY I.C I I DAF PAK DEMI PLC LATER
EM103-00002
0-WD510-
71 0 00GDR10AT001 PRIMERY FILTER A DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00002
0-WD510-
72 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00002
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
73 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00002
0-WD510-
74 0 00GDR10AT002 PRIMERY FILTER B DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00002
0-WD510-
75 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00002
0-WD510-
76 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00002
0-WD510-
77 0 00GDR10AT003 PRIMERY FILTER C DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00002
0-WD510-
78 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00002
0-WD510-
79 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00002
0-WD510-
80 0 XV-00GDR10AA061 PRIMERY FILTER "A" INLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
81 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
82 0 XV-00GDR10AA062 PRIMERY FILTER "A" OUTLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
83 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
84 0 XV-00GDR10AA063 PRIMERY FILTER "A" DRAIN V/V LIMT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
85 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
86 0 XV-00GDR10AA064 PRIMERY FILTER "B" INLET V/V LIMT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
87 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
88 0 XV-00GDR10AA065 PRIMERY FILTER "B" OUTLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
89 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
90 0 XV-00GDR10AA066 PRIMERY FILTER "B" DRAIN V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
91 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
92 0 XV-00GDR10AA067 PRIMERY FILTER "C" INLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
93 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
94 0 XV-00GDR10AA068 PRIMERY FILTER "C" OUTLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
95 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
96 0 XV-00GDR10AA069 PRIMERY FILTER "C" DRAIN V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00002
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
97 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00002
0-WD510-
98 0 MOP(SKID-Y001) MAIN MOTOR(A) DI 1_START DRY I.C I I SKID-Y001 DEMI PLC LATER
EM103-00002
0-WD510-
99 0 DI 1_FAULT DRY I.C I I SKID-Y001 DEMI PLC LATER
EM103-00002
0-WD510-
100 0 FAN MOTOR(A) DI 1_START DRY I.C I I SKID-Y001 DEMI PLC LATER
EM103-00002
0-WD510-
101 0 DI 1_FAULT DRY I.C I I SKID-Y001 DEMI PLC LATER
EM103-00002
0-WD510-
102 0 SKID-Y001 REMOTE MODE(A) DI 1_REMOTE DRY I.C I I SKID-Y001 DEMI PLC LATER
EM103-00002
0-WD510-
103 0 MOP(SKID-Y002) MAIN MOTOR(B) DI 1_START DRY I.C I I SKID-Y002 DEMI PLC LATER
EM103-00002
0-WD510-
104 0 DI 1_FAULT DRY I.C I I SKID-Y002 DEMI PLC LATER
EM103-00002
0-WD510-
105 0 FAN MOTOR(B) DI 1_START DRY I.C I I SKID-Y002 DEMI PLC LATER
EM103-00002
0-WD510-
106 0 DI 1_FAULT DRY I.C I I SKID-Y002 DEMI PLC LATER
EM103-00002
0-WD510-
107 0 SKID-Y002 REMOTE MODE(B) DI 1_REMOTE DRY I.C I I SKID-Y002 DEMI PLC LATER
EM103-00002
0-WD510-
108 0 XV-00GDR21AA061 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
109 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
110 0 XV-00GDR21AA062 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
111 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
112 0 XV-00GDR21AA063 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
113 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
114 0 XV-00GDR21AA064 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
115 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
116 0 XV-00GDR21AA065 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
117 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
118 0 XV-00GDR21AA066 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
119 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
120 0 XV-00GDR21AA067 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
121 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
122 0 XV-00GDR21AA068 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
123 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
124 0 XV-00GDR21AA069 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
125 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
126 0 XV-00GDR21AA070 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
127 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
128 0 FIT-00GDR21CF101 UF UNIT "A" OUTLET FLOW(MAG.) DI 1_PULSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
129 0 XV-00GDR22AA061 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
130 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
131 0 XV-00GDR22AA062 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
132 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
133 0 XV-00GDR22AA063 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
134 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
135 0 XV-00GDR22AA064 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
136 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
137 0 XV-00GDR22AA065 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
138 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
139 0 XV-00GDR22AA066 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
140 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
141 0 XV-00GDR22AA067 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
142 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
143 0 XV-00GDR22AA068 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
144 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
145 0 XV-00GDR22AA069 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
146 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
147 0 XV-00GDR22AA070 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
148 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
149 0 FIT-00GDR22CF101 UF UNIT "B" OUTLET FLOW(MAG.) DI 1_PULSE DRY I.C I I FILED DEMI PLC LATER
EM103-00003
0-WD510-
150 0 00GDR40AP001 UF BACKWASH PUMP A DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00004
0-WD510-
151 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00004
0-WD510-
152 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00004
0-WD510-
153 0 00GDR40AP002 UF BACKWASH PUMP B DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00004
0-WD510-
154 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00004
0-WD510-
155 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00004

156 0 00GDR50AP001 FILTERED WATER FEED PUMP A DI 1_START DRY I.C I I MCC DEMI PLC LATER -

157 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER -

158 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER -

159 0 00GDR50AP002 FILTERED WATER FEED PUMP B DI 1_START DRY I.C I I MCC DEMI PLC LATER -

160 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER -

161 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER -

0-WD510-
162 0 XV-00GDF10AA061 SWRO MICRO FILTER "A" INET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
163 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
164 0 XV-00GDF10AA062 SWRO MICRO FILTER "A" OUTLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
165 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
166 0 XV-00GDF10AA063 SWRO MICRO FILTER "B" INET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
167 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
168 0 XV-00GDF10AA064 SWRO MICRO FILTER "B" OUTLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00004
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
169 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
170 0 XV-00GDF10AA065 FOR SWRO H/P PUMP "A" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
171 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
172 0 XV-00GDF10AA066 FOR SWRO H/P PUMP "B" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
173 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
174 0 XV-00GDF10AA067 SWRO MICRO FILTER "AB" OUTLET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
175 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00004
0-WD510-
176 0 PS-00GDF21CP201 SWRO HIGH PRESS.PUMP "A" INLET PRESS.SWITCH DI 1_PAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00005
0-WD510-
177 0 FIT-00GDF31CF101 SWRO UNIT "A" OUTLET FLOW(MAG.) DI 1_PULSE DRY I.C I I FILED DEMI PLC LATER
EM103-00005
0-WD510-
178 0 00GDF21AP001 SWRO HIGH PRESS. PUMP A DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00005
0-WD510-
179 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00005
0-WD510-
180 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00005
0-WD510-
181 0 XV-00GDF31AA061 SWRO UNIT "A" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00005
0-WD510-
182 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00005
0-WD510-
183 0 XV-00GDF31AA062 SWRO UNIT "A" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00005
0-WD510-
184 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00005
0-WD510-
185 0 XV-00GDF31AA063 SWRO UNIT "A" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00005
0-WD510-
186 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00005
0-WD510-
187 0 XV-00GDF31AA064 SWRO UNIT "A" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00005
0-WD510-
188 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00005
0-WD510-
189 0 PS-00GDF22CP201 SWRO HIGH PRESS.PUMP "B" INLET PRESS.SWITCH DI 1_PAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00006
0-WD510-
190 0 FIT-00GDF32CF101 SWRO UNIT "B" OUTLET FLOW(MAG.) DI 1_PULSE DRY I.C I I FILED DEMI PLC LATER
EM103-00006
0-WD510-
191 0 00GDF22AP001 SWRO HIGH PRESS. PUMP B DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00006
0-WD510-
192 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00006
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
193 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00006
0-WD510-
194 0 XV-00GDF32AA061 SWRO UNIT "B" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00006
0-WD510-
195 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00006
0-WD510-
196 0 XV-00GDF32AA062 SWRO UNIT "B" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00006
0-WD510-
197 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00006
0-WD510-
198 0 XV-00GDF32AA063 SWRO UNIT "B" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00006
0-WD510-
199 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00006
0-WD510-
200 0 XV-00GDF32AA064 SWRO UNIT "B" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00006
0-WD510-
201 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00006
0-WD510-
202 0 LS-00GDN60CL201 NaOH DOSING TANK LEVEL DI 1_HH DRY I.C. I.A I.A FILED DEMI PLC LATER
EM103-00007
0-WD510-
203 0 DI 1_H DRY I.C. I I FILED DEMI PLC LATER
EM103-00007
0-WD510-
204 0 DI 1_LAL DRY I.C I I FILED DEMI PLC LATER
EM103-00007
0-WD510-
205 0 DI 1_LL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00007
0-WD510-
206 0 00GDN60AM001 NaOH DOSING TANK AGITATOR DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
207 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
208 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
209 0 00GDN60AP001 NaOH DOSING PUMP A DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
210 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
211 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
212 0 00GDN60AP002 NaOH DOSING PUMP B DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
213 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
214 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
215 0 00GDF50AP001 BWRO FEED PUMP A DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
216 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00007
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
217 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
218 0 00GDF50AP002 BWRO FEED PUMP B DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
219 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
220 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
221 0 TIS-00GDE10CT201 CHEMICAL CLEANING TANK TEMP.SWITCH DI 1_TEMP AL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00007
0-WD510-
222 0 00GDE20AP001 CHEMICAL CLEANING PUMP A DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
223 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
224 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
225 0 00GDE20AP002 CHEMICAL CLEANING PUMP B DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
226 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
227 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
228 0 00GDE10AM001 CHEMICAL CLEANING TANK AGITATOR DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
229 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
230 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00007
0-WD510-
231 0 HE-00GDE10AH001 ELECTRIC HEATER DI 1_START DRY I.C I I FILED DEMI PLC LATER
EM103-00007
0-WD510-
232 0 DI 1_FAULT DRY I.C I I FILED DEMI PLC LATER
EM103-00007
0-WD510-
233 0 DI 1_REMOTE DRY I.C I I FILED DEMI PLC LATER
EM103-00007
0-WD510-
234 0 XV-00GDE10AA061 CHEMICAL CLEANING TANK(SERVICE WATER) INET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00007
0-WD510-
235 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00007
0-WD510-
236 0 XV-00GDM20AA001 SERVICE WATER(UF/SWRO/BWRO CIP INLET) V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00007
0-WD510-
237 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00007
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
238 0 PS-00GDF60CP201 BWRO HIGH PRESS.PUMP "A" INLET PRESS.SWITCH DI 1_PAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00008
0-WD510-
239 0 FIT-00GDF80CF101 BWRO UNIT "A" OUTLET FLOW(TURBINE) DI 1_PULSE DRY I.C I I FILED DEMI PLC LATER
EM103-00008
0-WD510-
240 0 00GDF70AP001 BWRO HIGH PRESS. PUMP A DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00008
0-WD510-
241 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00008
0-WD510-
242 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00008
0-WD510-
243 0 XV-00GDF60AA061 BWRO FEED PUMP DISCH. V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00008
0-WD510-
244 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00008
0-WD510-
245 0 XV-00GDF80AA061 BUFFER TANK INET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00008
0-WD510-
246 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00008
0-WD510-
247 0 XV-00GDF80AA062 BWRO UNIT "A" DRAIN V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00008
0-WD510-
248 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00008
0-WD510-
249 0 PS-00GDF61CP201 BWRO HIGH PRESS.PUMP "B" INLET PRESS.SWITCH DI 1_PAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00009
0-WD510-
250 0 FIT-00GDF81CF101 BWRO UNIT "B" OUTLET FLOW(TURBINE) DI 1_PULSE DRY I.C I I FILED DEMI PLC LATER
EM103-00009
0-WD510-
251 0 00GDF71AP001 BWRO HIGH PRESS. PUMP B DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00009
0-WD510-
252 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00009
0-WD510-
253 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00009
0-WD510-
254 0 XV-00GDF61AA061 BWRO FEED PUMP DISCH. V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00009
0-WD510-
255 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00009
0-WD510-
256 0 XV-00GDF81AA061 BUFFER TANK INET V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00009
0-WD510-
257 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00009
0-WD510-
258 0 XV-00GDF81AA062 BWRO UNIT DRAIN "B" V/V LIMIT DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER
EM103-00009
0-WD510-
259 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER
EM103-00009
0-WD510-
260 0 LS-00GDM10CL201 BUFFER TANK LEVEL SWITCH DI 1_H DRY I.C I I FILED DEMI PLC LATER
EM103-00010
0-WD510-
261 0 DI 1_L DRY I.C I I FILED DEMI PLC LATER
EM103-00010
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
262 0 DI 1_LAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00010
0-WD510-
263 0 00GDM20AP001 DESALINATED WATER PUMP A DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00010
0-WD510-
264 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00010
0-WD510-
265 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00010
0-WD510-
266 0 00GDM20AP002 DESALINATED WATER PUMP B DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00010
0-WD510-
267 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00010
0-WD510-
268 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00010
0-WD510-
269 0 00GDM20AP003 DESALINATED WATER PUMP C DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00010
0-WD510-
270 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00010
0-WD510-
271 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00010
0-WD510-
272 0 FIT-00GDM20CF101 DESALINATED WATER PUMP A/B/C DISCH. FLOW(ORIFFICE) DI 1_PULSE DRY I.C I I FILED DEMI PLC LATER
EM103-00010
0-WD510-
273 0 LS-00GDN20CL201 NaOcℓ DOSING TANK LEVEL SWITCH DI 1_HH DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00011
0-WD510-
274 0 DI 1_H DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
275 0 DI 1_L DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
276 0 DI 1_LLA DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00011
0-WD510-
277 0 00GDN20AM001 NaOcℓ DOSING TANK AGITATOR DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
278 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
279 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
280 0 00GDN20AP001 NaOcℓ DOSING PUMP A(FOR SEA WATER INTAKE) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
281 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
282 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
283 0 00GDN20AP002 NaOcℓ DOSING PUMP B(FOR SEA WATER INTAKE) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
284 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
285 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
286 0 00GDN20AP003 NaOcℓ DOSING PUMP C(FOR CEB) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
287 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
288 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
289 0 00GDN20AP004 NaOcℓ DOSING PUMP D(FOR CEB) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
290 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
291 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
292 0 LS-00GDN30CL201 ANTISCALANT DOSING TANK LEVEL SWITCH DI 1_HH DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
293 0 DI 1_H DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
294 0 DI 1_L DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
295 0 DI 1_LAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00011
0-WD510-
296 0 00GDN30AM001 ANTISCALANT DOSING TANK AGITATOR DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
297 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
298 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
299 0 00GDN30AP001 ANTISCALANT DOSING PUMP A(SWRO MICRO FILTER INLET) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
300 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
301 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
302 0 00GDN30AP002 ANTISCALANT DOSING PUMP B(SWRO MICRO FILTER INLET) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
303 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
304 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
305 0 LS-00GDN40CL201 ACID DOSING TANK LEVEL SWITCH DI 1_H DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
306 0 DI 1_H DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
307 0 DI 1_L DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
308 0 DI 1_LAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00011
0-WD510-
309 0 00GDM40AM001 ACID DOSING TANK AGITATOR DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
310 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
311 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
312 0 00GDN40AP001 ACID DOSING PUMP A(SWRO MICRO FILTER INLET) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
313 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
314 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
315 0 00GDN40AP002 ACID DOSING PUMP B(SWRO MICRO FILTER INLET) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
316 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
317 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
318 0 LS-00GDN10CL201 COAGULANT DOSING TANK LEVEL SWITCH DI 1_HH DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
319 0 DI 1_H DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
320 0 DI 1_L DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
321 0 DI 1_LAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00011
0-WD510-
322 0 00GDM10AM001 COAGULANT DOSING TANK AGITATOR DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
323 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
324 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
325 0 00GDN10AP001 COAGULANT DOSING PUMP A(D.A.F INLET) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
326 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
327 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
328 0 00GDN10AP002 COAGULANT DOSING PUMP B(D.A.F INLET) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
329 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
330 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
331 0 00GDN10AP003 COAGULANT DOSING PUMP C(D.A.F INLET) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
332 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
333 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DI
INPUT/OUTPUT
FUNCTION LOCATION REFERENCE DWG
SIGNAL
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-
334 0 LS-00GDN50CL201 SBS DOSING TANK LEVEL SWITCH DI 1_HH DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
335 0 DI 1_H DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
336 0 DI 1_L DRY I.C I I FILED DEMI PLC LATER
EM103-00011
0-WD510-
337 0 DI 1_LAL DRY I.C.A I.A I.A FILED DEMI PLC LATER
EM103-00011
0-WD510-
338 0 00GDN50AM001 SBS DOSING TANK AGITATOR DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
339 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
340 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
341 0 00GDN50AP001 SBS DOSING PUMP A(SWRO INLET/NEUT.PIT) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
342 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
343 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
344 0 00GDN50AP002 SBS DOSING PUMP B(SWRO INLET/NEUT.PIT) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
345 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
346 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
347 0 00GDN50AP003 SBS DOSING PUMP C(SWRO INLET/NEUT.PIT) DI 1_START DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
348 0 DI 1_FAULT DRY I.C I I MCC DEMI PLC LATER
EM103-00011
0-WD510-
349 0 DI 1_REMOTE DRY I.C I I MCC DEMI PLC LATER
EM103-00011

350 0 4.16KV SWITCH GEAR TRANSFORMER INCOMMING DI 1_OPEN DRY I.C I I FILED DEMI PLC LATER

351 0 DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER

352 0 DI 1_REMOTE DRY I.C I I FILED DEMI PLC LATER

353 0 480KV SWITCH GEAR TRANSFORMER OUTGOING DI 1_CLOSE DRY I.C I I FILED DEMI PLC LATER

354 0 DI 1_TRIP DRY I.C I I FILED DEMI PLC LATER

355 0 DI 1_REMOTE DRY I.C I I FILED DEMI PLC LATER

356 0 DI 1_OAL DRY I.C I I FILED DEMI PLC LATER


Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DO
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-EM103-
1 0 XV-00GDP20AA061 VACCUUM TANK OUTLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
2 0 XV-00GDP20AA062 VACCUUM TANK INLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
3 0 MOP(SKID-S001) VACUUM PUMP A DOII 1_START DRY - - C C - DEMI HMI SKID-S001 SKID-S001
00001
0-WD510-EM103-
4 0 VACUUM PUMP B DOII 1_START DRY - - C C - DEMI HMI SKID-S001 SKID-S001
00001
0-WD510-EM103-
5 0 PACKAGE AIR COMPRESSOR A DOII 1_START DRY - - C C - DEMI HMI PACKAGE PACKAGE
00001
0-WD510-EM103-
6 0 AIR COMPRESSOR B DOII 1_START DRY - - C C - DEMI HMI PACKAGE PACKAGE
00001
0-WD510-EM103-
7 0 00GDP30AP001 SEA WATER PUMP A DOII 1_OPEN DRY - - C C - DEMI HMI MCC LATER
00001
0-WD510-EM103-
8 0 00GDP30AP002 SEA WATER PUMP B DOII 1_OPEN DRY - - C C - DEMI HMI MCC LATER
00001
0-WD510-EM103-
9 0 00GDP30AP003 SEA WATER PUMP C DOII 1_OPEN DRY - - C C - DEMI HMI MCC LATER
00001
0-WD510-EM103-
10 0 SV-00GDP30AA002 SEA WATER SV A START DOI 1_OPEN 120V - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
11 0 SV-00GDP30AA003 SEA WATER SV B START DOI 1_OPEN 120V - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
12 0 SV-00GDP30AA004 SEA WATER SV C START DOI 1_OPEN 120V - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
13 0 XV-00GDP30AA061 SEA WATER PUMP A OUTLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
14 0 XV-00GDP30AA062 SEA WATER PUMP B OUTLET V/VLIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
15 0 XV-00GDP30AA063 SEA WATER PUMP C OUTLET V/VLIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
16 0 00GDK80AP001 RETURN PUMP DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
17 0 00GDE40AM001 NEUTRALIZATION PIT AGITATOR DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
18 0 00GDE40AP001 NEUTRALIZATION PUMP A DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
19 0 00GDE40AP002 NEUTRALIZATION PUMP B DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00001
0-WD510-EM103-
20 0 MOP(DAF PACKAGE) REMOTE START DOII 1_START DRY - - C C - DEMI HMI FILED DAF-PAC
00002
0-WD510-EM103-
21 0 00GDR10AT001 PRIMERY FILTER A DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00002
0-WD510-EM103-
22 0 00GDR10AT002 PRIMERY FILTER B DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00002
0-WD510-EM103-
23 0 00GDR10AT003 PRIMERY FILTER C DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00002
0-WD510-EM103-
24 0 XV-00GDR10AA061 PRIMERY FILTER "A" INLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00002
0-WD510-EM103-
25 0 XV-00GDR10AA062 PRIMERY FILTER "A" OUTLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00002
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DO
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-EM103-
26 0 XV-00GDR10AA063 PRIMERY FILTER "A" DRAIN V/V LIMT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00002
0-WD510-EM103-
27 0 XV-00GDR10AA064 PRIMERY FILTER "B" INLET V/V LIMT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00002
0-WD510-EM103-
28 0 XV-00GDR10AA065 PRIMERY FILTER "B" OUTLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00002
0-WD510-EM103-
29 0 XV-00GDR10AA066 PRIMERY FILTER "B" DRAIN V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00002
0-WD510-EM103-
30 0 XV-00GDR10AA067 PRIMERY FILTER "C" INLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00002
0-WD510-EM103-
31 0 XV-00GDR10AA068 PRIMERY FILTER "C" OUTLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00002
0-WD510-EM103-
32 0 XV-00GDR10AA069 PRIMERY FILTER "C" DRAIN V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00002
0-WD510-EM103-
33 0 MOP(SKID-Y001) REMOTE START(A) DOII 1_START DRY - - C C - DEMI HMI SKID-Y001 SKID-Y001
00002
0-WD510-EM103-
34 0 MOP(SKID-Y002) REMOTE START(B) DOII 1_START DRY - - C C - DEMI HMI SKID-Y002 SKID-Y002
00002
0-WD510-EM103-
35 0 XV-00GDR21AA061 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
36 0 XV-00GDR21AA062 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
37 0 XV-00GDR21AA062 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
38 0 XV-00GDR21AA064 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
39 0 XV-00GDR21AA065 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
40 0 XV-00GDR21AA066 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
41 0 XV-00GDR21AA066 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
42 0 XV-00GDR21AA068 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
43 0 XV-00GDR21AA069 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
44 0 XV-00GDR21AA070 ULTRA FILTRATION UNIT(UF UNIT "A") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
45 0 XV-00GDR22AA061 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
46 0 XV-00GDR22AA062 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
47 0 XV-00GDR22AA063 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
48 0 XV-00GDR22AA064 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
49 0 XV-00GDR22AA065 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
50 0 XV-00GDR22AA066 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DO
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-EM103-
51 0 XV-00GDR22AA067 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
52 0 XV-00GDR22AA068 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
53 0 XV-00GDR22AA069 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
54 0 XV-00GDR22AA070 LINE MIXER FOR BACKWASH UNIT(UF UNIT "B") V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00003
0-WD510-EM103-
55 0 00GDR40AP001 UF BACKWASH PUMP A DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00004
0-WD510-EM103-
56 0 00GDR40AP002 UF BACKWASH PUMP B DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00004
0-WD510-EM103-
57 0 00GDR50AP001 FILTERED WATER FEED PUMP A DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00004
0-WD510-EM103-
58 0 00GDR50AP002 FILTERED WATER FEED PUMP B DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00004
0-WD510-EM103-
59 0 XV-00GDF10AA061 SWRO MICRO FILTER "A" INET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00004
0-WD510-EM103-
60 0 XV-00GDF10AA062 SWRO MICRO FILTER "A" OUTLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00004
0-WD510-EM103-
61 0 XV-00GDF10AA063 SWRO MICRO FILTER "B" INET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00004
0-WD510-EM103-
62 0 XV-00GDF10AA064 SWRO MICRO FILTER "B" OUTLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00004
0-WD510-EM103-
63 0 XV-00GDF10AA065 FOR SWRO H/P PUMP "A" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00004
0-WD510-EM103-
64 0 XV-00GDF10AA066 FOR SWRO H/P PUMP "B" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00004
0-WD510-EM103-
65 0 XV-00GDF10AA067 SWRO MICRO FILTER "AB" OUTLET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00004
0-WD510-EM103-
66 0 00GDF21AP001 SWRO HIGH PRESS. PUMP A DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00005
0-WD510-EM103-
67 0 XV-00GDF31AA061 SWRO UNIT "A" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00005
0-WD510-EM103-
68 0 XV-00GDF31AA062 SWRO UNIT "A" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00005
0-WD510-EM103-
69 0 XV-00GDF31AA063 SWRO UNIT "A" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00005
0-WD510-EM103-
70 0 XV-00GDF31AA064 SWRO UNIT "A" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00005
0-WD510-EM103-
71 0 00GDF22AP001 SWRO HIGH PRESS. PUMP B DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00005
0-WD510-EM103-
72 0 XV-00GDF32AA061 SWRO UNIT "B" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00006
0-WD510-EM103-
73 0 XV-00GDF32AA062 SWRO UNIT "B" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00006
0-WD510-EM103-
74 0 XV-00GDF32AA063 SWRO UNIT "B" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00006
0-WD510-EM103-
75 0 XV-00GDF32AA064 SWRO UNIT "B" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00006
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DO
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-EM103-
76 0 00GDN60AM001 NaOH DOSING TANK AGITATOR DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00007
0-WD510-EM103-
77 0 00GDN60AP001 NaOH DOSING PUMP A DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00007
0-WD510-EM103-
78 0 00GDN60AP002 NaOH DOSING PUMP B DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00007
0-WD510-EM103-
79 0 00GDF50AP001 BWRO FEED PUMP A DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00007
0-WD510-EM103-
80 0 00GDF50AP002 BWRO FEED PUMP B DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00007
0-WD510-EM103-
81 0 00GDE20AP001 CHEMICAL CLEANING PUMP A DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00007
0-WD510-EM103-
82 0 00GDE20AP002 CHEMICAL CLEANING PUMP B DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00007
0-WD510-EM103-
83 0 00GDE10AM001 CHEMICAL CLEANING TANK AGITATOR DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00007
0-WD510-EM103-
84 0 HE-00GDE10AH001 ELECTRIC HEATER DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00007
0-WD510-EM103-
85 0 XV-00GDE10AA061 CHEMICAL CLEANING TANK(SERVICE WATER) INET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00007
0-WD510-EM103-
86 0 XV-00GDM20AA001 SERVICE WATER(UF/SWRO/BWRO CIP INLET) V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00007
0-WD510-EM103-
87 0 00GDF70AP001 BWRO HIGH PRESS. PUMP A DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00007
0-WD510-EM103-
88 0 XV-00GDF60AA061 BWRO FEED PUMP DISCH. V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00007
0-WD510-EM103-
89 0 XV-00GDF80AA061 BUFFER TANK INET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00008
0-WD510-EM103-
90 0 XV-00GDF80AA062 BWRO UNIT "A" DRAIN V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00008
0-WD510-EM103-
91 0 00GDF71AP001 BWRO HIGH PRESS. PUMP B DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00008
0-WD510-EM103-
92 0 XV-00GDF61AA061 BWRO FEED PUMP DISCH. V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00008
0-WD510-EM103-
93 0 XV-00GDF81AA061 BUFFER TANK INET V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00008
0-WD510-EM103-
94 0 XV-00GDF81AA062 BWRO UNIT DRAIN "B" V/V LIMIT DOII 1_OPEN DRY - - C C - DEMI HMI FILED LATER
00008
0-WD510-EM103-
95 0 00GDM20AP001 DESALINATED WATER PUMP A DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00009
0-WD510-EM103-
96 0 00GDM20AP002 DESALINATED WATER PUMP B DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00009
0-WD510-EM103-
97 0 00GDM20AP003 DESALINATED WATER PUMP C DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00009
0-WD510-EM103-
98 0 00GDN20AM001 NaOcℓ DOSING TANK AGITATOR DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
99 0 00GDN20AP001 NaOcℓ DOSING PUMP A(FOR SEA WATER INTAKE) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
100 0 00GDN20AP002 NaOcℓ DOSING PUMP B(FOR SEA WATER INTAKE) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(SEA) I/O LIST
Service : WTP(Sea water treatment system)
Signal Type : DO
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
ALARM
NO REV. TAG NO. SERVICE HMI REMARKS
LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD510-EM103-
101 0 00GDN20AP003 NaOcℓ DOSING PUMP C(FOR CEB) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
102 0 00GDN20AP004 NaOcℓ DOSING PUMP D(FOR CEB) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
103 0 00GDN30AM001 ANTISCALANT DOSING TANK AGITATOR DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
104 0 00GDN30AP001 ANTISCALANT DOSING PUMP A(SWRO MICRO FILTER INLET) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
105 0 00GDN30AP002 ANTISCALANT DOSING PUMP B(SWRO MICRO FILTER INLET) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
106 0 00GDM40AM001 ACID DOSING TANK AGITATOR DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00010
0-WD510-EM103-
107 0 00GDN40AP001 ACID DOSING PUMP A(SWRO MICRO FILTER INLET) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
108 0 00GDN40AP002 ACID DOSING PUMP B(SWRO MICRO FILTER INLET) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
109 0 00GDM10AM001 COAGULANT DOSING TANK AGITATOR DOII 1_START DRY - - C C - DEMI HMI FILED LATER
00010
0-WD510-EM103-
110 0 00GDN10AP001 COAGULANT DOSING PUMP A(D.A.F INLET) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
111 0 00GDN10AP002 COAGULANT DOSING PUMP B(D.A.F INLET) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
112 0 00GDN10AP003 COAGULANT DOSING PUMP C(D.A.F INLET) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
113 0 00GDN50AM001 SBS DOSING TANK AGITATOR DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
114 0 00GDN50AP001 SBS DOSING PUMP A(SWRO INLET/NEUT.PIT) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
115 0 00GDN50AP002 SBS DOSING PUMP B(SWRO INLET/NEUT.PIT) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010
0-WD510-EM103-
116 0 00GDN50AP003 SBS DOSING PUMP C(SWRO INLET/NEUT.PIT) DOII 1_START DRY - - C C - DEMI HMI MCC LATER
00010

117 0 4.16KV SWITCH GEAR TRANSFORMER INCOMMING DOII 1_CLOSE DRY - - C C - DEMI HMI FILED LATER

118 0 4.16KV SWITCH GEAR TRANSFORMER INCOMMING DOII 1_TRIP DRY - - C C - DEMI HMI FILED LATER

119 0 480KV SWITCH GEAR TRANSFORMER OUTGOING DOII 1_CLOSE DRY - - C C - DEMI HMI FILED LATER

120 0 480KV SWITCH GEAR TRANSFORMER OUTGOING DOII 1_TRIP DRY - - C C - DEMI HMI FILED LATER

121 0 DESAL SYSTEM DESAL REMOTE DOII 1_TREMOTE DRY - - C C C DCS FILED LATER

122 0 DESAL SYSTEM DESAL FAULT DOII 1_TRIP DRY - - C C C DCS FILED LATER
VIDEO LINK

F.O FDF FDF F.O


CON. W/HUB CON. W/HUB

FDF FDF

MEDIA MEDIA
FDF FDF
CONVERTER CONVERTER

MEDIA MEDIA
FDF FDF
CONVERTER CONVERTER

VIDEO LINK
INDEX

1. LEGEND

2. ABBREVIATION

3. INPUT OUTPUT SUMMARY LIST

4. INPUT OUTPUT LIST


DCS I/O LIST
PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECT

1. RULE FOR FILLING IN OF THE COLUMNS

REFERENCE DRWING
INPUT/OUTPUT SIGNAL ENGINEERING DATA FUNCTION ALARM
LOCATION
NO. TAG NO. SERVICE LOGIC/LOOP REMARK
LOOP FROM/TO P&ID
I/O SIGNAL RANGE UNIT DCS LCP OTHER SET DWG.
POWER
NOTE1 NOTE2 NOTE3 NOTE4 NOTE5 NOTE6 NOTE7 NOTE8 NOTE9 NOTE9 NOTE9 NOTE10 NOTE11 NOTE12 NOTE13

NOTE1 : SERIAL NO.


NOTE2 : TAG NO.
NOTE3 : DESCRIPTION OF SERVICE
NOTE4 : INPUT/OUTPUT OF MODULE (AI, AO, DI, DOI, DOII, DOIII, PI)
NOTE5 : KIND OR ELEMENT OF SIGNAL (4-20mA, 1-5V, RTD, T/C, PI/O, D/L, S/W(1=LOW))
NOTE6 : POWER SOURCE (INT. : INTERNAL(24V), EXT.: EXTERNAL(24V), DRY : DRY Contact, 24V , 120V AC
NOTE7 : ENGINEERING RANGE OF SIGNAL
NOTE8 : ENGINEERING UNIT OF SIGNAL (mmH2O, bar, 'C, %, m3/hr, T/hr, Nm3/hr, mmHg, mmHgV, mm/s, rpm, pH, ppb)
NOTE9 : FUNCTIONS IN THE SYSTEM (A, C, I, SOE)
NOTE10: LOCATION OF SOURCE OF SIGNAL (DCS, MarkVIe, SWGR, LOCAL, MCC, LCP, etc)
NOTE11: ALARM SET (HH/H/L/LL)
NOTE12: REFERENCE DRAWING NO. OF LOGIC/LOOP DIAGRAM
NOTE13: REFERENCE DRAWING NO. OF P&ID

2. ABBREVIATIONS

PI-DCS: PLANT DISTRIBUTED CONTROL SYSTEM (FOR BOP) A: ALARM TCP : TURBINE CONTROL PANEL (GE)
PII-DCS: PLANT DISTRIBUTED CONTROL SYSTEM (FOR HRSG) C: CONTROL ESP : EMERGENCY SHUT-DOWN PUSH BUTTON
S-DCS: S/T DISTRIBUTED CONTROL SYSTEM (GE-MarkVIe) I: INDICATION
AI: ANALOG INPUT SOE: SEQUENCE OF EVENT 120V : AC 120V UPS
AO: ANALOG OUTPUT LOCAL: LOCAL INSTRUMENT DRY : DRY CONTACT (DC24V)
DI: DISCRETE INPUT VALVE: VALVE ACTUATOR
DOI: DISCRETE OUTPUT(SOLENOID VALVE, with AC120V) MP: MARSHALLING PANEL
DOII: DISCRETE OUTPUT(SWGR, MCC, DRIVE (Dry contact)) IRP : INTERPOSING RELAY PANEL
PI: PULSE INPUT L/C: 480V LOAD CENTER
RTD: RESISTANCE TEMPERATURE DETECTOR MCC: 480V MOTOR CONTROL CENTER
T/C: THERMOCOUPLE (Type K) SWGR R-I/O : SWITCH GEAR REMOTE INPUT/OUTPUT CABINET
D/L: DATA LINK HRSG R-I/O : HRSG REMOTE INPUT/OUTPUT CABINET
S/W: SOFTWARE LOGIC BOP R-I/O : BOP SYSTEM REMOTE INPUT/OUTPUT CABINET
GPP : GENERATOR PROTECTION PANEL (GE)

DAEWOO ENGINEERING COMPANY


DCS I/O LIST
PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECT

3. KKS NUMBERING STRUCTURE DEFINITION

TOTAL PLANT
SYSTEM CODE (LEVEL 1)
SEQUENCE UNIT CODE (SERIAL NO.)
EQUIPMENT UNIT CODE (LEVEL 2)
COMPONENT CODE (SERIAL NO.)
SIGNAL CODE (LEVEL 3)
COMPONENT CODE FOR SIGNAL (SERIAL NO.)

NOTE)
1) LEVEL 0,1 AND 2 SHALL BE REFER TO PROCEDURE FOR PLANT IDENTIFICATION (KKS)
2) LEVEL 3 SHALL BE REFER TO ITEM NO. 13 (KKS CODE APPLICATION FOR LEVEL 3)
EX) 01 ENA 02 AA 201 XB 01 (MOV OPENED STATUS)

4. KKS CODE APPLICATION FOR LEVEL 3

1) SWGR/MCC FOR PUMP/FAN


(1) STATUS FEED BACK
- RUNNING / ON STATUS : nnaaannaannnXB01
- STOPPED / OFF STATUS : nnaaannaannnXB02
- RUNNING (LOW) : nnaaannaannnXB03
- REMOTE (LOCAL) : nnaaannaannnXB27
- FAULT : nnaaannaannnXB28

(2) LOCAL SWITCH BOX for MCC/SWGR ONLY


- START : nnaaannaannnXB11
- STOP : nnaaannaannnXB12
- LSB REMOTE SELECTED : nnaaannaannnXG11
(3) AUTO (DCS) COMMAND
- START / ON (or Start/Stop, On/Off) : nnaaannaaaYB01
- STOP / OFF : nnaaannaaaYB02
- START (LOW) : nnaaannaaaYB03

DAEWOO ENGINEERING COMPANY


DCS I/O LIST
PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECT

2) ON/OFF, INCHING DRIVE - SOV or MOV


(1) STATUS FEED BACK
- POSITION TRANSMITTER - MOV only : nnaaannaannnXQ01
- POSITION OPEN STATUS : nnaaannaannnXB01
- POSITION CLOSE STATUS : nnaaannaannnXB02
- REMOTE / LOCAL - MOV only : nnaaannaannnXB03
- TORQUE OPEN STATUS (MOV SHUT-OFF) : nnaaannaannnXB04
- TORQUE CLOSE STATUS(MOV SHUT-OFF) : nnaaannaannnXB05
- FAULT - MOV only : nnaaannaannnXB28
(2) AUTO (DCS) COMMAND
- OPEN COMMAND : nnaaannaannnYB01
- CLOSE COMMAND : nnaaannaannnYB02

3) MOV (MODULATING DRIVE)


(1) STATUS FEED BACK
- POSITION TRANSMITTER : nnaaannaannnXQ01
- POSITION OPEN STATUS : nnaaannaannnXB01
- POSITION CLOSE STATUS : nnaaannaannnXB02
- REMOTE / LOCAL : nnaaannaannnXB03
- FAULT : nnaaannaannnXB28
(2) AUTO (DCS) COMMAND
- ANALOG OUTPUT COMMAND : nnaaannaannnYQ01

4) PNEMATIC CONTROL VALVE


(1) STATUS FEED BACK
- POSITION TRANSMITTER : nnaaannaannnXQ01
- POSITION OPEN STATUS : nnaaannaannnXB01
- POSITION CLOSE STATUS : nnaaannaannnXB02
(2) AUTO (DCS) COMMAND
- ANALOG OUTPUT COMMAND : nnaaannaannnYQ01

5) PACKAGE CONTROL
(1) STATUS FEED BACK
- RUNNING / ON : nnaaannaannnXJ01
- STOPPED / OFF : nnaaannaannnXJ02
- LOCAL / REMOTE : nnaaannaannnXJ03
- COMMON ALARM (If any) : nnaaannaannnXJ28
- FAULT : nnaaannaannnXJ29
- CONTACT from PACKAGE SYSTEM (If any) : nnaaannaannnXJ10 ~ XJ20

DAEWOO ENGINEERING COMPANY


DCS I/O LIST
PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECT

(2) SIGNAL TRANSMITTION OF FIELD INSTRUMENT FROM LCP TO DCS


- FIELD INSTRUMENT (Contact via LCP) : nnaaannaannnXJ01 ~ 40
- CLOSE COMMAND (4~20mA via LCP) : nnaaannaannnXJ40 ~ 90
(3) SIGNAL TRANSMITTION OF FIELD INSTRUMENT DCS TO LCP
- FIELD INSTRUMENT (Contact via LCP) : nnaaannaannnYJ01 ~ 40
- CLOSE COMMAND (4~20mA via LCP) : nnaaannaannnYJ40 ~ 90
(4) GROUP AUTO (DCS) COMMAND (TO PACKAGE SYSTEM)
- START / ON : nnaaannaannnYB01
- STOP / OFF : nnaaannaannnYB02
(4) INDIVIDUAL DRIVE CONTROL FOR PACAKGE SYSTEM FROM DCS
- BASE ON LEVEL 3

6) SET POINT
THIS KKS NUMBER SHOWS THE SOFTWARE. THESE VALUE ARE ANALOG INPUT FOR ALARM OR INTERLOCK PURPOSE.
HH : HIGH-HIGH ALARMING XH03
H : HIGH ALARMING XH01
L : LOW ALARMING XH02
LL : LOW-LOW ALARMING XH04

5. NOTES

1) DETAILD DESIGN OF THE DCS I/O ASSIGNMENT AND CONTROLLER ASSIGNMENT SHALL BE PROVIDED BY DCS VENDOR.

2) MISSING DATA LIKE TAG NO, REFERENCE DRAWING FOR INPUT / OUTPUT POINT, SET POINT WILL BE FILLED ACCORDING TO DESIGN DEVELOPMENT

DAEWOO ENGINEERING COMPANY


ABBREVIATION
PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECTProject

ABBREVIATION SERVICE DESCRIPTION ABBREVIATION SERVICE DESCRIPTION ABBREVIATION SERVICE DESCRIPTION

AUX AUXILIARY D/P DIFFERENCE PRESSURE S/O SHUT-OFF

BFP BOILER FEED WATER PUMP DE DRIVE END S/V SOLENOID VALVE

BLDG BUILDING DISCH DISCHARGE SC SPECIFIC CONDUCTIVITY

BLWR BLOWER DS DE-SUPERHEATER STG STEAM TURBINE GENERATOR

BP BYPASS FWP FEED WATER PUMP STM STEAM

BRG BEARING GT GAS TURBINE TBN TURBINE

blank H HIGH TEMP. TEMPERATURE

C/V CONTROL VALVE HDR HEADER TR TRANSFORMER

CC CATION CONDUCTIVITY HP HIGH PRESSURE VIB VIBRATION

CCCW COLSED CYCLE COOLING WATER HRH HOT REHEAT STEAM VLV VALVE

CCW CLOSED COOLING WATER HRSG#1 DCS HRSG#1 DISTRIBUTED CONTROL SYSTEM WTR WATER

CCWP CLOSED COOLING WATER PUMP HRSG#2 DCS HRSG#2 DISTRIBUTED CONTROL SYSTEM EQ EQUALIZING

CLG COOLING HRSG#3 DCS HRSG#3 DISTRIBUTED CONTROL SYSTEM BFW BOILER FEED WATER

CLR COOLER LP LOW PRESSURE HTR HEATER

CMD COMMEND LS LEVEL SWITCH SWP SERVICE WATER PUMP

COM COMMON MOV MOTOR OPERATED VALVE

COMPR COMPRESSOR MP MAIN STEAM PRESSURE

COND CONDENSER NDE NON DRIVE END

CRH COLD REHEAT STEAM P-DCS PLANT(BOP) DISTRIBUTED CONTROL SYSTEM

CTRL CONTROL P/P PUMP

CW COOLING WATER PPC POWER CONTROL CENTER

D.W DEMI WATER PRESS PRESSURE

DAEWOO ENGINEERING COMPANY


PROJECT : CHILCAUNO POWER STATION ADD-ON PROJECT DCS IN/OUT SUMMARY LIST

SIGNAL COMM. DCS


PCS
REV AREA SERVICE PCS TOTAL POINTS GRAPHIC REMARK
LOCATION PCS DOI PCS DOII DCS DOIII
AI RTD AO T/C(K) DI PI SOE (w/Others) PAGE
(SOV.T/SW) (IRP) (24V DC)

DEMI.WAT
0 WTP (Supplied by DAEWOO ENGINEERING at DEMI. WT 33 - 2 - 0 - - - 0 - 35 LATER
ER

합 계 33 2 0 0 0 35

NOTES

1. The IRP shall be installed in DCS system panels.

2. DO to MV SWGR, LV SWGR, MCC AND STG CONTROL SYSTEM ; Buffer Relay shall be applied.

3. DI from STG CONTROL SYSTEM ; Buffer Relay shall be applied. SIEMENS shall supply DC 125V loop power.

4. Total Input & Output signal quantity can be changed in detail design development.

5. Communication Points will be changed according to Vendor Prints.


6. This document is based on BOP P&ID Rev.0 and Vendor prints (HRSG, ACC, Bypass stack etc.)

modbus@dweng.co.kr
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : AI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD913-EM103-
1 0 LIT-03GCL10CL101 DESALINATED WATER STORAGE TANK LEVEL TRANS. AI 4~20mA EXT 0~15,000 mmH20 I.C.A - I.A FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
2 0 FIT-03GCL20CF101 DEMI. FEED WATER PUMP A/B OUTLET FLOW(TURBINE) AI 4~20mA INT 0~1250 mmH20 I.C - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
3 0 AIT-03GCL20CQ101 DEMI. FEED WATER PUMP A/B OUTLET (COND) AI 4~20mA INT 0~500 ㎲/㎝ I.C - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
4 0 LIT-03GKB10CL101 SERVICE WATER TANK LEVEL TRANS. AI 4~20mA EXT 0~3,500 mm I.C.A - I.A FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
5 0 FIT-03GCF30CF101 DWRO UNIT "A" OUTLET FLOW(TURBINE),EDI UNIT "A" AI 4~20mA INT 3~30 ㎥/Hr I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
6 0 PIT-03GCF10CP101 DWRO HIGH PRESS. PUMP A INLET PRESS.TRANS AI 4~20mA EXT 0~6 Bar I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
7 0 PIT-03GCL20CP101 DEMI. FEED WATER PUMP A/B OUTLET PRESS.TRANS. AI 4~20mA EXT 0~6 Bar I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
8 0 PIT-03GCF20CP101 DWRO UNIT "A" OUTLET PRESS.TRANS. AI 4~20mA EXT 0~35 Bar I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
9 0 PIT-03GCF30CP101 DWRO UNIT "A" OUTLET PRESS.TRANS. AI 4~20mA EXT 0~35 Bar I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
10 0 03GCF20AP001 DWRO HIGH PRESS. PUMP A (HZ) AI 4~20mA INT 0~60 Hz I - I MCC DEMI PLC HOLD LATER
00002
0-WD913-EM103-
11 0 DWRO HIGH PRESS. PUMP A (AMPARE) AI 4~20mA INT HOLD A I - I MCC DEMI PLC HOLD LATER
00002
0-WD913-EM103-
12 0 FIT-03GCF31CF102 DWRO UNIT "B" OUTLET FLOW(TURBINE),EDI UNIT "A" AI 4~20mA INT 3~30 ㎥/Hr I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
13 0 PIT-03GCF11CP101 DWRO HIGH PRESS. PUMP B INLET PRESS.TRANS AI 4~20mA EXT 0~6 Bar I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
14 0 PIT-03GCL21CP101 DEMI. FEED WATER PUMP A/B OUTLET PRESS.TRANS. AI 4~20mA EXT HOLD HOLD I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
15 0 PIT-03GCF21CP101 DWRO UNIT "B" OUTLET PRESS.TRANS. AI 4~20mA EXT 0~35 Bar I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
16 0 PIT-03GCF31CP101 DWRO UNIT "B" OUTLET PRESS.TRANS. AI 4~20mA EXT 0~30 Bar I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
17 0 03GCF21AP001 DWRO HIGH PRESS. PUMP B (HZ) AI 4~20mA INT 0~60 Hz I - I MCC DEMI PLC HOLD LATER
00002
0-WD913-EM103-
18 0 DWRO HIGH PRESS. PUMP B (AMPARE) AI 4~20mA INT HOLD A I - I MCC DEMI PLC HOLD LATER
00002
0-WD913-EM103-
19 0 AIT-03GCF40CQ101 DWRO-A PERMEATE CONDUCTIVITY (COND) AI 4~20mA INT 0~500 pH I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
20 0 AIT-03GCF40CQ102 EDI UNIT "A" OUTLET CONDUCTIVITY (COND) AI 4~20mA INT 0~20 mΩ I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
21 0 PIT-03GCF40CP101 EDI UNIT "A" DIFF.PRESS.TRANS. AI 4~20mA EXT 0~4 Bar I.A - I.A SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
22 0 AIT-03GCF41CQ101 DWRO-B PERMEATE CONDUCTIVITY (COND) AI 4~20mA INT 0~500 ㎲/㎝ I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
23 0 AIT-03GCF41CQ102 EDI UNIT "B" OUTLET CONDUCTIVITY (COND) AI 4~20mA INT 0~20 mΩ I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
24 0 PIT-03GCF41CP101 EDI UNIT "B" DIFF.PRESS.TRANS. AI 4~20mA EXT 0~4 Bar I.A - I.A SKID-B023 DEMI PLC HOLD LATER
00003
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : AI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD913-EM103-
25 0 FIT-03GCF40CF103 EDI UNIT "A/B" OUTLET FLOW(TURBINE) AI 4~20mA INT 4~40 ㎥/Hr I - I FILED DEMI PLC HOLD LATER
00003
0-WD913-EM103-
26 0 LIT-03GCL30CL101 DEMI. WATER STORAGE TANK LEVEL TRANS. AI 4~20mA EXT 0~15,000 mmH20 I.A - I.A FILED DEMI PLC HOLD LATER
00004
0-WD913-EM103-
27 0 FIT-03GRR10CF101 WASTEWATER PUMP A/B DISCH. FLOW(MAG.) AI 4~20mA INT 0~20 m3/h I - I FILED DEMI PLC HOLD LATER
00005
0-WD913-EM103-
28 0 AIT-03GRR20CQ101 PH AJUSTMENT TANK (PH) AI 4~20mA INT 3 pH I - I FILED DEMI PLC HOLD LATER
00006
0-WD913-EM103-
29 0 LIT-03GRL10CL101 IRRIGATION WATER STORAGE TANK LEVEL TRANS. AI 4~20mA EXT 0~10,000 mmH20 I.A - I.A FILED DEMI PLC HOLD LATER
00006
0-WD913-EM103-
30 0 PDIT-00GMA34CP001 CHILER INLET FILTER DP A AI 4~20mA EXT 0~30 Bar I.A - I.A FILED DEMI PLC HOLD LATER
00006
0-WD913-EM103-
31 0 PDIT-00GMA34CP002 CHILER INLET FILTER DP B AI 4~20mA EXT 0~30 Bar I.A - I.A FILED DEMI PLC HOLD LATER
00006
0-WD913-EM103-
32 0 TIT-00GMA34CT101 COOLING TOWR INLET AI 4~20mA EXT 0~100 ℃ I.A - I.A FILED DEMI PLC HOLD LATER
00006
0-WD913-EM103-
33 0 TIT-00GMA34CT102 COOLING TOWR OUTLET AI 4~20mA EXT 0~100 ℃ I.A - I.A FILED DEMI PLC HOLD LATER
00006

34 0

35 0

36 0

37

38 - - - - - - - -
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : AO
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE LOOP HMI REMARKS
. SET LOGIC/LOOP
I/O SIGNAL POWE RANGE UNIT DEMI SEA DCS FROM TO P & ID
DWG
R WTP WTP
0-WD913-EM103-
1 0 03GCF20AP001 DWRO HIGH PRESS. PUMP A (INV.PI) AO 4~20mA INT 0~100 % C - - DEMI PLC MCC LATER
00002
0-WD913-EM103-
2 0 03GCF21AP001 DWRO HIGH PRESS. PUMP B (INV.PI) AO 4~20mA INT 0~100 % C - - DEMI PLC MCC LATER
00002

3 0

4 0

5 0

6 0

7 0

8 0

9 0

10 0

11 0

12 0

13 0

3
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD913-EM103-
1 0 XV-00GDM20AA061DESALINATED WATER STORAGE TANK INLET V/V LIMIT DI 1_ OPEN DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
2 0 DI 1_ CLOSE DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
3 0 LS-03GCL10CL201 DESALINATED WATER STORAGE TANK LEVEL SWITCH DI 1_ H DRY - - I.C.A - I.A FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
4 0 DI 1_ L DRY - - I.C.A - I.A FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
5 0 DI 1_ LLAL DRY - - I.C.A - I.A FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
6 0 FIT-03GCL20CF101 DEMI. FEED WATER PUMP A/B OUTLET FLOW(TURBINE) DI 1_PULSE DRY - - I.C - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
7 0 03GCL20AP001 DEMI. FEED WATER PUMP A DI 1_ START DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD913-EM103-
8 0 DI 1_ FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD913-EM103-
9 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD913-EM103-
10 0 03GCL20AP002 DEMI. FEED WATER PUMP B DI 1_ START DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD913-EM103-
11 0 DI 1_ FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD913-EM103-
12 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD913-EM103-
13 0 XV-00GDM20AA062SERVICE WATER TANK INLET V/V LIMIT DI 1_OPEN DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
14 0 DI 1_CLOSE DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
15 0 03GHE20AP001 SERVICE WATER PUMP A DI 1_ START DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
16 0 DI 1_ FAULT DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
17 0 DI 1_REMOTE DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
18 0 03GHE20AP002 SERVICE WATER PUMP B DI 1_ START DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
19 0 DI 1_ FAULT DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
20 0 DI 1_REMOTE DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD913-EM103-
21 0 PS-03GCF10CP201 DWRO HIGH PRESS.PUMP "A" INLET PRESS.SWITCH DI 1_PAL DRY - - I.C.A - I.A FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
22 0 FIT-03GCF30CF101 DWRO UNIT "A" OUTLET FLOW(TURBINE),EDI UNIT "A" DI 1_PULSE DRY - - I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
23 0 03GCF20AP001 DWRO HIGH PRESS. PUMP A DI 1_ START DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD913-EM103-
24 0 DI 1_ FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00002
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD913-EM103-
25 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD913-EM103-
26 0 XV-03GCF10AA061 DWRO MICRO FILTER INLET V/V LIMIT DI 1_OPEN DRY - - I - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
27 0 DI 1_CLOSE DRY - - I - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
28 0 PS-03GCF11CP101 DWRO HIGH PRESS.PUMP "B" INLET PRESS.SWITCH DI 1_PAL DRY - - I.C.A - I.A FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
29 0 FIT-03GCF31CF102 DWRO UNIT "B" OUTLET FLOW(TURBINE),EDI UNIT "A" DI 1_PULSE DRY - - I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
30 0 03GCF21AP002 DWRO HIGH PRESS. PUMP B DI 1_ START DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD913-EM103-
31 0 DI 1_ FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD913-EM103-
32 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD913-EM103-
33 0 XV-03GCF11AA061 DWRO MICRO FILTER INLET V/V LIMIT DI 1_OPEN DRY - - I - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
34 0 DI 1_CLOSE DRY - - I - I FILED DEMI PLC HOLD LATER
00002
0-WD913-EM103-
35 0 FIS-03GCF40CF201 EDI MODULE A-#1 PRODUCT FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
36 0 FIS-03GCF40CF202 EDI MODULE A-#1 CONCENTRATE FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
37 0 FIS-03GCF40CF203 EDI MODULE A-#2 PRODUCT FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
38 0 FIS-03GCF40CF204 EDI MODULE A-#2 CONCENTRATE FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
39 0 FIS-03GCF40CF205 EDI MODULE A-#3 PRODUCT FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
40 0 FIS-03GCF40CF206 EDI MODULE A-#3 CONCENTRATE FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
41 0 FIS-03GCF40CF207 EDI MODULE A-#4 PRODUCT FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
42 0 FIS-03GCF40CF208 EDI MODULE A-#4 CONCENTRATE FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
43 0 FIS-03GCF40CF209 EDI MODULE A-#5 PRODUCT FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
44 0 FIS-03GCF40CF210 EDI MODULE A-#5 CONCENTRATE FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
45 0 FIS-03GCF40CF221 EDI UNIT "A" CONCENTRATION FLOW SWITCH DI 1_FAULT DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
46 0 EDI UNIT "A" ALARM DI 1_RUN DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
47 0 EDI MODULE A-#1 DI 1_RUN DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
48 0 EDI MODULE A-#2 DI 1_RUN DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD913-EM103-
49 0 EDI MODULE A-#3 DI 1_RUN DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
50 0 EDI MODULE A-#4 DI 1_RUN DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
51 0 EDI MODULE A-#5 DI 1_RUN DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
52 0 PS-03GCF40CP201 EDI UNIT "A" INLET PRESS.SWITCH DI 1_PAL DRY - - I.A - I.A SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
53 0 XV-03GCF40AA061 EDI UNIT "A" INLET V/V LIMIT SWITCH(SERVICE) DI 1_OPEN DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
54 0 DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
55 0 XV-03GCF40AA062 EDI UNIT "A" INLET V/V LIMIT SWITCH(RETURN) DI 1_OPEN DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
56 0 DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
57 0 XV-03GCF40AA063 EDI UNIT "A" OUTLET V/V LIMIT SWITCH(SERVICE) DI 1_OPEN DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
58 0 DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
59 0 XV-03GCF40AA064 EDI UNIT "A" OUTLET V/V LIMIT SWITCH(RETURN) DI 1_OPEN DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
60 0 DI 1_CLOSE DRY - - I - I SKID-B022 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
61 0 FIS-03GCF40CF211 EDI MODULE B-#1 PRODUCT FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
62 0 FIS-03GCF40CF212 EDI MODULE B-#1 CONCENTRATE FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
63 0 FIS-03GCF40CF213 EDI MODULE B-#2 PRODUCT FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
64 0 FIS-03GCF40CF214 EDI MODULE B-#2 CONCENTRATE FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
65 0 FIS-03GCF40CF215 EDI MODULE B-#3 PRODUCT FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
66 0 FIS-03GCF40CF216 EDI MODULE B-#3 CONCENTRATE FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
67 0 FIS-03GCF40CF217 EDI MODULE B-#4 PRODUCT FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
68 0 FIS-03GCF40CF218 EDI MODULE B-#4 CONCENTRATE FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
69 0 FIS-03GCF40CF219 EDI MODULE B-#5 PRODUCT FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
70 0 FIS-03GCF40CF220 EDI MODULE B-#5 CONCENTRATE FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
71 0 FIS-03GCF40CF222 EDI UNIT "B" CONCENTRATION FLOW SWITCH DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
72 0 EDI UNIT "B" ALARM DI 1_FAULT DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD913-EM103-
73 0 EDI MODULE B-#1 DI 1_RUN DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
74 0 EDI MODULE B-#2 DI 1_RUN DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
75 0 EDI MODULE B-#3 DI 1_RUN DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
76 0 EDI MODULE B-#4 DI 1_RUN DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
77 0 EDI MODULE B-#5 DI 1_RUN DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
78 0 PS-03GCF41CP202 EDI UNIT "B" INLET PRESS.SWITCH DI 1_PAL DRY - - I.A - I.A SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
79 0 XV-00GCF41AA061 EDI UNIT "B" INLET V/V LIMIT SWITCH(SERVICE) DI 1_OPEN DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
80 0 DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
81 0 XV-00GCF41AA062 EDI UNIT "B" INLET V/V LIMIT SWITCH(RETURN) DI 1_OPEN DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
82 0 DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
83 0 XV-00GCF41AA063 EDI UNIT "B" OUTLET V/V LIMIT SWITCH(SERVICE) DI 1_OPEN DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
84 0 DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
85 0 XV-00GCF41AA064 EDI UNIT "B" OUTLET V/V LIMIT SWITCH(RETURN) DI 1_OPEN DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
86 0 DI 1_CLOSE DRY - - I - I SKID-B023 DEMI PLC HOLD LATER
00003
0-WD913-EM103-
87 0 FIT-03GCF40CF103 EDI UNIT "A/B" OUTLET FLOW(TURBINE) DI 1_PULSE DRY - - I.C - I FILED DEMI PLC HOLD LATER
00003
0-WD913-EM103-
88 0 03GHC10AP001 DEMI. WATER PUMP A DI 1_START DRY - - I - I FILED DEMI PLC HOLD LATER
00003
0-WD913-EM103-
89 0 DI 1_FAULT DRY - - I - I FILED DEMI PLC HOLD LATER
00003
0-WD913-EM103-
90 0 DI 1_REMOTE DRY - - I - I FILED DEMI PLC HOLD LATER
00003
0-WD913-EM103-
91 0 03GHC10AP002 DEMI. WATER PUMP B DI 1_START DRY - - I - I FILED DEMI PLC HOLD LATER
00003
0-WD913-EM103-
92 0 DI 1_FAULT DRY - - I - I FILED DEMI PLC HOLD LATER
00003
0-WD913-EM103-
93 0 DI 1_REMOTE DRY - - I - I FILED DEMI PLC HOLD LATER
00003
0-WD913-EM103-
94 0 LS-03GCN10CL201 CIP CHEMICAL TANK LEVEL SWITCH DI 1_HH DRY - - I - I FILED DEMI PLC HOLD LATER
00004
0-WD913-EM103-
95 0 DI 1_H DRY - - I - I FILED DEMI PLC HOLD LATER
00004
0-WD913-EM103-
96 0 DI 1_L DRY - - I - I FILED DEMI PLC HOLD LATER
00004
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD913-EM103-
97 0 DI 1_LAL DRY - - I.A - I.A FILED DEMI PLC HOLD LATER
00004
0-WD913-EM103-
98 0 03GCN10CT201 CIP CHEMICAL TANK TEMP SWITCH DI 1_TEMP AL DRY - - I.A - I.A FILED DEMI PLC HOLD LATER
00004
0-WD913-EM103-
99 0 03GCN10AH001 CIP CHEMICAL TANK ELECTRIC HEATER DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
100 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
101 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
102 0 03GCN10AM001 CIP CHEMICAL TANK AGITATOR DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
103 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
104 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
105 0 03GCN20AP001 CIP FEED PUMP A DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
106 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
107 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
108 0 03GCN20AP002 CIP FEED PUMP B DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
109 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD913-EM103-
110 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00004
0-WD914-EM103-
111 0 LS-03GRK10CL201 ONLY WASTE STORAGE TANK LEVEL SWITCH DI 1_H DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD914-EM103-
112 0 DI 1_L DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD914-EM103-
113 0 DI 1_LAL DRY - - I - I FILED DEMI PLC HOLD LATER
00001
0-WD914-EM103-
114 0 03GRK20AP001 ONLY WATER TRANSFER PUMP A DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD914-EM103-
115 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD914-EM103-
116 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD914-EM103-
117 0 03GRK20AP002 ONLY WATER TRANSFER PUMP B DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD914-EM103-
118 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD914-EM103-
119 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00001
0-WD914-EM103-
120 0 MOP(SKID-D001) OIL REMOVAL PUMP DI 1_START DRY - - I - I SKID-D001 DEMI PLC HOLD LATER
00001
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD914-EM103-
121 0 DI 1_FAULT DRY - - I - I SKID-D001 DEMI PLC HOLD LATER
00001
0-WD914-EM103-
122 0 LS-03GRK30CL201 SKIMMED OIL TANK LEVEL SWITCH DI 1_HAL DRY - - I.A - I.A SKID-D001 DEMI PLC HOLD LATER
00001
0-WD914-EM103-
123 0 LS-03GRR10CL201 WASTE WATER PIT LEVEL SWITCH DI 1_H DRY - - I - I FILED DEMI PLC HOLD LATER
00002
0-WD914-EM103-
124 0 DI 1_L DRY - - I - I FILED DEMI PLC HOLD LATER
00002
0-WD914-EM103-
125 0 DI 1_LAL DRY - - I.A - I.A FILED DEMI PLC HOLD LATER
00002
0-WD914-EM103-
126 0 03GRR10AP001 WASTEWATER PUMP A DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
127 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
128 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
129 0 03GRR10AP002 WASTEWATER PUMP B DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
130 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
131 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
132 0 FIT-03GRR10CF101 WASTEWATER PUMP A/B DISCH. FLOW(MAG.) DI 1_PULSE DRY - - I.C - I FILED DEMI PLC HOLD LATER
00002
0-WD914-EM103-
133 0 LS-03GRR20CL201 PH AJUSTMENT TANK LEVEL SWTCH DI 1_H DRY - - I - I FILED DEMI PLC HOLD LATER
00002
0-WD914-EM103-
134 0 DI 1_LAL DRY - - I.A - I.A FILED DEMI PLC HOLD LATER
00002
0-WD914-EM103-
135 0 03GRR20AM001 PH ADJUSTMENT TANK AGITATOR DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
136 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
137 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
138 0 03GRR30AP001 WATER TRANSFER PUMP A DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
139 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
140 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
141 0 03GRR30AP002 WATER TRANSFER PUMP B DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
142 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
143 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
144 0 03GRL20AP001 IRRIGATION WATER PUMP A DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00002
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD914-EM103-
145 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
146 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
147 0 03GRL20AP002 IRRIGATION WATER PUMP B DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
148 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
149 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00002
0-WD914-EM103-
150 0 LS-03GRN20CL201 ACID STORAGE TANK LEVEL SWTCH DI 1_H DRY - - I - I FILED DEMI PLC HOLD LATER
00003
0-WD914-EM103-
151 0 DI 1_L DRY - - I - I FILED DEMI PLC HOLD LATER
00003
0-WD914-EM103-
152 0 DI 1_LAL DRY - - I.A - I.A FILED DEMI PLC HOLD LATER
00003
0-WD914-EM103-
153 0 03GRN20AP001 ACID INJECTION PUMP A DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
154 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
155 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
156 0 03GRN20AP002 ACID INJECTION PUMP B DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
157 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
158 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
159 0 LS-03GRN10CL201 CAUSTIC STORAGE TANK LEVEL SWTCH DI 1_H DRY - - I - I FILED DEMI PLC HOLD LATER
00003
0-WD914-EM103-
160 0 DI 1_L DRY - - I - I FILED DEMI PLC HOLD LATER
00003
0-WD914-EM103-
161 0 DI 1_LAL DRY - - I.A - I.A FILED DEMI PLC HOLD LATER
00003
0-WD914-EM103-
162 0 03GRN10AP001 CAUSTIC INJECTION PUMP A DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
163 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
164 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
165 0 03GRN10AP002 CAUSTIC INJECTION PUMP B DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
166 0 DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER
00003
0-WD914-EM103-
167 0 DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER
00003

168 0 WATER TREATMENT SYSTEM DI 1_START DRY - - I - I DCS DEMI PLC HOLD LATER -
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DI
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP

169 0 DESAL AUTO START ORDER DI 1_START DRY - - I.C - I DCS DEMI PLC HOLD LATER -

170 0 DEMI AUTO START OPDER DI 1_START DRY - - I.C - I DCS DEMI PLC HOLD LATER -

171 0 02GMA34AA041 MOV OPENED ORDER DI 1_START DRY - - I.C - I DCS DEMI PLC HOLD LATER -

172 0 MOV CLOSED ORDER DI 1_START DRY - - I.C - I DCS DEMI PLC HOLD LATER -

173 0 COOLING TOWER MOTOR-A REMOTE DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER -

174 0 COOLING TOWER MOTOR-A RUN DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER -

175 0 COOLING TOWER MOTOR-A TRIP DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER -

176 0 COOLING TOWER MOTOR-B REMOTE DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER -

177 0 COOLING TOWER MOTOR-B RUN DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER -

178 0 COOLING TOWER MOTOR-B TRIP DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER -

179 0 COOLING TOWER PUMP-A REMOTE DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER -

180 0 COOLING TOWER PUMP-A RUN DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER -

181 0 COOLING TOWER PUMP-A TRIP DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER -

182 0 COOLING TOWER PUMP-B REMOTE DI 1_REMOTE DRY - - I - I MCC DEMI PLC HOLD LATER -

183 0 COOLING TOWER PUMP-B RUN DI 1_START DRY - - I - I MCC DEMI PLC HOLD LATER -

184 0 COOLING TOWER PUMP-B TRIP DI 1_FAULT DRY - - I - I MCC DEMI PLC HOLD LATER -
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DO
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD913-EM103-
1 0 XV-00GDM20AA061 DESALINATED WATER STORAGE TANK INLET V/V LIMIT DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00001
0-WD913-EM103-
2 0 XV-00GDM20AA062 DESALINATED WATER STORAGE TANK INLET V/V LIMIT DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00001
0-WD913-EM103-
3 0 03GCL20AP001 DEMI. FEED WATER PUMP A DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00001
0-WD913-EM103-
4 0 03GCL20AP002 DEMI. FEED WATER PUMP B DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00001
0-WD913-EM103-
5 0 03GHE20AP001 SERVICE WATER PUMP A DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00001
0-WD913-EM103-
6 0 03GHE20AP002 SERVICE WATER PUMP B DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00001
0-WD913-EM103-
7 0 03GCF20AP001 DWRO HIGH PRESS. PUMP A DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00002
0-WD913-EM103-
8 0 XV-03GCF10AA061 DWRO MICRO FILTER INLET V/V LIMIT DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00002
0-WD913-EM103-
9 0 03GCF21AP001 DWRO HIGH PRESS. PUMP B DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00002
0-WD913-EM103-
10 0 XV-03GCF11AA061 DWRO MICRO FILTER INLET V/V LIMIT DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00002
0-WD913-EM103-
11 0 MOP(SKID-B022) EDI UNIT "A" DOII 1_START DRY - - C - - DEMI PLC SKID-B002 - LATER
00003
0-WD913-EM103-
12 0 EDI UNIT "A" DOII 1_EMG.STOP DRY - - C - - DEMI PLC SKID-B002 - LATER
00003
0-WD913-EM103-
13 0 XV-03GCF40AA061 EDI UNIT "A" INLET V/V (SERVICE) DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00003
0-WD913-EM103-
14 0 XV-03GCF40AA062 EDI UNIT "A" INLET V/V (RETURN) DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00003
0-WD913-EM103-
15 0 XV-03GCF40AA063 EDI UNIT "A" OUTLET V/V (SERVICE) DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00003
0-WD913-EM103-
16 0 XV-03GCF40AA064 EDI UNIT "A" OUTLET V/V (RETURN) DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00003
0-WD913-EM103-
17 0 MOP(SKID-B023) EDI UNIT "B" DOII 1_START DRY - - C - - DEMI PLC SKID-B023 - LATER
00003
0-WD913-EM103-
18 0 EDI UNIT "B" DOII 1_EMG.STOP DRY - - C - - DEMI PLC SKID-B023 - LATER
00003
0-WD913-EM103-
19 0 XV-00GCF41AA061 EDI UNIT "B" INLET V/V (SERVICE) DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00003
0-WD913-EM103-
20 0 XV-00GCF41AA062 EDI UNIT "B" INLET V/V (RETURN) DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00003
0-WD913-EM103-
21 0 XV-00GCF41AA063 EDI UNIT "B" OUTLET V/V (SERVICE) DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00003
0-WD913-EM103-
22 0 XV-00GCF41AA064 EDI UNIT "B" OUTLET V/V (RETURN) DOII 1_OPEN DRY - - C - - DEMI PLC FILED - LATER
00003

23 0 03GHC10AP001 DEMI. WATER PUMP A DOII 1_START DRY - - C - - DEMI PLC MCC - LATER -

24 0 03GHC10AP002 DEMI. WATER PUMP B DOII 1_START DRY - - C - - DEMI PLC MCC - LATER -
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DO
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP
0-WD913-EM103-
25 0 03GCN10AH001 CIP CHEMICAL TANK ELECTRIC HEATER DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00004
0-WD913-EM103-
26 0 03GCN10AM001 CIP CHEMICAL TANK AGITATOR DOII 1_START DRY - - C - - DEMI PLC FILED - LATER
00004
0-WD913-EM103-
27 0 03GCN20AP001 CIP FEED PUMP A DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00004
0-WD913-EM103-
28 0 03GCN20AP002 CIP FEED PUMP B DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00004
0-WD913-EM103-
29 0 03GRK20AP001 OILY WATER TRANSFER PUMP A DOII 1_START DRY - - C - - DEMI PLC FILED - LATER
00005
0-WD913-EM103-
30 0 03GRK20AP002 OILY WATER TRANSFER PUMP B DOII 1_START DRY - - C - - DEMI PLC FILED - LATER
00005
0-WD913-EM103-
31 0 03GRR10AP001 WASTEWATER PUMP A DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00006
0-WD913-EM103-
32 0 03GRR10AP002 WASTEWATER PUMP B DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00006
0-WD913-EM103-
33 0 03GRR20AM001 PH ADJUSTMENT TANK AGITATOR DOII 1_START DRY - - C - - DEMI PLC FILED - LATER
00006
0-WD913-EM103-
34 0 03GRR30AP001 WATER TRANSFER PUMP A DOII 1_START DRY - - C - - DEMI PLC FILED - LATER
00006
0-WD913-EM103-
35 0 03GRR30AP002 WATER TRANSFER PUMP B DOII 1_START DRY - - C - - DEMI PLC FILED - LATER
00006
0-WD913-EM103-
36 0 03GRL20AP001 IRRIGATION WATER PUMP A DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00006
0-WD913-EM103-
37 0 03GRL20AP002 IRRIGATION WATER PUMP B DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00006
0-WD913-EM103-
38 0 03GRN20AP001 ACID INJECTION PUMP A DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00007
0-WD913-EM103-
39 0 03GRN20AP002 ACID INJECTION PUMP B DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00007
0-WD913-EM103-
40 0 03GRN10AP001 CAUSTIC INJECTION PUMP A DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00007
0-WD913-EM103-
41 0 03GRN10AP002 CAUSTIC INJECTION PUMP B DOII 1_START DRY - - C - - DEMI PLC MCC - LATER
00007

42 0 WATER TREATMENT SYSTEM FOR DESAL DOII 1_REMOTE DRY - - C - - DEMI PLC DCS - LATER -

43 0 WATER TREATMENT SYSTEM FOR DESAL DOII 1_TOTAL AL DRY - - C - - DEMI PLC DCS - LATER -

44 0 WATER TREATMENT SYSTEM FOR DEMI DOII 1_REMOTE DRY - - C - - DEMI PLC DCS - LATER -

45 0 WATER TREATMENT SYSTEM FOR DEMI DOII 1_TOTAL AL DRY - - C - - DEMI PLC DCS - LATER -

46 0 COOLING TOWER MOTOR-A DOII 1_START DRY - - C - - DEMI PLC UCC - LATER -

47 0 COOLING TOWER MOTOR-B DOII 1_START DRY - - C - - DEMI PLC UCC - LATER -

48 0 COOLING TOWER PUMP-A DOII 1_START DRY - - C - - DEMI PLC UCC - LATER -
Project : CHILCAUNO POWER STATION ADD-ON PROJECT HMI(DEMI) I/O LIST
Service : WTP(Demineralization Plant system)
Signal Type : DO
INPUT/OUTPUT ENGINEERING
FUNCTION LOCATION REFERENCE DWG
SIGNAL DATA
REV ALARM
NO TAG NO. SERVICE HMI REMARKS
. LOOP SET LOGIC/LOOP
I/O SIGNAL RANGE UNIT DEMI SEA DCS FROM TO P & ID
POWER DWG
WTP WTP

49 0 COOLING TOWER PUMP-B DOII 1_START DRY - - C - - DEMI PLC UCC - LATER -

50 0 DEMI SYSTEM DEMI REMOTE DOII 1_REMOTE DRY - - C - C DEMI PLC DCS - LATER -

51 0 DEMI SYSTEM DEMI FAULT DOII 1_FAULT DRY - - C - C DEMI PLC DCS - LATER -
CHILCAUNO POWER STATION ADD - ON PROJECT
WATER TREATMENT SYSTEM
PLC PANEL
For DEMI & INDUSTRIAL WATER

April 19, 2012


VIDEO LINK

F.O FDF FDF F.O


CON. W/HUB CON. W/HUB

FDF FDF

MEDIA MEDIA
FDF FDF
CONVERTER CONVERTER

MEDIA MEDIA
FDF FDF
CONVERTER CONVERTER

VIDEO LINK
PROJECT : CHILCA UNO POWER STATION ADD-ON PROJECT(Water Treatment System)/HMI HARD WARE

No. Proprietary Name Specification Unit Q'TY Remark

1 Industrial Computer Chassis : Rack-360GW-PX Sets 2 Attach #1


*.14 Slot Industrial chassis/White Color
Dimmension : 435.5(D) x 431(W) x 176(H)mm
Disk bay : Two 5.25" and One 3.5" disk bay
*.Power : ST-450PCG(ATX-450W)
*.Back Plane : PCI-14S2(1 x PICMG/8 x ISA/4 x PCI
*.CPU Board : WAB-Q354
LGA775 45nm Intel Core 2 Quad,Core 2 Duo,Celeron 800/1066 MHz FSB
Intel Q35+ICH9DO Chipset,AMI Flash BIOS
4 x DDR2 SDRAM DIMM Memory(MAX.8GB)
Onboard VGA,Audio,Dual Realteck LAN
2 x RS232,7 x USB2.0,6 x SATAII,1 x IDE,1 x FDD,1 x LPT
*.CPU : Intel Core 2 Duo E8500(3.16GHz/6MB)
*.RAM : 2GB DDR2 PC2-6400 * 2EA
*.HDD : 500GB SATA(7200rpm)
*.DVD : DVD-Multi(SATA)
*.Keyboard : 106 Keyboard
*.Mouse : Basic Optical Mouse
*.O/S : Microsoft Windows 7 PROFESSIONAL K COEM(DSP) 32bit
2 LG Mointor *.Model : W2453VP Sets 2 Attach #2
*.Picture Size : 24"(61cm)
*.Resulation : 1920 x 1080
*.Contrast Range : 50,000 : 1 (DFC)
*.Response Speed : 2ms
*.Luminannce : 300cd/㎡
*.Input Terminal : D-sub,DVI,HDMI
3 Alarm Printer Model : HP Deskjet Ink Advantage K010 Set 1 Attach #3

1 OF 2
PROJECT : CHILCA UNO POWER STATION ADD-ON PROJECT(Water Treatment System)/HMI HARD WARE

No. Proprietary Name Specification Unit Q'TY Remark

*.Method of Printing : Inkjet


*.Resulation : 600DPI
*.Printing Speed(Black & White) : 20ppm
*.Printing Speed(Color) : 16ppm
*.Color : 256Color Above

4 Hard Copier Model : HP LaserJet 5200n Set 1 Attach #4


*.Method of Printing : A3 Laserjet
*.Resulation : 600 * 600DPI
*.Printing Speed(Black & White) : 20ppm

5 Software Package
5-1 InTouch Runtime Edition(Sea water AREA) InToutch Runtime 3K Tag with I/O,V10.1(01-2334) Set 1 Attach #5
InTouch Development Edition(demi. water
5-2 InToutch Development Studio Large 5K/3k /500 V10.1a(97-1220) Set 1 Attach #5
AREA)

6 Desk & Chair for HMI Station Maker Standard Set 2 Attach #6

2 OF 2
Single board computer
Full Size

WSB-Q354 PICMG1.0 CPU Card supports Intel® LGA 775 Core 2 Duo CPU in 45nm
process at FSB800/1066/1333MHz, Intel® Q35 & ICH9R, VGA, Dual PCIe
GbE, Six SATA II with RAID, IDE, FDD, LPT, USB2.0

Generation Core Duo / Core 2 Duo / Core 2 Quad


Process 65nm 45nm
Front_Panel LGA 775 Four DIMM ICH9R TPM IDE LPT

LGA775

Quad Core
Yorkfield • Quad Core
• Up to 12MB L2
COM2 • 95W/130W TDP
COM1 • FSB1333/1066/800MHz
PCIE-Q350
Dual LAN
IEI Solution IMB-Q354
WSB-Q354
CPU

KB/MS

Q35 IrDA LGA775

Dual Core
KB
DIO • Dual Core
Wolfdale
• Up to 6MB L2
• 65W TDP

Dual DDR2
667 FSB1066 Intel® Matrix • FSB1333/1066/800MHz
PCIE-Q350
Storage Manager IEI Solution IMB-Q354
WSB-Q354
FSB 1066 / 800 / 533MHz 1333 / 1066 / 800MHz

PCIe
PCI-E Features
Specifications 1. PICMG1.0 and RoHS compliant
2. Supports Intel® LGA775 Core™2 Duo processor in 45 nm Process
CPU (Wofldale) at FSB 1333/1066/800MHz
LGA775 45nm Intel® Core™2 Quad (Yorkfield), Core™2 Duo (Wolfdale) , 3. Intel® Q35 & ICH9R Platform
Core™2 Duo, Celeron at FSB800/1066/1333MHz processors 4. 6 SATA II with Intel Matrix Storage Technology supported
System Chipset 5. Dual Broadcom PCIe GbE
Intel® Q35 + ICH9R 6. TPM1.2 IT Security Solution Supported
BIOS
AMI BIOS Label with 8Mb SPI EEPROM
System Memory Packing List
4 x 240pin DIMM socket dual channel DDRII at 800/667MHz up to 8GB
Ethernet 1 x WSB-Q354 single board computer
Dual Broadcom BCM5787M GbE with ASF 2.0
IO Interface 1 x Mini jumper pack
2 x RS-232
7 x USB2.0 (1 on bracket, 6 on board by pin header) 6 x SATA cable (P/N: 32000-062800-RS)
6 x SATA II support RAID 0, 1, 10, 5
3 x SATA power cable (P/N: 32100-088600-RS)
1 x IDE
1 x FDD 1 x Dual RS-232 cable (P/N:19800-000051-RS)
1 x LPT
1 x Keyboard and mouse (PS/2) 1 x USB cable (P/N: CB-USB02-RS)
1 x 5-pin on-board header for KB
Digital I/O 1 x KB/MS Y-cable (P/N:32000-000138-RS)
8-bit Digital I/O, 4-bit input / 4-bit output
IrDA 1 x Utility CD
1 x Infrared
1 x QIG
Audio
10-pin on-board header supports 7.1 channel HD Audio by IEI AC-
KIT883HD
Graphic Ordering Information
Analog VGA output Part No. Description
TPM1.2
1 x 20-pin on-board header for TPM(Trusted Platrom Module) PICMG1.0 CPU Card supports Intel® LGA 775 Core™2 Duo
Watchdog Timer CPU in 45nm proces at FSB800/1066/1333MHz,
WSB-Q354-R10
Software Programmable supports 1~255sec. system reset Intel® Q35 & ICH9R, VGA, Dual PCIe GbE, Six SATA II with
Power Supply RAID, IDE, FDD, LPT, USB2.0
ATX
7.1 Channel HD audio kit with Realtek ALC883 supports dual
Power Consumption AC-KIT883HD-R10
audio streams
3.3 V @ 0.03 A, 5 V @ 8.62 A, 5 Vsb @ 0.11 A, 12 V @ 0.1A,
Vcore@2.29A (Intel Core™2 Duo E8400, DDR2 800MHz 2GB x 4) 3D High Performance CPU cooler
Mark 2001SE CF-775A-RS
(115 mm x 115 mm x 67 mm, 130W)
Temperature
operation: 0°C ~ 60°C (32°F ~ 140°F) CF-520-RS
High Performance CPU cooler
Humidity (115 mm x 115 mm x 67 mm, 115W)
operation: 5% ~95% non-condensing
Infineon 20-pin Trusted Platform Module with S/W Management
Dimensions TPM-IN01-R10
Tool
338 mm x 126 mm
Weight Winbond 20-pin Trusted Platform Module with S/W
GW:1.1kg TPM-WI01-R10
Management Tool

19800-000066-RS KB/MS cable with bracket

32000-000052-RS IDE flat cable

WSB-Q354-V23
User’s Guide

W2453V

Make sure to read the Important Precautions before using the product.
Keep the User's Guide(CD) in an accessible place for future reference.

See the label attached on the product and give the information to your
dealer when you ask for service.
Important Precautions

This unit has been engineered and manufactured to ensure your personal safety,
however improper use may result in potential electrical shock or fire hazards. In
order to allow the proper operation of all safeguards incorporated in this display,
observe the following basic rules for its installation, use, and servicing.

On Safety
Use only the power cord supplied with the unit. In case you use another power
cord, make sure that it is certified by the applicable national standards if not being
provided by the supplier. If the power cable is faulty in any way, please contact the
manufacturer or the nearest authorized repair service provider for a replacement.

The power supply cord is used as the main disconnection device. Ensure that the
socket-outlet is easily accessible after installation.

Operate the display only from a power source indicated in the specifications of
this manual or listed on the display. If you are not sure what type of power supply
you have in your home, consult with your dealer.

Overloaded AC outlets and extension cords are dangerous. So are frayed power
cords and broken plugs. They may result in a shock or fire hazard. Call your service
technician for replacement.

Do not Open the Display:


There are no user serviceable components inside.
There are Dangerous High Voltages inside, even when the power is OFF.
Contact your dealer if the display is not operating properly.

To Avoid Personal Injury :


Do not place the display on a sloping shelf unless properly secured.
Use only a stand recommended by the manufacturer.
Do not drop an object on or apply impact to the product. Do not throw any toys
or objects on the product screen.
It can cause injury to human, problem to product and damage the display.

To Prevent Fire or Hazards:


Always turn the display OFF if you leave the room for more than a short period
of time. Never leave the display ON when leaving the house.
Keep children from dropping or pushing objects into the display's cabinet
openings. Some internal parts carry hazardous voltages.
Do not add accessories that have not been designed for this display.
When the display is to be left unattended for an extended period of time, unplug
it from the wall outlet.
In the presence of thunder and lightning, never touch the power cord and signal
cable because it can be very dangerous. It can cause electric shock.

On Installation
Do not allow anything to rest upon or roll over the power cord, and do not place
the display where the power cord is subject to damage.

A1
Important Precautions

Do not use this display near water such as near a bathtub, washbowl, kitchen
sink, laundry tub, in a wet basement, or near a swimming pool.
Displays are provided with ventilation openings in the cabinet to allow the release
of heat generated during operation. If these openings are blocked, built-up heat
can cause failures which may result in a fire hazard. Therefore, NEVER:

Block the bottom ventilation slots by placing the display on a bed, sofa, rug, etc.
Place the display in a built-in enclosure unless proper ventilation is provided.
Cover the openings with cloth or other material.
Place the display near or over a radiator or heat source.

Do not rub or strike the Active Matrix LCD with anything hard as this may scratch,
mar, or damage the Active Matrix LCD permanently.

Do not press the LCD screen with your finger for a long time as this may cause
some afterimages.

Some dot defects may appear as Red, Green or Blue spots on the screen.
However, this will have no impact or effect on the display performance.

If possible, use the recommended resolution to obtain the best image quality for
your LCD display. If used under any mode except the recommended resolution,
some scaled or processed images may appear on the screen. However, this is
characteristic of the fixed-resolution LCD panel.

Leaving a fixed image on the screen for a long time may cause damage to the
screen and cause image burn-in. Make sure to use a screen saver on the product.
Burn-in and related problems are not covered by the warranty on this product.

Do not shock or scratch the front and sides of the screen with metallic objects.
Otherwise, it may cause damage to the screen.

On Cleaning
Unplug the display before cleaning the face of the display screen.
Use a slightly damp (not wet) cloth. Do not use an aerosol directly on the display
screen because over-spraying may cause electrical shock.

On Repacking
Do not throw away the carton and packing materials. They make an ideal
container in which to transport the unit. When shipping the unit to another
location, repack it in its original material.

On Disposal
The fluorescent lamp used in this product contains a small amount of mercury.
Do not dispose of this product with general household waste.
Disposal of this product must be carried out in accordance to the regulations of
your local authority.

A2
Connecting the Display

Connecting the stand


1. Place the monitor with its front facing downward on a soft cloth.
2. Assemble the stand base into stand body in the correct direction as shown in
the picture, then tighten the screw which is attached to the stand base.

Stand Base
Stand Body Screw

3. Once assembled take the monitor up carefully and face the front side.

Disassembling the stand


1. Place the monitor face down on the cushion or soft cloth.
2. Loosen the screw which is attached to the stand base, then take off the stand base
from stand body.
Stand Body Stand Base

Screw

Important
This illustration depicts the general model of connection. Your monitor may differ from
the items shown in the picture.
Do not carry the product upside down holding only the stand base. The product may
fall and get damaged or injure your foot.

A3
Connecting the Display

Before setting up the monitor, ensure that the power to the monitor, the computer
system, and other attached devices is turned off.

Positioning your display


1. Adjust the position of the panel in various ways for maximum comfort.
Tilt Range: -5˚~15˚

Swivel: 355˚

Ergonomic
It is recommended that in order to maintain an ergonomic and comfortable viewing
position, the forward tilt angle of the monitor should not exceed 5 degrees.

A4
Connecting the Display

Using the Computer


1. Make sure to turn off the computer and product. Connect the cable as below
sketch map form 1 to 2 .
A Connect DVI-D Cable NOTE
This is a simplified representation of the rear view.
B Connect D-sub Cable (PC) This rear view represents a general model; your display may differ from the view as
shown.
C Connect D-sub Cable (Mac) User must use shielded signal interface cables (D-sub 15 pin cable, DVI cable) with
ferrite cores to maintain standard compliance for the product.
D Connect HDMI Cable

Power Cord Signal Cable

Headphone/Earphone Input Wall-outlet type

AV equipment
(Set-Top Box, DVD, Video,
Video Game Console)

DVI-D(This feature is not


available in all countries.)

Mac adapter
For Apple Macintosh use, a separate plug adapter is needed
to change the 15 pin high density (3 row) D-sub VGA
connector on the supplied cable to a 15 pin 2 row connector.

2. Touch the power button on the front of panel to turn


the power on. When monitor power is turned on, the
'Self Image Setting Function' is executed
automatically. (Only to the D-sub signal cable input)

NOTE
'Self Image Setting Function'? This function provides the user with optimal display settings.When the user
connects the monitor for the first time, this function automatically adjusts the display to optimal settings for
individual input signals.
'AUTO/SET Function'? When you encounter problems such as blurry screen, blurred letters, screen flicker
or tilted screen while using the device or after changing screen resolution, touch the AUTO/SET function button
to improve resolution.

A5
Connecting the Display

Using the cable holder (This feature is not available in all models.)

OPEN

Cable holder

1 2
OPEN

4 3

EN
OP

A6
Control Panel Functions

Front Panel Controls

1 2 3 4 5 6 7 8

Control Function

Button Use this button to enter CINEMA MODE,AUTO


BRIGHT,TIME CONTROL,LIVE SENSOR,SMART
items,for more information,refer to page A15.

Button DSUB and DVI input,use this button to enter EZ


ZOOMING,4:3 IN WIDE,PHOTO EFFECT items.
HDMI input,use this button to enter 4:3 IN WIDE,
PHOTO EFFECT,VOLUME items.
For more information,refer to page A16 -A17 .

MENU Button Use this button to enter or exit from the On Screen Display.

OSD LOCKED/UNLOCKED
This function allows you to lock the current control settings, so
that these settings are not inadvertently changed. To lock the
OSD settings, press and hold the MENU button for several
seconds. The message "OSD LOCKED" appears.
You can unlock the OSD settings at any time by
pushing the MENU button for several seconds. The
message "OSD UNLOCKED" appears.

A7
Control Panel Functions

Control Function

Use these buttons to select or adjust functions in the On


Buttons
Screen Display.

Button For more information, refer to page A18 -A19.


( )

Button Use this button to make either D-Sub,DVI or HDMI


connector active. This feature is used when two
(SOURCE)
computers are connected to the display. The default
setting is D-Sub.

AUTO/SET Use this button to select an icon in the On Screen


Button Display.

AUTO IMAGE ADJUSTMENT


When adjusting your display settings, always press
the AUTO/SET button prior to entering the On
Screen Display(OSD). This will automatically adjust
your display image to the ideal settings for the
current screen resolution size (display mode).
The best display mode is:
W2453V : 1920 x 1080

Power Button Use this button to turn the display on or off.

Power Indicator This Indicator lights up as red when the display is


operating normally(On Mode). If the display is in
Sleep Mode (Energy Saving), this indicator color
changes to flicker.

Light Sensor This is lens for light sensor sletect outside luminance,
when setting AUTO BRIGHT ON.

A8
On Screen Display (OSD) Control Adjustment

Screen Adjustment
Making adjustments to the image size, position and operating parameters of
the display is quick and easy with the On Screen Display Control system.
A short example is given below to familiarize you with the use of the controls.
The following section is an outline of the available adjustments and selections
you can make using the OSD.

NOTE
Allow the display to stabilize for at least 30 minutes before making image adjustments.

To make adjustments in the On Screen Display, follow these steps:

Press the MENU Button, then the main menu of the OSD appears.

To access a control, use the or Buttons. When the icon you want
becomes highlighted, press the AUTO/SET Button.

Use the / Buttons to adjust the image to the desired level. Use the
AUTO/SET Button to select other sub-menu items.

Push the MENU Button once to return to the main menu to select another
function. Push the MENU Button twice to exit from the OSD.

A9
On Screen Display(OSD) Selection and Adjustment
The following table indicates all the On Screen Display control, adjustment,
and setting menus.
Main menu Sub-menu A D H Reference
CINEMA MODE To focus on the moving picture selected.
AUTO BRIGHT To control screen brightness automatically.
TIME CONTROL To mind user using time.
LIVE SENSOR To control touch key distance.
SMART To control smart key menu.
EZ ZOOMING To adjust the resolution
4:3 IN WIDE To adjust the image size
NORMAL
PHOTO GAUSSIAN BLUR
To adjust screen color mode
EFFECT SEPIA
MONOCHROME
VOLUME To adjust the volume
BRIGHTNESS
To adjust the brightness, contrast and
CONTRAST
PICTURE gamma of the screen
GAMMA
**BLACK LEVEL To set offset level
sRGB
PRESET 6500K
9300K
COLOR To costomize the color of the screen
RED
GREEN
BLUE
HORIZONTAL
To adjust the position of the screen
VERTICAL
TRACKING CLOCK
To improve the clarity and stability of the
PHASE
screen
SHARPNESS
LANGUAGE
OSD HORIZONTAL
POSITION VERTICAL
*WHITE BALANCE To costomize the screen status for a
SETUP user's operating environment
**OVERSCAN
POWER INDICATOR
FACTORY RESET
MOVIE
*INTERNET
**GAME
FLATRON USER To select or customize desired image
F-ENGINE *NORMAL settings
**STANDARD
*DEMO
**SPORTS

● : Adjustable A : DSUB Input


* : only for DSUB/DVI Input D : DVI Input
** : only for HDMI Input H : HDMI Input

NOTE
The order of icons may differ depending on the model (A10~A19).

A10
On Screen Display(OSD) Selection and Adjustment

You were introduced to the procedure of selecting and adjusting an item


using the OSD system. Listed below are the icons, icon names, and icon
descriptions of the all items shown on the Menu.

Press the MENU Button, then the main menu of the OSD appears.

Main Menu

MENU : Exit
: Adjust (Decrease/Increase)
SET : Enter
: Select another sub-menu
: Restart to select sub-menu
Button Tip

Menu Name

Sub-menus
Icons

NOTE
OSD (On Screen Display) menu languages on the monitor may differ from the manual.

A11
On Screen Display(OSD) Selection and Adjustment

Main menu Sub menu Description

PICTURE

PICTURE

DSUB/DVI input
BRIGHTNESS To adjust the brightness of the screen.

CONTRAST To adjust the contrast of the screen.

GAMMA Set your own gamma value. : -50/0/50


On the monitor, high gamma values
display whitish images and low gamma
values display high contrast images.
HDMI input
BLACK LEVEL You can set the offset level. If you select
'HIGH', the screen will be bright and if you
select ‘LOW’, the screen will be dark.
(only for HDMI input)

* Offset? As the criteria for video signal, it is the


darkest screen the monitor can show.

MENU : Exit
: Decrease
: Increase
SET : Select another sub-menu

COLOR

COLOR

PRESET • sRGB: Set the screen color to fit the


SRGB standard color
specification.
• 6500K: Slightly reddish white.
• 9300K: Slightly bluish white.

RED Set your own red color levels.

GREEN Set your own green color levels.


MENU : Exit
: Decrease BLUE Set your own blue color levels.
: Increase
SET : Select another sub-menu

A12
On Screen Display(OSD) Selection and Adjustment

Main menu Sub menu Description

TRACKING

TRACKING

HORIZONTAL To move image left and right.

VERTICAL To move image up and down.

CLOCK To minimize any vertical bars or


stripes visible on the screen
background.
The horizontal screen size will also
change.
PHASE To adjust the focus of the display.
This item allows you to remove
any horizontal noise and clear or
sharpen the image of characters.
MENU : Exit
: Decrease SHARPNESS To adjust the clearness of the
: Increase screen.
SET : Select another sub-menu

A13
On Screen Display(OSD) Selection and Adjustment

Main menu Sub menu Description

SETUP

SETUP LANGUAGE To choose the language in which the


control names are displayed.

OSD To adjust position of the OSD window


POSITION on the screen.

WHITE If the output of the video card is different


BALANCE the required specifications, the color
level may deteriorate due to video
DSUB/DVI input signal distortion. Using this function, the
signal level is adjusted to fit into the
standard output level of the video card
in order to provide the optimal image.
Activate this function when white and
black colors are present in the screen.
(only for DSUB input)

OVERSCAN To select the range of output image for


HDMI input
DTV timing in HDMI input.
(only for HDMI input)
Recommend overscan function to turn
on when connect AV equipment.

POWER Use this function to set the power


INDICATOR indicator on the front side of the monitor
to ON or OFF.
MENU : Exit If you set OFF, it will go off.
: Adjust If you set ON at any time, the power
: Adjust indicator will automatically be turned on.
SET : Select another sub-menu

FACTORY Restore all factory default settings except


RESET "LANGUAGE."
Press the , buttons to reset immediately.

If this does not improve the screen image, restore the factory default settings.
If necessary, perform the white balance function again. This function will be enabled only when
the input signal is an analog signal.

A14
On Screen Display(OSD) Selection and Adjustment

The OSD screen will appear when you touch the button on the right bottom of the
monitor.

Main menu Sub menu Description

CINEMA MODE It focuses better on the moving picture in


selected area.
*This function is operated only if the
fortemanager is installed to pc.
*Only for DSUB and DVI input.

AUTO BRIGHT If select on,it automatically controls the


brightness of display to best suit the
surrounding working environment,providing
the optimal viewing condition and maximized
user convenience.
If select off,auto brightness is off.

TIME CONTROL Remind user using time by showing alarm


OSD and flickering power LED.
Selection:OFF/1HOUR/2HOUR

LIVE SENSOR This function turns on the button LED for


pushing comfortable.When detect the
presence of users hand before touch it.

SMART To adjust AUTO BRIGHT,TIME CONTROL,


LIVE SENSOR.
If select ON it turns on AUTO BRIGHT,LIVE
SENSOR and makes time CONTROL to 1HOUR.
If select off,it turns off those.
If set AUTO BRIGHT,TIME CONTROL,LIVE
SENSER directly,this setting is changed to
USER automatically.

A15
On Screen Display(OSD) Selection and Adjustment

The OSD screen will appear when you touch the button on the left bottom of the
monitor.

DSUB/DVI input

HDMI input

VOLUME

Main menu Sub menu Description

EZ ZOOMING EZ Zoom lowers the display’s resolution in


single-step increments. Depressing the button
once lowers the resolution by one step; while a
second button-press returns the resolution to
the original display settings.

*This function is operated only if the


forteManager is installed to PC.
*ForteManager is not supported in HDMI input.

4:3 IN WIDE To select the image size of the screen.

WIDE 4:3

• WIDE : Switch to full screen mode according to input


image signal.
• 4 : 3 : Change the image signal ratio into 4:3.

A16
On Screen Display(OSD) Selection and Adjustment

Main menu Sub menu Description

To select the color of the screen.

PHOTO EFFECT
• NORMAL :
The PhotoEffect function is disabled.

• GAUSSIAN BLUR :
This option is to add the effect to the screen that
the dark and sharp image becomes brighter and
more blurred.
• SEPIA :
This option changes the screen to be Sepia tone.
The Sepia tone is brown color tone.

• MONOCHROME :
This option changed the screen to be Gray tone.
The screen image is displayed with just white,
black, gray colors.

NORMAL GAUSSIAN BLUR SEPIA MONOCHROME

*Photo Effect feature may not work in HDMI Input.


(Photo effect operate at DSUB format)

VOLUME To adjust the volume of headphone/Earphone.


(Only for HDMI input)

SET

A17
On Screen Display(OSD) Selection and Adjustment

The OSD screen will appear when you touch the button on the left bottom of
the monitor.

Menu Name

Icons

Sub-menu Name

Main menu Sub menu Description

MOVIE Select this when you are watching a video or


movie.

DSUB/DVI input

INTERNET Select this when you are working on the


document (Word etc.)

HDMI input

GAME Select this when you are playing a game.

DSUB/DVI input

NORMAL Select this when you want to use the product in


the most general using environment.
* Normal mode is when f-ENGINE is turned off.

HDMI input

STANDARD Select this when you want to use the original


standard video.

* In the General (Standard) mode, the


is turned off.

A18
On Screen Display(OSD) Selection and Adjustment

Main menu Sub menu Description


DSUB/DVI input
DEMO This is used for advertising in the store. The screen
will be divided to show the standard mode on the
left and video mode on the right so that the
consumers can check the difference after applying
the video mode.

HDMI input

SPORTS Select this when you watching general sports.

USER You can manually adjust ACE or RCM


(only for DSUB/DVI input), HUE or SATURATION
(only for HDMI input).
You can save or restore the adjusted value even
when using a different environment.
To adjust the USER sub-menu
function,press the AUTO/SET Button.
... ACE(Adaptive Clarity Enhancer) : Selects the clarity mode.
DSUB/DVI input
Not applied
Weak clarity and luminosity contrast.
Strong clarity and luminosity contrast.

... RCM(Real Color Management) : Selects the color mode.

Not applied
Green enhance
HDMI input Flesh tone
Color Enhance

... HUE : Adjust the screen hue.


... SATURATION : Adjust the screen saturation.

MENU : Exit
: Decrease
: Increase
AUTO/SET : Select another sub-menu

A19
Troubleshooting

Check the following before calling for service.

No image appears
● Is the power cord of the • Check and see if the power cord is connected
display connected? properly to the power outlet.

● Is the power indicator • Press the Power button.


light on?

● Is the power indicator • If the display is in power saving mode, try moving
flickering? the mouse or pressing any key on the keyboard to
bring up the screen.
• Try to turn on the PC.

● Do you see an "OUT OF • This message appears when the signal from the
RANGE" message on PC (video card) is out of horizontal or vertical
the screen? frequency range of the display. See the
'Specifications' section of this manual and
configure your display again.

● Do you see a "CHECK • This message appears when the signal cable
SIGNAL CABLE" between your PC and your display is not
message on the connected. Check the signal cable and try again.
screen?

Do you see a "OSD LOCKED" message on the screen?

● Do you see “OSD • You can secure the current control settings,
LOCKED” when you so that they cannot be inadvertently changed.
push MENU button? You can unlock the OSD controls at any time
by pushing the MENU button for several
seconds: the message
“OSD UNLOCKED” will appear.

A20
Troubleshooting

Display image is incorrect


● Display Position is • Press the AUTO/SET button to automatically
incorrect. adjust your display image to the ideal setting.
If the results are unsatisfactory, adjust the image
position using the H position and V position icon
in the on screen display.

● On the screen • Press the AUTO/SET button to automatically


background, vertical adjust your display image to the ideal setting.
bars or stripes are If the results are unsatisfactory, decrease the
visible. vertical bars or stripes using the CLOCK icon in
the on screen display.

● Any horizontal noise • Press the AUTO/SET button to automatically


appearing in any adjust your display image to the ideal setting.
image or characters If the results are unsatisfactory, decrease the
are not clearly horizontal bars using the PHASE icon in the on
portrayed. screen display.
• Check Control Panel --> Display --> Settings
and adjust the display to the recommended
resolution or adjust the display image to the ideal
setting. Set the color setting higher than 24 bits
(true color).

Important
Check Control Panel --> Display --> Settings and see if the frequency or the
resolution were changed. If yes, readjust the video card to the recommend
resolution.
If the recommended resolution (optimal resolution) is not selected, letters may
be blurred and the screen may be dimmed, truncated or biased. Make sure to
select the recommend resolution.
The setting method can differ by computer and O/S (Operation System),
and resolution mentioned above may not be supported by the video card
performance. In this case, please ask to the computer or the video card
manufacturer.

A21
Troubleshooting

Display image is incorrect


● The screen color is • Check if the signal cable is properly connected
mono or abnormal. and use a screwdriver to fasten if necessary.
• Make sure the video card is properly inserted in
the slot.
• Set the color setting higher than 24 bits (true color)
at Control Panel - Settings.

● The screen blinks. • Check if the screen is set to interlace mode and if
yes, change it to the recommend resolution.

Have you installed the display driver?

● Have you installed the • Be sure to install the display driver from the display
display driver? driver CD (or diskette) that comes with your
display. Or, you can also download the driver from
our web site: http://www.lge.com.

● Do you see an • Make sure to check if the video card supports


"Unrecognized monitor, Plug&Play function.
Plug&Play (VESA DDC)
monitor found"
message?

A22
Specifications W2453V

Display 24.0 inches (60.9 cm) Flat Panel Active matrix-TFT LCD
Anti-Glare coating
Visible diagonal size: 60.9 cm
0.276*0.276 mm pixel pitch
Sync Input Horizontal Freq. 30 - 83 kHz (Automatic)
Vertical Freq. Analog,Digital : 56 - 75 Hz (Automatic)
HDMI : 56 - 61 Hz (Automatic)
Input Form Separate TTL, Positive/Negative
SOG (Sync On Green)
Digital (HDCP)
Video Input Signal Input 15 pin D-Sub Connector
DVI - D connector (Digital)
19 pin HDMI Connector
Input Form Analog (0.7 Vp-p/ 75 ohm), Digital, HDMI

Resolution Max Analog : VESA 1920 x 1080 @60 Hz


Digital : VESA 1920 x 1080 @60 Hz
Recommend VESA 1920 x 1080 @60 Hz
Plug&Play DDC 2B (Digital,HDMI), DDC 2AB (Analog)
Power On Mode : 47 W(Typ.)
Consumption Sleep Mode ≤ 1W
Off Mode ≤ 1W
Dimensions With Stand Without Stand
&Weight Width 58.23 cm / 22.92 inches 58.23 cm / 22.92 inches
Height 44.44 cm / 17.49 inches 43.08 cm / 16.96 inches
Depth 21.20 cm / 8.34 inches 6.63 cm / 2.61 inches
Net 5.39 kg (11.88 lbs)
Range Tilt -5˚~15˚
Swivel 355°
Power Input AC 100-240V~ 50/60Hz 1.2A
Environmental Operating Conditions
Conditions Temperature 10˚C to 35 ˚C
Humidity 10 % to 80 % non-Condensing
Storage Conditions
Temperature -20˚C to 60 ˚C
Humidity 5 % to 90 % non-Condensing
Stand Base Attached( ), Detached ( O )
Power cord Wall-outlet type

NOTE
Information in this document is subject to change without notice.

A23
Specifications

Preset Modes (Resolution)


DSUB/DVI Timing

Display Modes (Resolution) Horizontal Freq. (kHz) Vertical Freq. (Hz)

1 720 x 400 31.468 70


2 640 x 480 31.469 60
3 640 x 480 37.500 75
4 800 x 600 37.879 60
5 800 x 600 46.875 75
6 1024 x 768 48.363 60
7 1024 x 768 60.123 75
8 1152 x 864 67.500 75
9 1280 x 1024 63.981 60
10 1280 x 1024 79.976 75
11 1680 x 1050 65.290 60
*12 1920 x 1080 67.500 60

* Recommend Mode

HDMI Timing

Display Modes (Resolution) Horizontal Freq. (kHz) Vertical Freq. (Hz)

1 480P 31.50 60
2 576P 31.25 50
3 720P 37.50 50
4 720P 45.00 60
5 1080i 28.12 50
6 1080i 33.75 60
7 1080P 56.25 50
8 1080P 67.50 60

Indicator
MODE LED Color

On Mode Red
Sleep Mode Flicker
Off Mode Off

A24
Digitally yours
hp_k010a.jpg
(654 X 5254)
Wonderware® InTouch® HMI Version 10.1 Service Pack 3 Readme
Last revision: 11/4/2010

About This Release

Version 10.1 SP3 of Wonderware® InTouch HMI includes support for new operating systems, an XML graphics importer, and resolved issues.

Wonderware InTouch HMI version 10.1 SP3 Information

Support for New Operating Systems

XML Graphics Importer

System Requirements

Using Wonderware InTouch with Windows 7 and Windows Server 2008 R2

Installing Microsoft .NET Framework on Wonderware InTouch 10.1 SP3

Upgrading from a Previous Version of Wonderware InTouch

Product Compatibility

Resolved Issues - Wonderware InTouch 10.1 SP3

Known Issues - Wonderware InTouch 10.1 SP3

Antivirus Software Exclusions

Support for New Operating Systems

Wonderware InTouch 10.1 SP3 supports the following new releases of Microsoft operating systems:

Windows 7, Professional, 32/64-bit (emulation mode) versions


Windows Server 2008 R2, Standard, 64-bit (emulation mode) version

System Requirements

This section describes the hardware and software requirements to install Wonderware® InTouch HMI Version 10.1 SP3.

Hardware Requirements
Software Requirements
Using Wonderware InTouch with Windows 7 and Windows Server 2008 R2
Other Software Requirements

Standalone InTouch Node

Computer with 1.2 GigaHertz (GHz) or faster processor (32/64bit). Intel Itanium 2 processor is not supported.
512 MB of memory minimum, 1 GigaByte (GB) or greater recommended
At least 4 GB of available disk space for 32-bit OS, 6 GB available disk space for 64-bit OS
Super VGA (1024 × 768) or higher-resolution video adapter and monitor
CD-ROM or DVD drive for installation
Keyboard
Mouse or compatible pointing device

Non-GR Platform With or Without an InTouch Application

Computer with 2 GHz or faster processor (32/64 bit). Multi-core processor is strongly recommended. Intel Itanium 2 processor is not supported.
1 GB of memory minimum, 4 GB or greater recommended
At least 30 GB of available disk space for 32-bit OS, 40 GB for 64-bit OS
Super VGA (1024 × 768) or higher-resolution video adapter and monitor
Network interface card
CD-ROM or DVD drive for installation
Keyboard
Mouse or compatible pointing device
Software Requirements

The following table lists the supported operating systems that can be installed on computers that run InTouch server and client components.

Product Name Components


Window WindowV ArchestrA Run
Operating Systems ArchestrA IDE Galaxy Repository
Maker iewer Time
Windows 7 Professional 64-bit • • • • •
Windows 7 Professional 32-bit • • • • •
Windows Server 2008 R2 Standard • • • • •
Windows 2008 Standard 32-bit
• • • • •
(See Vista Restrictions)
Windows 2008 Standard 64-bit
• • • • •
(See Vista Restrictions)
Windows Vista SP2 Business, Enterprise, or Ultimate
• • • • •
(See Vista Restrictions)
Windows Vista SP1 Business, Enterprise, or Ultimate
• • • • •
(See Vista Restrictions)
Windows Vista Business, Enterprise, or Ultimate
• • • • •
(See Vista Restrictions)
Windows 2003 Standard Server R2 • • • • •
Windows 2003 Standard Server SP2 • • • • •
Windows 2003 Enterprise Server R2 • • • • •
Windows 2003 Enterprise Server SP2 • • • • •
Windows XP Professional SP3 • • • •
Windows XP Tablet • • •

Terminal Server Restrictions for Windows 2008

ArchestrA Symbols referencing InTouchViewApp_001.Tag1


Running on the Console Refers to the tag value of the application running on the console.
Running in a Session Refers to the tag value of the application running on the console.
Restarting the Window Viewer application running on the console causes references from the terminal session to disconnect and then reconnect.

InTouch Graphic referencing Tag1


Running on the Console Refers to the tag value of the application running on the console.
Running in a Session Refers to the tag value of the application running in the session.

ArchestrA Graphic referencing InTouch:Tag1


Running on the Console Refers to the tag value of the application running on the console.
Running in a Session Refers to the tag value of the application running in the session.

InTouch Graphic referencing Galaxy:InTouchViewApp_001.Tag1


Running on the Console Refers to the tag value of the application running on the console.
Running in a Session Refers to the tag value of the application running on the console.

Using Multiple Network Interface Cards with Windows Server 2008

About This Release


Version 10.1 of Wonderware® InTouch HMI includes the following enhancements and new features:

Language Switching for ArchestrA Symbols

You can switch to localized strings for ArchestrA Symbols. This


includes any configuration-time changes to support the
extracting and importing of text strings. You can localize the
following strings:
Text constant custom properties
Text graphics
Text overrides of custom properties in WindowMaker
You can also add, edit, and remove the locale data from the
Symbol Editor.

Licensing

InTouch licensing now accounts for Terminal Service sessions.


The licensing system now enforces per session licensing to
prevent running unlicensed copies of InTouch within Terminal
Server Sessions.

Non-Administrator Interactive User

At a high level, this feature allows InTouch run-time functionality


to be run by users who do not have administrative rights on the
computer. It does not provide this support for configuration
operations. Functionality is available for the following operating
systems:
Windows XP SP3 (Power user)
Windows 2003 SP2, R2 + SP2 (Power user)
Windows Vista SP1 (Standard user with the UAC enabled)

Well-known Client Control Support

The Symbol Editor has been extended to allow new Graphic Objects to appear in the Symbol Editor tool palette.
Printing Enhancements

Several printing features are added to the InTouch HMI:


Saving and Printing a Tag Cross-Reference List
Printing Scripts
Printing Information about WindowMaker Objects
Printing Information about InTouch Windows
Printing Window Information from a Command Prompt

Deployed File Management

You can add additional files in a managed InTouch application so they are deployed and available at run time.

System Requirements
This section describes the hardware and software requirements to install Wonderware® InTouch HMI Version 10.1.

Hardware Requirements
Software Requirements
Other Software Requirements

Hardware Requirements

Computer with 1.2 gigahertz (GHz) or faster processor


512 MB of memory minimum, 1 gigabyte (GB) or greater recommended
At least 4 GB of available disk space
Super VGA (1024 × 768) or higher-resolution video adapter and monitor
CD-ROM or DVD drive for installation
Keyboard
Mouse or compatible pointing device

Software Requirements

The following table lists the supported operating systems that can be installed on computers that run InTouch server and client components.
Product Name Components
Window WindowV ArchestrA Run
Operating Systems ArchestrA IDE Galaxy Repository
Maker iewer Time
Windows Vista Business
• • • • •
(See Vista Restrictions)
Windows Vista Business SP1
• • • • •
(See Vista Restrictions)
Windows Vista Enterprise
• • • • •
(See Vista Restrictions)
Windows Vista Enterprise SP1
• • • • •
(See Vista Restrictions)
Windows Vista Ultimate
• • • • •
(See Vista Restrictions)
Windows Vista Ultimate SP1
• • • • •
(See Vista Restrictions)
Windows 2003 Standard Server R2 • • • • •
Windows 2003 Standard Server SP2 • • • • •
Windows 2003 Enterprise Server R2 • • • • •
Windows 2003 Enterprise Server SP2 • • • • •
Windows XP Professional SP3 • • • •
Windows XP Tablet • • •