AI No. Discipline Location Description of change Issue Date Cost Estimate (HK$)
1. Additional alarm bells will be provided to
cover the C&ED 291 M Restroom and C&ED
292 F Restroom as per the FSD comment during
their inspection on 3 Jan 2019. 2. Additional
remote indicator will be provided to cover the
FS-068 FS DOG Filtration Plant Room as per the FSD comment 29/1/2019 18,000.00
Additional exit sign, directional
sign and essential lighting to suit latest GBP.
EE-165 EE FSD Revise Tx room lighting layout for FS Inspection. 29/1/2019 69,000.00
Additional hose reels with associated pipeworks,
alarm bells, manual call points, visual fire alarms,
remote indicators, directional signs, heat
detectors and smoke detectors will be provided as
FS-069 FS CEBI per the FSD comment during their inspection on 31/1/2019 139,000.00
Additional alarm bells, manual call points, visual
fire alarms and smoke detectors will be provided
as per the FSD comment during their inspection
FS-070 FS FXRVIS on 17-22 Jan 2019. 31/1/2019 86,000.00
Additional exit sign, directional
sign and essential lighting to suit latest GBP.
Revise Tx room lighting layout and 4/F lighting
EE-166 EE HKP layout for FS Inspection. 31/1/2019 45,000.00
Change 3 nos. of isolator from
40A (DP) to 63A (TPN). Change the
corresponding MCCB units from 40A (SPN) to
EE-169 EE PTB 63A (TPN). Change the corresponding power 31/1/2019 219,000.00
Change the rating of isolators for
under deck bridge deck bridge lighting from 40A
(TPN) to 63A (TPN). Change the rating of
isolators for gantry lighting from 40A (SPN) to
63A (TPN). Change the corresponding power
EE-170 EE CRBO cable from 2-core to 4-core. 12/2/2019 81,000.00
Omit IT trunking in IMMD 13
Strong Room. Extend cable tray to floor panel
with brush outlet for cabling work at all conputer
rooms. Revise adaptable boxes location and
additional concealed conduit for Facial Access
EE-171 EE PTB Control System at IMMD 20 Computer Server 12/2/2019 23,000.00
Revise Kiosk 75x75mm trunking to suit the final
EE-173 EE CPK setting out of VEC for ImmD operation need. 12/2/2019 18,800.00
Modification of F&E cable
EE-175 EE PTB containment to suit user daily's operation 14/2/2019 98,000.00
Modification of F&E cable
containment to suit user daily's operation.
EE-176 EE CEBI Modification of electrical layouts to suit user 14/2/2019 20,000.00
Modification of F&E cable
containment to suit user daily's operation.
EE-177 EE CEBO Modification of electrical layouts to suit user 14/2/2019 14,000.00
Change 1 no. of Directional Exit
EE-178 EE DOG Sign to 2 nos. of Directional Exit Sign. 14/2/2019 4,000.00
Additional emergency lighting
and revise exit sign at FXI to suit FS Inspection
EE-179 EE FXI comment. 14/2/2019 25,000.00
Revise card reader, breakglass, door
SY-053 SY CEBI release button provision to suit user requirements. 14/2/2019 5,000.00
Relocate repeated panel and thermostat to suit
AC-047 AC CEBO user's daily operation. 21/2/2019 120,000.00
Additional FRP enclosure to be provided in
Genset Room as per the FSD comment during
AC-048 AC PTB their inspection on 22 Jan 2019. 21/2/2019 288,000.00
Additional 6nos. of 20W horn speaker to suit FS
AE-008 AE CEBI Inspection comment at CBI. 21/2/2019 33,000.00
Additional Telephone points,
adaptable boxes and socket outlets for FSD
operation need. Revise Trunking routing to suit
EE-168 EE FSD for FSD operation need. 21/2/2019 266,000.00
Extend cable tray to floor panel
with brush outlet for cabling work at all conputer
EE-172 EE CEBI rooms. 21/2/2019 2,000.00
Revise Kiosk 75x75mm trunking to suit the final
EE-174 EE GVK setting out of VEC for ImmD operation need. 21/2/2019 28,200.00
Revise emergency lighting and
EE-180 EE CEBI exit sign at CBI to suit FS Inspection comment. 21/2/2019 55,000.00
Revise of drainage pipeworks
routing to match the latest coordination and
SD-056 SD GVKI SCCU approval drawing 21/2/2019 277,000.00
Additional drainage pipeworks
to suit latest GBP. Revise of drainage pipeworks
routing to match the latest coordination and
SD-057 SD CEBO SCCU approval drawing 21/2/2019 198,000.00
Revise of drainage pipeworks
routing to match the latest coordination and
SD-058 SD GVKO SCCU approval drawing 21/2/2019 298,000.00
Relocate adaptable box and socket to suit C&ED
operation need as per the joint site inspection on
14 Dec 2019. Additional adaptable box for the
EE-183 EE GVKI vertical posts to suit ImmD and C&ED operation 27/2/2019 221,500.00
Relocate adaptable box and
socket to suit C&ED operation need as per the
joint site inspection on 14 Dec 2019. Additional
adaptable box for the vertical posts to suit ImmD
EE-184 EE GVKO and C&ED operation need. 27/2/2019 221,500.00
Relocate socket at DOG NER to
EE-185 EE DOG suit C&ED operation need. 27/2/2019 44,000.00
Additional hose reels with associated pipeworks,
sprinkler heads with associated pipeworks, alarm
bells, breakglasses, heat detectors, flashing lights
and directional signs will be provided as per the
FS-075 FS CEBO FSD comment during their inspection on 19-22 1/3/2019 80,000.00
Additional 5nos. of 20W horn speaker
AE-009 AE CEBO to suit FS Inspection comment at CBO. 6/3/2019 28,000.00
Revise emergency lighting at
EE-182 EE CEBO CBO to suit FS Inspection comment. 6/3/2019 24,000.00
FS-096 FS MS2 Additional Breakglass unit and fire extinguisher 5/7/2019 7000
Additional alarm bells and sprinkler heads with
associated pipeworks will be provided as per FSD
FS-097 FS C&PCK comments on 4 July 2019 5/7/2019 136,000.00
Additional E-lighting for Coach canoply and
EE-270 EE PTB additional F.C.U for FS panel outside DG Store 9/7/2019 143,000.00
Additional F.C.U for FS panel outside DG Store
and additional F.C.U for ELV Equipment from
EE-271 EE FSD RFI-BS-4037 9/7/2019 31,500.00
Additional alarm bells, breakglass and sprinkler
heads with associated pipeworks will be provided
as per FSD comments on 4
FS-098 FS PCEB July 2019 9/7/2019 120,000.00
As per FSD inspector's request, 93°C high
temperature sprinklers instead of 68°C normal
temperature sprinklers will be
provided under skylights/glazed roof of Coach
Covered Walkway
and Glazed Canopy to suit Clause 14.4 of BS EN
FS-091 FS PTB 12845:2003. 17/7/2019 297,000.00
Additional monitor modules for the interface of
the control of fire
shutters at 1/F Supermarket & 2/F Convenience
Store between
AC & FS will be provided as per FSD comments
FS-100 FS PTB on 12 July 2019 17/7/2019 5,000.00
Addotional directional sign, exit sign, visual fire
alarm and breakglass unit will be provided as per
FS-101 FS PB FSD comments on 15 July 2019 17/7/2019
Addotional alarm bell and breakglass unit will be
FS-102 FS MS2 provided as per FSD comments on 15 July 2019 17/7/2019 27,000.00
EE-272 EE PTB Additional E-lighting for SES panel, last exit 24/7/2019
Additional E-lighting for small rooms and
EE-273 EE PTB protected lobby 24/7/2019
Additional of repeated FS signal to RF Exit Door
SY-054 SY PTB for emergency release 26/7/2019 9,800.00