Вы находитесь на странице: 1из 12

Managing Fault Ride Through Compliance

Place your chosen


image here. The four
corners must just
cover the arrow tips.
For covers, the three
pictures should be the
same size and in a
straight line.

D Balasingam (Bala) & Ian Nuttall


National Grid – Generator & Asset Compliance
Grid Code Requirement

All generators should ride through faults at the nearest


275 kV or 400 kV transmission network
Applies to both balanced & unbalanced faults
Compliance is managed by looking at simulation studies
Type tests are requested on wind turbine types that
constitute more than 100 MW in any one site

2
Type A Faults
 Solid Faults lasting <140 ms
During Type A Faults
 Generator should remain connected without tripping
 Generate maximum reactive current within transient
rating
Following Type A Fault Clearance
 Recovery to at least 90% of pre-fault power within 0.5 s
 Any oscillations must be damped

3
Type B Faults

 Faults lasting > 140 ms


 Residual Voltage > Profile given in CC.6.3.15.1.(b)
During Type B Faults
 Generator should remain connected without tripping
 Provide Active Power at least in proportional to the voltage at the
Grid Entry Point
 Generate maximum reactive current within transient rating
Following Type B Fault Clearance
 Recovery to at least 90% of pre-fault power within 1s
 Any oscillations must be damped

4
CC.6.3.15.1 (b) (i)

5
Type B Faults
 An example Type B fault: Lasting 300 ms with a
residual voltage of 30%
 Therefore it should provide active power proportional to
grid interface voltage during fault and power recovery
within 1s following fault clearance
 Consider a fault lasting 100 ms with a residual voltage
of 30% (Is it type A or type B?)
 It should provide active power proportional to grid
interface voltage during fault
 Power recovery within 0.5 following fault clearance

6
Comparison between UK Grid
Code and the ENTSO-E Proposals

7
ENTSO-E Draft Requirements
 ENTSO-E consultation published in January 2012.

 Includes different envelopes for FRT on different generator sizes and


types.

 Following plots indicate the comparison between current GB Grid Code


and the ENTSO-E proposals for
 Type B & C Synchronous
 Type D Synchronous
 Type B & C Power Park Modules
 Type D Power Park Modules

8
ENTSO-E RfG - Voltage Duration Profiles
Type D Units Table 7.1
Voltage (p.u)
NOT TO SCALE

RFG Min
RFG Max

1.0
0.9
0.85

0.5

0.25

0 0.14 0.25 0.45 0.7 1.5 Time (s)

9
ENTSO-E RfG - Voltage Duration
Profile – Range compared with GB
Requirement
Voltage (p.u)
NOT TO SCALE

RFG Min
RFG Max

1.0
GB Requirement

0.9
0.85
0.8

0.5

0.25
0.15

0 0.14 0.25 0.45 0.7 1.2 1.5 Time (s)

10
ENTSO-E RfG Requirements

 The TSO shall define the Post Fault Active Power Recovery
Characteristics
 The TSO shall define the fault ride through capabilities in the
case of asymmetrical faults.
 In general the Minimum ENTSO-RfG Fault Ride Through
requirements are less onerous than those in GB.
 Interpretation of the ENTSO-E Fault Ride Through
Requirements are further clarified in Question 24 of the FAQ
document.
 https://www.entsoe.eu/resources/network-codes/requirements-for-generators/

 Early adoption of the ENTSO-E RfG may be a possible way


forward subject to National Choice based on Minimum
Transmission System Need and Generator capability.

11
 Any questions?

12

Вам также может понравиться