Building Energy
Efficiency Project
Case Study: Aranya Bhawan, Jaipur
OVERVIEW
Aranya Bhawan, the office building of the Rajasthan Forest Department in Jaipur, was one
of the first projects selected for the BEEP Integrated Design Charrette and the charrette
was held in December 2012. The project was implemented by the Rajasthan State Road
Development Corporation Limited (RSRDC) and was inaugurated on 23rd March, 2015.
PROJECT DETAILS:
• Built-up area: ~10,000m2
(excluding basement
parking and service area)
• Number of floors: Five
(G+4) + one basement
level for parking and
services
• Number of users: 344
• Types of spaces: Offices,
museum, library,
auditorium, guest rooms
During the charrette, energy performance of Aranya Bhawan was simulated, using energy
simulation tool Design Builder/Energy Plus.
Aranya Bhawan qualifies for 5-star rating under the Bureau of Energy Efficiency (BEE)
star rating programme for office buildings.
ENERGY EFFICIENCY MEASURES
BUILDING ENVELOPE
ALUMINIUM FRAME
PLASTER OUTSIDE
115 MM BRICK WALL 6 MM THK TOUGHENED LOW-E GLASS
COOLING SYSTEM
Cooling Tower
The actual energy and thermal performance monitoring of Aranya Bhawan was carried
out by Energetic Consulting Pvt. Ltd. (ECPL). This was primarily done in 2 stages: winter
monitoring was done from 11th January to 25th January, 2016 and summer monitoring
was done from 5th May to 19th May, 2016.
Actual energy
Solar fraction of
performance index
PV system
(EPI)
Electricity end-use
in the building
ENERGY PERFORMANCE MONITORING RESULTS
7
6.1
5.7
5.5
6
5.4
5.3
5.3
5.2
4.9
kWh/m2 .month
4.6
4.5
4.5
5 3.9
3.9
3.9
4
3.4
3.4
3.3
3.2
3
2.0
2
1.4
1.3
1.2
1.1
0
May-15 Jun-15 Jul-15 Aug-15 Sep-15 Oct-15 Nov-15 Dec-15 Jan-16 Feb-16 Mar-16 Apr-16
Simulated EPI Actual EPI
Installed
SPV plant of
40000
kWh/m2 .month
30000
20000
10000
0
May-15 Jun-15 Jul-15 Aug-15 Sep-15 Oct-15 Nov-15 Dec-15 Jan-16 Feb-16 Mar-16 Apr-16
The solar photovoltaic system was commissioned in the month of October 2015. Thus,
till the end of the monitoring period (April 2016), the solar fraction was 5% of the total
electricity consumed in the building. It is expected that the annual solar fraction for
Jan-Dec 2016 would be nearly 20%.
ENERGY PERFORMANCE MONITORING RESULTS
STP
3%
Miscellaneous
7%
Lighting AHU
5% Co n d 15%
e n ser
Office Equipment Pu m
12% p Chiller
26% p
HVAC CT Fan y Pu m 54%
Mis c n d ar
60% ella
neo
4% Se co10%
7% us
STP
2%
Primary Pump
5%
Of the electricity consumed in HVAC, the chillers consume 54%, pumps consume 27% and
the AHU and cooling tower fans consume 19%.
The study also showed that of the 2 operational chillers, one was operating at a better
COP (7.5) than the other (5.5). This could be attributed to fouled tubes of the under-
performing chiller.