Академический Документы
Профессиональный Документы
Культура Документы
Instruction Book
1
OWNERSHIP DATA
Unit type : ..................................................................... Owner's machine No. : ................................................
Motor type : ................................................................. Unit serial No. : ............................................................
Delivery date : .............................................................. Motor serial No. : .........................................................
Service Plan : ................................................................ First start-up date : ......................................................
Selected lubricants
Compressor : ................................................................ Capacity : ......................................................................
Bearing grease type, electric motor ............................
GA 15, GA 18, GA 22
Instruction Book
• Copyright Notice
Any unauthorised use or copying of the contents or any part thereof is
prohibited.
Use only authorised parts any damage or malfunction caused by the use of
unauthorised parts is not covered by warranty or product liability.
www.atlascopco.com
Marketing Handbook
No. 9095 0503 04
2013-05
Table of Contents
1 Safety precautions........................................................................................................ 6
4 Installation ...................................................................................................................32
9095 0503 04 4
Instruction book
6 Maintenance ................................................................................................................45
5 9095 0503 04
Instruction book
1 Safety precautions
Processing of any other gas requires additional safety precautions typical to the application, which
are not included herein.
In addition to normal safety rules, which should be observed with stationary air compressors and
equipment, the following safety directions and precautions are of special importance.
When operating this unit, the operator must employ safe working practices and observe all related
local work safety requirements and ordinances.
The owner is responsible for maintaining the unit in a safe operating condition. Parts and accessories
shall be replaced if unsuitable for safe operation.
Authorized, trained, competent personnel only shall perform installation, operation, maintenance or
repair.
Normal ratings (pressures, temperatures, time settings, etc.) shall be durably marked.
Any modification on the compressor shall only be performed in agreement with Atlas Copco and
under supervision of authorized, competent personnel.
If any statement in this book, especially with regard to safety, does not comply with local legislation,
the stricter of the two shall apply.
These precautions are general and cover several machine types and equipment; hence some
statements may not apply to the unit(s) described in this book.
Apart from general engineering practice in conformity with the local safety regulations, the following
directives are specially stressed:
1. A compressor shall be lifted only with adequate equipment in conformity with local safety rules.
Please consult Atlas Copco to check if a dedicated lifting device is designed for this purpose.
Loose or pivoting parts shall be securely fastened before lifting. It is strictly forbidden to dwell or
stay in the risk zone under a lifted load. Lifting acceleration and retardation shall be kept within
safe limits.
Wear a safety helmet when working in the area of overhead or lifting equipment.
2. Any blanking flanges, plugs, caps and desiccant bags shall be removed before connecting up the
pipes. Any device for protection during transport shall be removed. Distribution pipes and
connections shall be of correct size and suitable for the working pressure. Undersized pipe or
poor routing of pipe will degrade the performance of the compressor.
9095 0503 04 6
Instruction book
3. Place the unit where the air is as cool and clean as possible. If necessary, install a suction duct.
Never obstruct the air inlet. Care shall be taken to minimize the entry of moisture with the inlet
air. Stationary compressors are not designed for outdoor operation.
4. The aspired air shall be free from corrosive chemicals (e.g. sulfur) and flammable fumes or
vapors (e.g. paint solvents that can lead to internal fire or explosion).
5. Air-cooled units shall be installed in such a way that an adequate flow of cooling air is available
and that the exhausted air does not recirculate to the inlet.
6. Arrange the air intake so that loose clothing of people cannot be sucked in.
7. Ensure that the discharge pipe from the compressor to the after-cooler or air net is free to expand
under heat and that it is not in contact with or close to flammable material.
8. No external force may be exerted on the air outlet valve; the connected pipe must be free of
strain.
9. If remote control is installed, the unit shall bear an obvious sign reading: “DANGER: This
machine is remotely controlled and may start without warning.”
As a further safeguard, persons switching on remotely controlled units shall take adequate
precautions to ensure that there is no one checking on or working on the machine. To this end, a
suitable notice shall be affixed to the start equipment.
10. On units with automatic start-stop system, a sign stating “This machine may start without
warning.” Shall be attached near the instrument panel.
11. Manual valves shall be installed to isolate each compressor from other compressors or from the
system air pressure. Non-return valves (check valves) shall not be relied upon for safely isolating
pressure systems A check valve in the air piping from the compressor can interfere with the
proper operation of the compressor controls.
12. Never remove or tamper with the safety devices, guards or insulations fitted on the unit. Every
pressure vessel or auxiliary installed outside the unit to contain air above atmospheric pressure
shall be protected by a pressure-relieving device or devices as required.
13. Pipework or other parts with a temperature in excess of 70°C and which personnel in normal
operation may accidentally touch, shall be guarded or insulated. Other high-temperature
pipework shall be clearly marked.
14. If the ground is not level or can be subject to variable inclination, consult Atlas Copco.
15. Never drill holes in an electrical cabinet. Small metallic burrs can cause short-circuits in electrical
components.
16. Make sure to avoid condensation on electrical components (e.g. cubicle, Elektronikon and
frequency converter).
17. To preserve the protection of the electric cabinet and to protect its components from dust from
the environment and the entry of moisture in the electrical cabinet, it is absolutely necessary to
use a proper cable gland when connecting the power supply cable to the compressor.
Use of an improper cable gland can result in damage to or failure of the equipment. This
could also result in fire and fatalities.
18. For shipboard applications where variable inclination is expected, consult Atlas Copco’s line of
dedicated Marine equipment.
19. Avoid contact with sharp edges or hot surfaces to prevent damage to cable insulation.
20. The unit shall be protected against short circuits by fuses or adequate circuit breakers.
21. The customer shall provide a main disconnecting device in the compressor room.
7 9095 0503 04
Instruction book
22. Before initial start-up and after service interventions, make sure the following final inspection
checks are made:
a. Inspect all electrical connections to verify there are no loose connections and all are tightened
correctly.
b. Check for strain relief on the (main) power cables.
c. Verify that the power requirement for the unit has been provided for by referencing to the unit
power label on the inside of the electrical cabinet door of the unit.
d. The branch circuit protection and supply cable size for the compressor must be sized to meet
the power requirement per local electrical codes.
e. Verify that the unit is correctly grounded using the proper size of wire connected to a tested
earth ground.
An improper electrical installation can result in damage to or failure of the equipment. This
could also result in fire and fatalities.
23. Before initial start-up and after service interventions, make sure the following final mechanical
inspection checks are made:
a. Inspect all connections to make sure they are tight, sealed and secured.
b. Visually inspect metal or nylon tubing located in the compressor. Tubes can come loose or
get damaged in shipping. Verify the flexibility of the nylon tubes while inspecting for damage.
Verify that all tubes are secure in their fittings to insure that none might leak or come loose
when the compressor is in operation.
Damaged or loose tubes can result in lubricant being sprayed on hot surfaces when the
compressor is in operation and result in damage to the compressor or fire.
After inspection, the power can be put to the installed compressor. With the proper power applied, the
rotation of the compressor and the cooling fan can be verified.
1. Air hoses shall be of correct size and suitable for the working pressure. Never use frayed,
damaged or deteriorated hoses. Use only the correct type and size of hose end fittings and
connections. When blowing through a hose or airline, ensure that the open end is held securely.
A free end will whip and may cause injury. Make sure that a hose is fully depressurized before
disconnecting it.
2. Never play with compressed air. Do not apply it to your skin or direct an air stream at people.
Never use it to clean dirt from clothes. When using it to clean equipment, do so with extreme
caution and use eye protection.
3. The compressor is not considered as capable of producing air for breathing quality. For breathing
air quality, the compressed air must be adequately purified according to local legislation and
standards.
4. Never operate the unit when there is a possibility of taking in flammable or toxic fumes.
5. Never operate the unit at pressures below or in excess of its limit ratings as indicated on the
Principal Data sheet.
6. Keep all bodywork doors shut during operation. The door may be opened for short periods only,
e.g. to carry out checks. Wear ear protection when opening a door.
9095 0503 04 8
Instruction book
7. People staying in environments or rooms where sound pressure level reaches or exceeds 90dB
(A) shall wear ear protection.
8. Periodically check that:
a. All guards are in place and securely fastened.
b. All hoses, tubes and / or pipes inside the unit are in good condition, secure and not rubbing.
c. There are no leaks.
d. All fasteners are tight.
e. All electrical cables are secure and in good order.
f. Safety valves and other pressure-relief devices are not obstructed by dirt or paint.
g. Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in good
repair, free of wear or abuse.
h. There is no excess of dust in the electrical cabinet.
9. If warm cooling air from compressors is used in heating systems, e.g. to warm up a workroom,
take precautions against air pollution and possible contamination of the breathing air.
10. Do not remove any of or tamper with the sound-damping material.
Maintenance and repair work shall only be carried out under supervision of someone qualified for
the job.
To maintain warranty and to insure the compressor operates correctly and safely, genuine parts
must be used. Use of non-genuine parts, failure to correctly install equipment or perform
recommended scheduled maintenance will void warranty and result in damage to or failure of the
equipment. This could also result in fire and fatalities.
Before performing any maintenance, stop the compressor, close the shut-off valve at the unit
discharge, remove all electrical power from the equipment, verify the receiver tank on the unit is at
zero pressure and let the machine cool down. Take positive precautions to ensure that the unit
cannot be started inadvertently by following a lock-out tag-out procedure. In addition, a warning sign
bearing a legend such as “work in progress; do not start” shall be attached to the starting
equipment.
1. Before removing any pressurized component, effectively isolate the unit from all sources of
pressure and relieve the entire system of pressure and electrical power. Take positive
precautions to ensure that the unit cannot be started inadvertently. In addition, a warning sign
bearing a legend such as “work in progress; do not start” shall be attached to the starting
equipment.
2. Protect hands to avoid injury from hot machine parts, e.g. during draining of oil.
3. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety precautions
against toxic vapors of cleaning liquids.
Never use caustic solvents, which can damage materials of the air net, e.g. polycarbonate bowls.
4. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by covering the
parts and exposed openings with clean cloth, paper or tape. Make sure that no tools, loose parts
or rags are left in or on the unit.
9 9095 0503 04
Instruction book
5. Never weld or perform any operation involving heat near the oil system. Oil tanks must be
completely purged, e.g. by steam-cleaning, before carrying out such operations. Never weld on,
or in any way modify, pressure vessels.
Whenever there is an indication or any suspicion that an internal part of a machine is overheated,
the machine shall be stopped but no inspection covers shall be opened before sufficient
cooling time has elapsed; this to avoid the risk of spontaneous ignition of the oil vapor when air is
admitted.
Never use a light source with open flame for inspecting the interior of a machine,
pressure vessel, etc.
6. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture from
entering them, e.g. when steam-cleaning or due to condensation of humid ambient air.
7. If the branch circuit is provided using a fused disconnect to supply power to the compressor, then
verify that all the fuses are of the same type and properly sized. If a circuit breaker is used to
supply power, verify that it is properly sized.
8. Visually inspect and verify that the connections at the branch circuit protection device are tight
and the wire insulation is not degraded.
9. Visually inspect the wire from the branch circuit protection device to the compressor starter to
verify that it is sized correctly and in good order.
10. Verify that the power wire and ground connections at the compressor starter are tight and in good
order.
11. Verify that the wire connections from the compressor starter to the compressor motor are tight
and in good order.
12. Replace filters in the electrical cabinet when they are saturated with dust.
13. Check if the sealing of the electrical cabinet is in perfect condition. If not, replace it.
14. Inspect all tubing in the compressor for possible leaks or normal aging and replace with genuine
parts if needed.
15. Verify if all tube fittings are tight and tubes are securely held in the fittings.
16. Also check all nylon tubes for chaffing, cracks and flexibility and replace with genuine parts to
insure safe operation.
17. Drain any condensate that may have collected in the receiver tank.
18. Take oil samples for evaluation and be sure to mark with customer name, compressor model,
compressor serial number and running hours of the compressor. Respect oil service intervals.
Oxidized oil will result in higher compressor temperatures that could result in fire.
19. Replace oil with genuine compressor oil of the same type when needed.
Low oil will result in oil foaming, oil carry over and higher compressor temperatures that
could result in fire.
20. Replace all consumables at recommended service intervals or sooner if operating conditions
warrant or replace every 12 months.
21. Make sure that all sound-damping material, e.g. on the bodywork and in the air inlet and outlet
systems of the compressor, is in good condition. If damaged, replace it by genuine material to
prevent the sound pressure level from increasing.
22. Every time the separator element is renewed, examine the discharge pipe and the inside of the
oil separator vessel for carbon deposits; if excessive, the deposits should be removed.
9095 0503 04 10
Instruction book
23. Before clearing the unit for use after maintenance or overhaul, check that operating pressures,
temperatures and time settings are correct and that the control and shutdown devices function
correctly. If removed, check that the coupling guard of the compressor drive shaft has been
reinstalled.
24. The following safety precautions are stressed when handling refrigerant:
a. Never inhale refrigerant vapors. Check that the working area is adequately ventilated; if
required, use breathing protection.
b. Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin with
water. If liquid refrigerant contacts the skin through clothing, never tear of or remove the
latter; flush abundantly with fresh water over the clothing until all refrigerant is flushed away;
then seek medical first aid.
c. Always wear safety glasses.
Poor maintenance or use of non-genuine parts will cause equipment failure and possibly result in
fire.
Before decommissioning, stop the compressor, close the shut-off valve at the unit discharge,
remove all electrical power from the equipment, verify the receiver tank on the unit is at zero
pressure and let the machine cool down. Take positive precautions to ensure that the unit cannot be
started inadvertently. In addition, a warning sign bearing a legend such as “work in progress; do
not start” shall be attached to the starting equipment.
1. Before performing other work on the compressor, remove the power cable from the power
supply.
2. Before removing any pressurized component, effectively isolate the unit from all sources of
pressure and relieve the entire system of pressure.
3. Protect hands to avoid injury from hot machine parts, e.g. during draining of oil.
4. Drain any condensate that may have collected in the receiver tank.
5. The following safety precautions are stressed when handling refrigerant:
a. Never inhale refrigerant vapors. Check that the working area is adequately ventilated; if
required, use breathing protection.
b. Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin with
water. If liquid refrigerant contacts the skin through clothing, never tear of or remove the
latter; flush abundantly with fresh water over the clothing until all refrigerant is flushed away;
then seek medical first aid.
c. Always wear safety glasses.
6. Dispose of the compressor according to local waste handling regulations.
11 9095 0503 04
Instruction book
2 General description
2.1 Introduction
lntroduction
GA 15 up to GA 22 are single-stage, oil-injected screw compressors driven by an electric motor.
The compressors are air-cooled.
GA Pack
GA Pack are enclosed in sound-insulated bodywork. The compressors are controlled by the
Atlas Copco ES99 I regulator. The electronic control module is fitted to the door on the front side.
An electric cabinet comprising the motor starter is located behind this panel.
9095 0503 04 12
Instruction book
GA 15 up to GA 22 Tank-mounted are mounted on a large air receiver (AR) of 500 l (125 gal, 4.5
cu.ft)
Reference Name
AF Air filter
AR Air receiver
AV Air outlet valve
Ca Air cooler
Co Oil cooler
Dm1 Manual drain, air receiver
E1 Control panel
M1 Drive motor
MT Condensate trap
OF Oil filter
OS Oil separator
OT Oil tank
S3 Emergency stop button
13 9095 0503 04
Instruction book
GA Full-Feature
GA Full-Feature (FF) are controlled by the Atlas Copco ES99. They are provided with an air dryer
integrated in the sound-insulated bodywork. The dryer removes condensate from the compressed
air by cooling the air to near freezing point and automatically draining the condensate
GA 15 up to GA 22 Tank-mounted are mounted on a large air receiver (AR) of 500 l (125 gal, 4.5
cu.ft)
9095 0503 04 14
Instruction book
Reference Name
AF Air filter
AR Air receiver
AV Air outlet valve
Ca Air cooler
Co Oil cooler
Reference Name
Dm1 Manual drain, air receiver
DR Dryer
ER1 Elektronikon I regulator
M1 Drive motor
OF Oil filter
OS Oil separator
OT Oil tank
S3 Emergency stop button
15 9095 0503 04
Instruction book
Reference Description
A Intake air
B Air/oil mixture
C Oil
D Wet compressed air
F Condensate
G Dry compressed air
Description
Air drawn through filter (AF) and open inlet valve (IV) into compressor element (E) is compressed.
Compressed air and oil flow into the oil tank (OT). The air is discharged through outlet valve (AV) via
minimum pressure valve (Vp) and air cooler (Ca).
Pack units are provided with a condensate trap (MT).
9095 0503 04 16
Instruction book
On Full-Feature compressors, the air flows through air dryer (DR) before it is discharged through
outlet valve (AV). Also see section Air dryer IFD.
Flow diagram
Oil system
References Description
1 For Pack units, compressed air flow to the condensate trap
For Full-Feature units, compressed air flow to the air dryer
A Air intake
B Air/oil mixture
C Oil
D Wet compressed air
F Condensate
Description
In oil tank (OT) most of the oil is removed from the air/oil mixture centrifugally. The rest is removed by
oil separator (OS). The oil collects in the lower part of oil tank (OT).
Air pressure forces the oil from oil tank (OT) through oil cooler (Co) and filter (OF) to compressor
element
(E) and the lubrication points.
Thermostatic by-pass valve (BV) starts opening the supply from cooler (Co) when the oil temperature
has increased to the set point. At approx. 15 ·C (27 ·F) above the set point, all the oil flows through the
oil cooler.
17 9095 0503 04
Instruction book
Flow diagram
Cooling system
References Description
A Intake air
B Air/oil mixture
C Oil
D Wet compressed air
E Condensate
Description
The cooling system comprises air cooler (Ca) and oil cooler (Co). The cooling air is generated by the
drive motor fan (FN).
9095 0503 04 18
Instruction book
Condensate drains
Pack units have a condensate trap (MT). The condensate trap is provided with a manual drain (Dm)
and an automatic drain (Da).
Full-Feature units have an electronic drain (1). The electronic drain is provided with an automatic
drain (Da). Tank-mounted units are provided with an additional manual drain on the air receiver.
19 9095 0503 04
Instruction book
Flow diagram
Regulating system of GA 15 up to GA 22
Unloading
If the air consumption is less than the air output of the compressor, the net pressure increases.
When the net pressure reaches the unloading pressure, solenoid valve (Y1) is de-energised. The
plunger of the valve returns:
• Solenoid valve (Y1) de-activates unloading valve/blow-off valve (UV).
• Unloading valve/blow-off valve (UV) connects the air receiver pressure (1) with chamber (2)
and to the blow-off opening (3).
• The pressure in chamber (2) causes the loading plunger (LP) to move upwards.
• The pressure is stabilised at low value. A small amount of air is kept drawn in and is
blown to the unloader.
Loading
When the net pressure decreases to the loading pressure, solenoid valve (Y1) is energised. The
plunger of solenoid (Y1) moves upwards:
• Solenoid valve (Y1) controls the unloading valve/blow-off valve (UV).
• Unloading valve/blow-off valve (UV) closes the air blow-off opening (3) and shuts off the
supply to chamber (2).
This causes loading plunger (LP) to move downwards and inlet valve (IV) to open fully. Air delivery is
resumed (100%), the compressor runs loaded.
9095 0503 04 20
Instruction book
Electrical components
The electrical system comprises following components:
Reference Designation
F1/2/3 Fuses
F4/5/6 Fuses
F7/8 Fuses for dryer (only on Full-Feature compressors)
F21 Overload relay, compressor motor
K11 Auxiliary contactor for dryer (only on Full-Feature compressors)
K21 Line contactor
K22 Star contactor
K23 Delta contactor
Reference Designation
T1/T3 Transformers
1X0 Terminal strip (voltage supply)
1X1 Terminal strip (motor)
X103/X108 Connectors
PE Earth terminal
21 9095 0503 04
Instruction book
9095 0503 04 22
Instruction book
Reference Compressor
T1 Transformer
K25 Phase sequence relay
K22 Start contactor
K23 Start contactor
K21 Line contactor
F1 Fuse
F2 Fuse
F3 Fuse
F21 Overload relay, compressor motor
23 9095 0503 04
Instruction book
Description
Air dryer
Compressed air enters heat exchanger (10) and is cooled by the outgoing, cold, dried air. Water in
the incoming air starts to condense. The air then flows through heat exchanger/evaporator (4)
where the refrigerant evaporates causing the air to be cooled further to close to the evaporating
temperature of the refrigerant. More water in the air condenses. The cold air then flows through
separator (5) where all the condensate is separated from the air. The condensate is automatically
drained. The cold, dried air flows through heat exchanger (10) where it is warmed up by the
incoming air.
9095 0503 04 24
Instruction book
3 Controller ES99
3.1 General description
ES99 is a control box for small and medium capacity compressors.
The board enables to manage all the operations concerning starting and stopping of the compressor. The same
board checks the status of the machine and informs about defaults.
Description Contact
Description Contact
25 9095 0503 04
Instruction book
9095 0503 04 26
Instruction book
3.1.6 Keyboard
This is the layout of the keyboard
By pushing the button, the compressor starts. This feature is valid if the
2
remote control is not activated.
27 9095 0503 04
Instruction book
9095 0503 04 28
Instruction book
3.2.2 Stopping
By pushing the button during the first two positions of starting, it makes the sudden stop of the compressor. If
the button is pushed when the star power relay is activated , the stopping procedure starts by counting the
length of time set in “t_spegn” on which the compressor runs in no-load mode with the solenoid valve not
energised. During all stopping procedure, the light 8 blinks. If the electronic control box is in “Stand-by” status,
pushing the stopping button makes the cancellation of all running procedures.
3.2.3 Stand By
In absence of air compressed needs from the user and with the pressure value over Pmax (signal from
pressure switch open), the compressor run in no load.
In order to reduce the energy costs, the compressor stops (stand-by) as soon as the following criteria are
matched:
1. Number of starting per hour .
2. When the compressor is still, starting must be immediate in order to supply satisfy the needs of the
user.
3. The time of no load before to stop the compressor in the case of no demand of air from the user,
must be the shortest as possible, compatible with the point 1).
The following is the criteria followed by the electronic board to define the time of no load before to stop
the compressor:
• When the compressor reached the maximum pressure for the first time, the no load time is set up to
30 seconds. This parameter is not changeable.
• When the compressor reaches the maximum pressure after the first cycle, the electronic card starts
to count the time of no load. If this time is lower than TX_1 (or TX_2 depending if the bridge is open
or closed) the next cycle the compressor will run in no load for all TY_1 (or TY_2 depending from the
• bridge 3 and 7)
• On the other hand, if the time of no load is bigger than TX_1 (or TX_2 depending if the bridge is
open or closed) the next cycle the compressor will run only for 30 seconds in no load.
29 9095 0503 04
Instruction book
3.2.5 Test
By pushing the button for a time less than 3 seconds, you clear all the alarms recorded by the
electronic control box; if you keep pushing for more than 3 seconds an automatic procedure is starting
to verify the good operational of the control box.
3.2.6 Alarms
The alarms controlled by the electronic control box are:
Overload electric motor
Wrong rotation
Over temperature
Emergency
9095 0503 04 30
Instruction book
In case of one of the above alarms, the compressor is immediately stopped and the related light shows
the reason. Flashing of the light shows that the alarm is still on, while fixed light turned on means
waiting for reset.
3.3 CONNECTIONS
3.3.1 Terminal board
1 12 Vac energy supply
2 12 Vac energy supply
3 Signal input ground
4 Overload thermal motor input
5 Wrong rotation input
6 Oil over temperature input
7 Time mode selection input
8 Connection to the ground
9 NC
10 Pressure switch input
11 Remote control input
12 Emergency push button input
13 NC
14 Signal input ground
15 NC
16 Star relay output connection
17 Power relay output connection
18 Delta relay output connection
19 Signal output ground
20 Solenoid valves output
ti
3.3.2 Circuit diagram
31 9095 0503 04
Instruction book
4 Installation
4.1 Dimension drawings
Dimension drawings, GA 15 up to GA 22
9095 0503 04 32
Instruction book
33 9095 0503 04
Instruction book
9095 0503 04 34
Instruction book
35 9095 0503 04
Instruction book
Ref. Name
1 Compressor air inlet
2 Motor and cooling air inlet
3 Compressed air outlet
4 Motor and compressor cooling air outlet
5 Electrical cable entry
6 Dryer cooling air inlet
7 Dryer cooling air outlet
8 Automatic drain
9 Manual drain
9095 0503 04 36
Instruction book
Description
1 Install the compressor unit on a solid, level floor suitable for taking the weight.
Recommended minimum distance between top of the unit and ceiling is 900 mm (35
in). Distance between unit and walls stated are minimum.
* Recommed distance is 500 mm for easy access.
Air receiver may not be bolted to the ground.
2 Position of the compressed air outlet valve (can be located on both sides of the air
receiver).
3 The maximum total pipe length (including interconnecting piping between compressor
and receiver) can be calculated as follows:
dp = (L x 450 x Qc1.85) / (d5 x p)
d = Inner diameter of the outlet pipe in mm
dp = Pressure drop (recommended maximum = 0.1 bar/1.5 psi)
L = Length of outlet pipe in m
p = Absolute pressure at the compressor outlet in bar(a)
Qc = Free air delivery of the compressor in l/s
4 Ventilation: the inlet grids and ventilation fan should be installed in such a way that any
recirculation of cooling air to the compressor is avoided. The maximum air velocity
through the grids is 5 m/s (16.5 ft/s).
Cooling air ducts are not allowed.
The maximum air temperature at the compressor intake is 46 ·C (115 ·F) (minimum 0
·C / 32 ·F).
Qv = Required ventilation capacity in m 3/s
N = Shaft input of compressor in kW
dT = Temperature increase in compressor room
5 Mains cable entry.
37 9095 0503 04
Instruction book
4.4 Pictographs
Pictographs GA 15 up to GA 22
Reference Designation
1 Warning: before connecting compressor electrically, consult Instruction book for motor
rotation direction
2 Torques for steel (Fe) or brass (CuZn) bolts
3 Warning: suction
4 Lightly oil gasket of oil filter, screw filter on and tighten by hand (approx. half a turn)
5 Consult the instruction book before carrying out maintenance
6 Warning: voltage
7 Warning: hot parts
8 Lock all doors of the bodywork before starting.
• If the sheet is pulled downwards: stop the compressor and switch off the voltage.
• Reverse two incoming lines. Repeat the previous step.
• If the sheet is blown away the motor rotation is correct.
9095 0503 04 38
Instruction book
5 Operating instructions
Safety
The operator must apply all relevant safety precautions, including those mentioned in
this book.
Outdoor/altitude operation
If the compressor is installed outdoors or if the air inlet temperature can be below 0 ·C/32 ·F,
precautions must be taken. In this case, and also if operating above 1000 m (3300 ft), consult Atlas
Copco.
Moving/lifting
Floor-mounted unit: the compressor can be moved by a lift truck. Take care not to damage any
installed connections under the frame while moving the truck or compressor. For lifting make sure
that the forks are long enough to give a stable support for the compressor.
Tank-mounted unit: Move the compressor by a lift truck by positioning the forks below the lifting
supports that are mounted between the feet of the air receiver. Make sure that the forks are
positioned in the centre of the air receiver and lift carefully.
Have the modifications checked by Atlas Copco. Stop the compressor and switch off the
voltage before connecting external equipment. Only voltage-free contacts are allowed.
39 9095 0503 04
Instruction book
Procedure
For the location of the air outlet valve and the drain connections, see sections
Introduction and Condensate system.
9095 0503 04 40
Instruction book
Electric cubicle
41 9095 0503 04
Instruction book
1 Consult the sections Electric cable size,Installation proposals and Dimension drawings
2 The following transport fixtures, painted red, must be removed:
• Bolts (1)
• Bushes (2)
• Supports (3)
3 Check that the electrical connections correspond to the local codes and that all wires are clamped
tight to their terminals.
The installation must be earthed and protected against short circuits by fuses of the inert type in all
phases. An isolating switch must be installed near the compressor.
9 Affix sheet (5) explaining the procedure for checking the motor rotation direction to the cooling air
outlet of the compressor. Consult section Dimension drawings.
Switch on the voltage. Start the compressor and stop it immediately. Check the rotation direction of
drive motor (M1) while the motor is coasting to a stop.
Check the motor rotation of the motor using sheet (5). If the motor rotation direction is correct, the
label on the top grating will be blown upwards. If the sheet remains in place, the rotation direction is
incorrect.
If the rotation direction of the drive motor is incorrect, open the isolating switch and reverse two
incoming electric lines.
Optional phase sequence relay:
• If the compressor should fail to start, check the display.
• If the display shows the pictograph for motor overload, check the phase sequence relay.
Incorrect rotation direction of the drive motor may cause damage to the compressor.
10 On compressors equipped with an Elektronikon I regulator, check the settings; see section Settings.
11 Start and run the compressor for a few minutes. Check that the compressor operates normally.
9095 0503 04 42
Instruction book
Procedure
1 Check the oil level, top up if necessary. See section Initial start-up.
5.4 Starting
Procedure
Please check the section Starting from Controller ES99
Procedure
The operator must apply all relevant Safety precautions. Also consult section Problem
solving.
Removing the front panel (service panel) during operation will lead to an automatic
shutdown of the unit after a certain time depending of the compressor version.
43 9095 0503 04
Instruction book
Press the stop button, close the air outlet valve and open (if provided) the manual condensate drains.
See section Introduction and section Condensate system for location of the outlet valve and water
drain.
Press the emergency stop button.
Regularly check the oil level. Three minutes after stopping, sight-glass (Gl) should be between 1/4
and 3/4 full. Wait until the compressor has stopped (40 seconds), depressurise the oil system by
unscrewing oil filler plug (FC) one turn and wait a few minutes. Remove the plug and top up oil, until
the sight-glass is full. Fit and tighten the plug (FC).
When automatic operation LED (8) is lit, the regulator is automatically controlling the
compressor, i.e. loading, unloading, stopping of the motors and restarting.
Regularly check that condensate is discharged during operation. See section Condensate system.
5.6 Stopping
Please check the section Stopping from Controller ES99
9095 0503 04 44
Instruction book
6 Maintenance
Service kits
For overhauling or carrying out preventive maintenance, service kits are available (see section Service
kits).
Service contracts
Atlas Copco offers several types of service contracts, relieving you of all preventive maintenance
work. Consult your Atlas Copco Customer Centre.
General
When servicing, replace all removed gaskets, O-rings and washers.
General
Period Operation
Yearly Replace DDx and PDx filters or whenever the pressure indicator points red.
Inspection of the wall thickness of the air receiver. Minimum wall thickness as specified
in respected. Local legislation overrules when more strict.
45 9095 0503 04
Instruction book
For GA 15 upto GA 22
Recommended
Oil temperature End pressure oil service Max. time
(°C) (bar) interval (running interval (years)
hours)
<110 <14 8000 2
>110 <14 6000 2
>105 >14 4000 2
GAR Applications 4000 2
lmportant
9095 0503 04 46
Instruction book
For GA 15 up to GA 22
It is strongly recommended to use Atlas Copco Fluid (see section Preventive maintenance schedule).
47 9095 0503 04
Instruction book
Warning
Procedure
9095 0503 04 48
Instruction book
1 Run the compressor until warm. Stop the compressor after 3 minutes of unloaded operation.
Close the air outlet valve and switch off the voltage. Wait a few minutes and depressurise by
unscrewing oil filler plug (FC) just one turn to permit any pressure in the system to escape.
Also open (if provided) the manual condensate drains.
2 Remove oil drain plug (DP1). Drain the oil by opening valve (Vd). Also remove the drain plug on
the flexible (1) near the element and the vent plug on the oil cooler. Close the valve and fit the
plugs after draining.
3 Collect the oil in a collector and deliver it to the local collection service. Refit and tighten the drain
and vent plugs after draining.
4 Remove the oil filter (OF). Clean the seat on the manifold. Oil the gasket of the new filter and
screw it into place. Tighten firmly by hand.
5 Remove filler plug (FC).
On GA 15 up to GA 22, insert an elbow coupling in the filler plug (FC) for easy filling. Fill the oil
tank (OT) with oil until the level reaches the middle of sight-glass (Gl).
Take care that no dirt drops into the system. Refit and tighten filler plug (FC).
6 Run the compressor loaded for a few minutes. Stop the compressor and wait a few minutes to
allow the oil to settle.
7 Depressurise the system by unscrewing filler plug (FC) just one turn to permit any pressure in the
system to escape. Remove the plug.
On GA 15 up to GA 22, fill the oil tank with oil until the sight-glass (Gl) is 3/4 full.
Tighten the filler plug.
8 • Reset the service timer:
• For compressors equipped with an Elektronikon I regulator, see section Calling up resetting
service timer
Warning
49 9095 0503 04
Instruction book
Procedure
1 Run the compressor until warm. Stop the compressor, close the air outlet valve and
switch off the voltage. Wait a few minutes and depressurise by unscrewing oil filler plug
(FC) just one turn to permit any pressure in the system to escape.
2 Wait 5 minutes and remove the oil separator (OS). Clean the seat on the manifold. Oil
the gasket of the new separator and screw it into place. Tighten firmly by hand.
3 Run the compressor loaded for a few minutes. Stop the compressor and wait a few
minutes to allow the oil to settle.
4 Depressurise the system by unscrewing filler plug (FC) just one turn to permit any
pressure in the system to escape. Remove the plug.
Fill the oil tank with oil until the sight-glass (Gl) is 3/4 full.
Tighten the filler plug.
5 • Reset the service timer:
• For compressors equipped with an Elektronikon I regulator, see section Calling up
resetting service timer
If the compressor is going to be stored without running from time to time, protective
measures must be taken. Consult Atlas Copco
9095 0503 04 50
Instruction book
Description
Service kits are available offering the benefit of genuine Atlas Copco parts while keeping the
maintenance budget low. The kits comprise all parts needed for servicing.
Service kit for oil filters and air filters Ordering number
GA 15 up to GA 22 for 4000 running hours (filters 2901 0866 01
and oil separator)
For GA 15 up to GA 22, cubicle filter element 1089 9556 23
Service kits GA 15 up to GA 22
Ordering number
5-litre can 2901 1700 00
20-litre can 2901 1701 00
209-litre drum 2901 1702 00
51 9095 0503 04
Instruction book
Air filter, GA 15 up to GA 22
Recommendations
1. Never remove the element while the compressor is running.
2. For minimum down-time, replace the dirty element by a new one.
3. Discard the element when damaged.
Procedure
1. Stop the compressor. Switch off the voltage.
2. On Pack units: remove the side panel.
On Full-Feature units: remove the front panel.
3. Remove the air filter assembly.
4. Remove the cover of air filter (AF) by turning it anti-clockwise. Remove the filter element. If
necessary, clean the cover.
5. Fit the new element and the cover.
6. Reset the air filter service warning.
Consult section Calling up/resetting service timer to reset the service warning on Elektronikon I
regulators.
9095 0503 04 52
Instruction book
7.2 Coolers
Cleaning
Keep the coolers clean to maintain efficiency
On air-cooled compressors:
• Stop the compressor, close the air outlet valve and switch off the voltage.
• Cover all parts under the coolers.
• Remove any dirt from the coolers with a fibre brush. Never use a wire brush or metal objects.
• Then clean with an air jet in the reverse direction to normal flow.
• If it is necessary to wash the coolers with a cleaning agent, consult Atlas Copco.
GA 15 up to GA 22
53 9095 0503 04
Instruction book
Operating
Operate the safety valve by unscrewing the cap one or two turns and retightening it.
Testing
Before removing the valve, depressurise the compressor.
See section Problem solving
Valve (SV) can be tested on a separate air line. If the valve does not open at the set pressure
stamped on the valve, consult Atlas Copco.
Valve (SV1) is fitted on tank-mounted versions. The valve can be tested on a separate air line. If
the valve does not open at the set pressure stamped on the valve, consult Atlas Copco.
Warning
No adjustments are allowed. Never run the compressor without safety valve.
9095 0503 04 54
Instruction book
8 Problem solving
55 9095 0503 04
Instruction book
9095 0503 04 56
Instruction book
57 9095 0503 04
Instruction book
9 Technical data
9.1 Electric cable size
Attention
Local regulations remain applicable if they are stricter than the values proposed below.
The voltage drop must not exceed 5% of the nominal voltage. It may be necessary to
use cables of a larger size than those stated to comply with this requirement
Cable size
GA 15 GA 18 GA 22
Frequency Hz Voltage (V} Cable size Cable size Cable size
General
The regulating and safety devices are factory-adjusted to give optimum performance
of the dryer. Do not alter the setting of any of the devices.
9095 0503 04 58
Instruction book
Reference conditions
Limits
59 9095 0503 04
Instruction book
Reference conditions
All data specified below apply under reference conditions, see section Reference
conditions and limitations
GA 15
Pressure drop over dryer, Full- bar(e) 0.25 0.25 0.25 0.25
Feature units
9095 0503 04 60
Instruction book
Instrictions
4
5
6
7
8 Yearly service inspection of the air receiver by a notified body is needed, as internal
corrosion can reduce the steel wall thickness with the consequent risk of bursting.
Minimum wallthickness as specified in the instruction book should be respected. Local
legislation overrules when more stric. The use of the air receiver is forbidden once the wall
thickness reaches the minimum value as indicated in the service manual of the air receiver
(part of the documentation delivered with the unit).
61 9095 0503 04
Instruction book
9095 0503 04 62
Instruction book
63 9095 0503 04