Evaporation Losses in Cooling Tower (by AE)

1 L1 =𝐿2 −𝐺 𝑊2 + GW1

Flow rate of water returning to cooling tower 100 = 1962 m3/hr


Flow rate of air per fan = 172.88
Number of fans in operation = 3
Flow rate of air entering cooling tower = 518.64
Dry bulb temperature = 45 °C
318 K
Atmospheric pressure at altitude of CT-100 93743 Pa
Gas constant = R = 8.314 Nm/gmol-K
Molecular weight of air = 29
Density of air Entering CT-100 = 1.028 Kg/m3
G1 = G2 = G = Flow rate of air entering = Flow rate of air leaving = 1919851
Relative humidity of air entering cooling tower = 32.2%
Vapor pressure of water at dry bulb temp by antoine equation = 71.70 mmHg
9560 Pa
Since % Relative humidity = (Pw/Pw0)
Partial pressure of water = 3077 Pa

Pressure of air at inlet of CT-100 11.97 mmwater


Pressure of air at inlet of CT-100 121 Pag
93864 Pa
Humidity of air entering CT-100 = 0.0210 Kg water/Kg air

Relative humidity of air leaving CT-100 90.0%


Dry bulb Temperature of air leaving CT-100 = 32 °C
Vap pressure of water at temp of air leaving CT-100 = 35.57 mmHg
4743 Pa
Partial pressure of water in air leaving CT-100 = 4268 Pa
Pressure of air at outlet of CT-100 93743 Pa
Humdity of air leaving CT-100 0.0296 Kg water/Kg air

L2 =flow rate of water entering CT-100 = 1962000 Kg/hr

L1 =𝐿2 −𝐺 𝑊2 + GW1
1945546 Kg/hr
Evaporation loss = 16454 Kg/hr
16.5 m3/hr
0.84% of circulating water