Вы находитесь на странице: 1из 9

(/) (/search)


Share

Codes & Integrated Systems Safety Your Business Lighting


Standards (/section/integrated- (/section/safety) (/section/your- (/section/li
(/section/codes- systems) business)
standards)

Codes & Standards (/section/codes-


standards)
Branch-Circuit, Feeder and
Service Calculations, Part XLII
By Charles R. Miller (/contributing-authors/charles-r-
miller)
 Published In August 2009

As stated in the introduction, the purpose of the National Electrical

Code (NEC) is the practical safeguarding of people and property from

hazards arising from the use of electricity [90.1(A)]. Ensuring branch

circuits, feeders and services are not undersized is one aspect of

practical safeguarding. Requirements for calculating branch-circuit,

feeder and service loads are provided in Article 220. Results from

these calculations are then used to size conductors and overcurrent

protective devices. While the size of the grounded or neutral conductor

could be the same as the ungrounded (hot) conductors, it may be

possible to reduce the size and still be in compliance with the National

Electrical Code (NEC). Depending on the system and the load, the

current draw on the neutral or grounded conductor could be

significantly less than the current draw on the ungrounded conductors.

While most of the requirements in Article 220 pertain to calculating

loads on ungrounded conductors, one section pertains to calculating

neutral loads. Provisions in 220.61 cover basic calculations, permitted

reductions and prohibited reductions for feeder or service neutral

loads. Because there are no neutral load calculation procedures in Part

IV, Optional Feeder and Service Load Calculations, all neutral loads

must be calculated in accordance with 220.61. Therefore, calculate the

neutral load in accordance with 220.61 regardless of whether the

feeder or service calculation was performed in accordance with the

standard method or optional method.

Last month’s column concluded by covering grounded-conductor

identification. This month, the discussion continues with feeder or

service neutral loads as specified in 220.61.


The feeder or service neutral load is the maximum unbalance of the

load determined by Article 220. As stated in 220.61(A), the maximum

unbalanced load shall be the maximum net calculated load between

the neutral conductor and any one ungrounded conductor. When

calculating the neutral load, it is not necessary to include loads that do

not contribute to the neutral current. For example, a nondwelling

occupancy has a calculated service load of 92 amperes on one phase

and 88 amperes on the other phase. The loads have been balanced as

evenly as possible. This calculated load already includes the

noncontinuous and continuous loads at 100 percent and 125 percent,

respectively. An electric water heater is one of the loads included in

the load calculation. The water heater has a current draw of 19

amperes at 240 volts. The voltage at this panelboard will be single-

phase, 120/240 volts. Since the water heater is 240 volts, it will not

contribute to the neutral current. Therefore, 19 amperes can be

omitted from the neutral load calculation. Subtract 19 amperes from

the highest calculated load (92 – 19 = 73 amperes). Although the

feeder conductors must have an ampere rating of at least 92 amperes,

the conductor feeding the neutral must have an ampacity of at least 73

amperes (see Figure 1).

While the neutral conductor in the last example could be the same size

as the ungrounded conductors, it could be smaller and still be Code-

compliant. For example, what minimum size THHN copper conductors

are required for the service in the last example? All conductor

terminations are rated 75°C. Because of the 75°C terminations, select

the allowable ampacity in the 75°C column of Table 310.16. The

ungrounded conductors have a calculated load of 92 amperes.

Therefore, the minimum size is 3 AWG copper for the ungrounded

conductors. The neutral conductor must have an allowable ampacity

of only 73 amperes. The minimum size required for the neutral

conductor is 4 AWG (see Figure 2).


When calculating the feeder or service neutral load, it is permissible to

apply a demand factor of 70 percent to household electric ranges,

wall-mounted ovens, counter-mounted cooking units and electric

dryers. A service or feeder supplying loads specified in 220.61(B)(1) or

(2) shall be permitted to have an additional demand factor of 70

percent as determined by the basic calculation. For example, a clothes

dryer will be installed in a one-family dwelling. What is the minimum

neutral load on the service for a 5,500-watt clothes dryer? When

calculating feeder or service neutral loads for clothes dryers, start by

finding the feeder or service load. Because there is only one dryer, the

minimum service load (at 100 percent) is 5,500 volt-amperes [Table

220.54]. Now, multiply the service load by 70 percent (5,500 × 70% =

3,850). The minimum neutral load on the service for a 5,500-watt

clothes dryer is 3,850 volt-amperes (see Figure 3).

The demand factor for the neutral load may be in addition to any

demand factors that may have already been applied. Demand factors

for household electric clothes dryers are in Table 220.54, and demand

factors for household electric cooking equipment are in Table 220.55.

For example, a 10-unit apartment building will have a 12-kW range in

each apartment. What load will these ranges add to a service neutral

calculation? Start by looking in the left column of Table 220.55 for 10

appliances. The maximum demand for 10 12-kW ranges is 25 kW. The

neutral load can be calculated by multiplying the maximum demand by

70 percent (25 × 70% = 17.5 kW). The neutral load for 10 12-kW

household electric ranges is 17.5 kW (see Figure 4).

Where the calculated neutral current is more than 200 amperes,

another reduction is permitted. Where the feeder or service is supplied

from a three-wire DC or single-phase AC system; a four-wire, three-

phase, three-wire, two-phase system; or a five-wire, two-phase system,

it is permissible to apply a demand factor of 70 percent to that portion


of the unbalanced load in excess of 200 amperes [220.61(B)(2)]. This

demand factor is also in addition to any demand factors that may have

already been applied. For example, after calculating the service load

for an office building by the basic calculation, the neutral load is

216,000 volt-amperes. What is the neutral load after applying the

demand factor from 220.61(B)(2)? The electrical service will be

supplied by a 208Y/120-volt, three-phase, four-wire system. First,

convert volt-amperes to amperes. Since this is a 208-volt, three-phase

system, the total voltage is 360 volts (208 × 1.732 = 360.256 ~ 360).

Divide 216,000 volt-amperes by the total voltage of 360 volts (216,000

÷ 360 = 600). The neutral load (before the additional 70 percent

demand factor) is 600 amperes. Find the amperes in excess of 200

amperes (600 – 200 = 400). Multiply 400 amperes by the 70 percent

demand factor (400 × 70% = 280). Add 280 back to the original 200-

ampere load (280 + 200 = 480). This office building has a neutral

demand load of 480 amperes (see Figure 5).

Next month, the discussion of feeder and service load calculations

continues.

MILLER, owner of Lighthouse Educational Services, teaches classes

and seminars on the electrical industry. He is the author of “Illustrated

Guide to the National Electrical Code” and “The Electrician’s Exam

Prep Manual.” He can be reached at 615.333.3336,

charles@charlesRmiller.com (mailto:charles@charlesRmiller.com) and

www.charlesRmiller.com (http://www.charlesRmiller.com).

Tags:Codes (/tags/codes)
About the Author

Charles R. Miller
(/contributing-
authors/charles-r-miller)
Code Contributor

Charles R. Miller, owner of Lighthouse


Educational Services, teaches custom-tailored
seminars on the National Electrical Code and
NFPA 70E. He is the author of “Illustrated Guide
to the National Electrical Code” and
“Electrician's Exam Prep Manual.”...

Stay Informed Join our


Newsletter
Having trouble finding time to sit down with the
latest issue of
ELECTRICAL CONTRACTOR? Don't worry, we'll
come to you.

Sign up and Get Connected

More Stories From Codes & Standards


(https://www.ecmag.com/section/codes- (https://www.ecmag.com/section/codes-
standards/gfci-protection-personnel- standards/new-definitions-and-revisions-
raceways-and-class-2-wiring-and-more) significant-changes-2020-nec-part-2)


Codes & Standards (/section/codes- Codes & Standards (/section/codes-
standards) standards)
 Jul 2019  Jul 2019
GFCI Protection for Personnel, New Definitions and
Raceways and Class 2 Wiring Revisions: Significant
and More (/section/codes- Changes in the 2020 NEC, Part
standards/gfci-protection- 2 (/section/codes-
personnel-raceways-and- standards/new-definitions-
class-2-wiring-and-more) and-revisions-significant-
changes-2020-nec-part-2)

Next Up
Codes & Standards (/section/codes-standards) Jul 2009
Code Q&A: Conductor Insulation, Utility
Room Lighting and More (/section/codes-
standards/code-qa-conductor-
insulation-utility-room-lighting-and-
more)
George W. Flach (/contributing-authors/george-w-flach)

Article 110 Requirements for Electrical Installations; Article 210 Branch


Circuits; Article 230 Services; Article 250 Grounding and Bonding; Article
310 Conductors for General Wiring; Article 338 Service Entrance Cable:
Types SE and USE; Article 680 Swimming Pools, Fountains, and Similar
Installations; Parts of the 2008...

Read the Article

Electrical Contractor Newsletters


About Us (/about- Contributors Having trouble finding time to sit


us) (/contributing- down with the latest issue of
authors)
Digital Edition ELECTRICAL CONTRACTOR?
(https://www.ecmagdigital.com/ecmag)
Contact
(/contact-us) Don't worry, we'll come to you.
Subscription
(/subscription) Media Kit
(/magazine/media-
kit)
Sign Up Now (/newsletters)
Site Help (/site- Privacy Policy
help) (/privacy-policy) Follow


Site Feedback Terms of Service
(/form/site- (/terms-service)  Like us on  Follow us on
feedback) Facebook Twitter
(https://www.facebook.com/ElectricalContracto
(https://twitter.com/ECMag

 View our  Visit our


Instagram Feed Channel
(https://www.instagram.com/ecmagdotcom/)
(https://www.youtube.com/

 Connect with  Subscribe to


us on LinkedIn our Feeds
(https://www.linkedin.com/groups/2340667/pro
(http://www.ecmag.com/art

NECA Family


NECANet ELECTRI
(https://www.necanet.org/)
International
(https://www.electri.org/)
NECA Convention
(https://www.necaconvention.org/)
NECA Connection
(https://www.necaconnection
NECA Education
(https://www.necanet.org/professional-
NECA Safety
development) Professionals
(https://www.necasafetyconf
NECA-NEIS
(https://www.neca-
neis.org/)

© 2003-2019. All rights reserved. Electrical Contractor


Magazine

(/)

Вам также может понравиться