Вы находитесь на странице: 1из 1

VARIOFACE RELAY MODULE VARIOFACE RELAY MODULE

Double Change Over- Coil Voltage 230V AC/ 110V AC Double Change Over- Coil Voltage 230V AC/ 110V AC

VARIOFACE Relay Modules with Layout Diagram


miniature relays having 2 changeovers,
either plugged or directly soldered for
230 AC/110V AC. Module comes with
necessary protection and signaling circuitry,
on board. Jumpers are provided for looping
on coil side. By removing all jumpers relays
can be made independent. Modules are
available in the combination of 4 and 8 relays
on single board.

ORDERING INFORMATION
Module
Description Type Order No. Pkt
Length (mm)
VARIOFACE Relay Module with 4 miniature PC230A04-2COB 57 92 35 4 1
Relays with socket, For 230V AC 110
VARIOFACE Relay Module with 8 miniature PC230A08-2COB 57 92 34 8 1
Relays with socket, For 230V AC 205
VARIOFACE Relay Module with 4 miniature PC110A04-2COB 57 92 34 9 1
Relays with socket, For 110V AC 110
VARIOFACE Relay Module with 8 miniature PC110A08-2COB 57 92 33 8 1 Field Connection Scheme
Relays with socket, For 110V AC 205
COIL DATA PC 230A... PC 110A...
Voltage 230V AC 110V AC
Resistance 18,790 Ohm. 3750 Ohm.
Consumption 5.3 mA 12.9 mA
CONTACT DATA
No of Contacts 2 PDT
Rated Load 5 Amp, 24V DC/ 220V AC (Resistive Load, cosø=1)
2 Amp, 24V DC/ 220V AC (Inductive Load, cosø= 0.4)
Contact Resistance 50 mOhm
TERMINATION
Relay Coil Side PCB Terminals screw on MKDS 3/2, 3/3 (Printed circuit terminal block,
nominal current: 24A, rated voltage: 250 V, type of connection:
Screw connection)
Relay Contact Side PCB Terminals screw on MKKDS 3/2, 3/3 (Printed circuit terminal block,
nominal current: 22A, rated voltage: 250 V, type of connection:
Screw connection)
C=NC
Cross Section of Solid Min / Max - 0.2 / 4.0 mm2
O=NO
permissible wire Stranded Min/ Max - 0.2 mm2 /2.5 mm2
P=Pole/ Common
Make PHOENIX CONTACT
GENERAL DATA
Relay Omron MY2-230V AC/ Omron MY2-110V AC
Operating Temperature 0o C to 50o C
Relative Humidity 5 to 95% RH
Storage Temperature -10o C to 60o C
Indication Green LED for Coil status

Jumper Setting Scheme

10 Phoenix Contact Phoenix Contact 11

Вам также может понравиться