APPLICATION NOTE

for

Multiple switch series support for


Test and Training Set

SCOPE
This document covers the support for
multiple switchgear series, added to the Test
and Training Set (TTS) in ADVC Controller
Range setVUE and flexVUE.
These changes will be the default behavior
when a TTS is attached.

Document Revision Level: R03

Copyright Schneider-Electric Global Recloser Solution


2012

Schneider Electric
80 Schneider Road, Eagle Farm, Qld 4009
Locked Bag 10, Eagle Farm Business Centre
Qld 4009, Australia
Tel: +61 7 3635 7500
Fax: +61 7 3636 7560
Page 1 of 5
A45 TTS multiple switch series support
LIMITATIONS

This document is copyright and is provided solely for


the use of the recipient. It is not to be copied in any
way, nor its contents divulged to any third party, nor
to be used as the basis of a tender or specification
without the express written permission of Schneider
Electric Recloser Solutions Pty Ltd.
This document discloses confidential intellectual
property that belongs to Schneider Electric Pty Ltd.
This document does not invest any rights to
Schneider Electric intellectual property in the
recipient. Moreover, the recipient is required not to
disclose any of the intellectual property contained in
this document to any other party unless authorised in
writing by Schneider Electric Pty Ltd.

REVISION RECORD

Level Date Author Comment


R00 6/6/12 Stuart C Initial
R01 6/6/12 Stuart C Info about switch type
R02 07/06/12 FG Implemented review
comments
R03 18/06/12 FG Final firmware version

Schneider Electric
80 Schneider Road, Eagle Farm, Qld 4009
Locked Bag 10, Eagle Farm Business Centre
Qld 4009, Australia
Tel: +61 7 3635 7500
Fax: +61 7 3636 7560
Page 1 of 5
A45 TTS multiple switch series support
Contents
Introduction .......................................................................................................................4
Firmware ...........................................................................................................................4
TTS With Multiple Switch Support .....................................................................................4
TTS Calibration .................................................................................................................4
References........................................................................................................................4

Page 4 of 5
A45 TTS multiple switch series support
Introduction
This document describes ADVC Controller Range behaviour when a TTS is connected.

Firmware

ADVC Controller firmware A45-11.01+

TTS With Multiple Switch Support


Each ADVC Controller Range is configured for a given switch series. This configuration
happens automatically when the controller is connected to a switch, or during the WSOS
morphing process.
The N24-150s calibration file is factory-loaded for all new TTS units. Previously, each TTS
calibrated as N24-150s were seen as an N series switch when connected to an ADVC
Controller.
Now, as long as the TTS has the calibration file N24-150s loaded, the controller will
automatically identify the TTS as being the same switchgear series to which the controller
was last connected. This new functionality is available only for TTS units calibrated with the
N24-150s switch type – TTS units containing a calibration file OTHER THAN N24-150s will
need to be re-loaded with the N24-150s calibration file in order to benefit from this new
functionality.
Please also note that the mechanical interlock functionality is not available when using TTS
units.

TTS Calibration
To identify the calibration file loaded, connect the controller to the TTS, go online in WSOS5,
open the Maintenance / Calibration screen, and read the Switchgear Type field – it should
read N24-150s(24kV 150kV BIL 1A CT’s) if it contains the factory-loaded calibration file.
If required, load a new N24-150s calibration file by requesting and saving locally the file from
Schneider Electric, connecting the controller to the TTS, going online in WSOS5, opening the
Maintenance / Calibration screen, perform Import Data File and Write Data to SCEM.
Remember to perform Read Switchgear Settings from Switchgear as a final step to update
your offline file.

References
Contact your local distributor if you need more information
on this application.