for
SCOPE
This document covers the support for
multiple switchgear series, added to the Test
and Training Set (TTS) in ADVC Controller
Range setVUE and flexVUE.
These changes will be the default behavior
when a TTS is attached.
Schneider Electric
80 Schneider Road, Eagle Farm, Qld 4009
Locked Bag 10, Eagle Farm Business Centre
Qld 4009, Australia
Tel: +61 7 3635 7500
Fax: +61 7 3636 7560
Page 1 of 5
A45 TTS multiple switch series support
LIMITATIONS
REVISION RECORD
Schneider Electric
80 Schneider Road, Eagle Farm, Qld 4009
Locked Bag 10, Eagle Farm Business Centre
Qld 4009, Australia
Tel: +61 7 3635 7500
Fax: +61 7 3636 7560
Page 1 of 5
A45 TTS multiple switch series support
Contents
Introduction .......................................................................................................................4
Firmware ...........................................................................................................................4
TTS With Multiple Switch Support .....................................................................................4
TTS Calibration .................................................................................................................4
References........................................................................................................................4
Page 4 of 5
A45 TTS multiple switch series support
Introduction
This document describes ADVC Controller Range behaviour when a TTS is connected.
Firmware
TTS Calibration
To identify the calibration file loaded, connect the controller to the TTS, go online in WSOS5,
open the Maintenance / Calibration screen, and read the Switchgear Type field – it should
read N24-150s(24kV 150kV BIL 1A CT’s) if it contains the factory-loaded calibration file.
If required, load a new N24-150s calibration file by requesting and saving locally the file from
Schneider Electric, connecting the controller to the TTS, going online in WSOS5, opening the
Maintenance / Calibration screen, perform Import Data File and Write Data to SCEM.
Remember to perform Read Switchgear Settings from Switchgear as a final step to update
your offline file.
References
Contact your local distributor if you need more information
on this application.