Shutdown SIS
Previous Screen
i02848479
Startup Procedure
SMCS - 4467
Illustration 1 g01425354
The terminals and heat sinks are live at hazardous voltages when power
is applied and for up to 8 minutes after power is removed.
1. Connect the digital voltage regulator. Refer to Testing and Adjusting, "Wiring Diagrams" for a proper
illustration. Take care to follow notes and observe polarities.
3. Connect serial cable between CATV and PC. Start the CATV PC Software. Establish communication
between the CATV and the PC. For more details, refer to "Establishing Communications" located in the
"Remote Communication" section.
4. Verify that all of the parameters are properly adjusted for the application. The following fields may need
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 01/08/2010
G3520C Generator Set GZM00001-UP(SEBP3869 - 20) - Document Structure Página 2 de 4
to be entered for first configuration. For more details, refer to "Settings Definitions" located in the
"Parameter Viewing and Configuration (Caterpillar PC Software)" section.
a. System Configuration
Frequency
PT Primary (V)
PT Secondary (V) - A PT is required if the generator is rated at more than 600 VAC. If no
PT is installed, set the PT Primary and PT Secondary to rated voltage.
CT Primary
Table 1
b. Setting Adjustments
Power Factor - Must select Droop under "Load Compensation Mode" for PF control.
Soft Start Bias (percent) - A starting value for the regulator on startup.
Soft Start Time (sec.) - For emergency applications, this value may need to be set to 2
seconds, or less.
Knee Frequency (Hz) - Select a value that is 0.2 to 2 Hz below rated frequency.
For applications that require special PID settings, refer to the "Gain Setting - Adjust"
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 01/08/2010
G3520C Generator Set GZM00001-UP(SEBP3869 - 20) - Document Structure Página 3 de 4
section.
d. Protections Settings
Over Excitation: Type - Threshold is the default setting. If "Inverse Time" is selected, the
time setting must be changed to a suggested value of 2 (based on the time dial settings for
the SR4B Generator curve). If this value is not changed, over excitation protection may not
exist.
8. Record all settings. For more details, refer to "Settings File" located in the "Parameter Viewing and
Configuration (Caterpillar PC Software)" section.
9. Press "Get From Unit" to verify that the settings were saved.
10. Disable communications (if desired). For more details, refer to "Terminating Communications" located
in the "Remote Communication" section.
https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 01/08/2010
G3520C Generator Set GZM00001-UP(SEBP3869 - 20) - Document Structure Página 4 de 4