Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines
Número de Mídia -RENR1200-01 Data de Publicação -10/01/1999 Data de Atualização -10/09/2001

i01175025

Fault Log Viewing OP1


SMCS - 4490; 7451

OP1 is the option that is used for viewing diagnostic fault codes. The fault log contains a history of
the diagnostic faults. These diagnostic faults are the faults that have occurred in the generator set
system since the last clearing. Also, the total number of occurrences are shown on the upper display.
The fault log assists when service personnel are troubleshooting the generator set system.

The diagnostic fault codes consist of the following items: a component identifier (CID), a failure
mode identifier (FMI) and a DIAG indicator. These diagnostic fault codes are shown on the upper
display. The CID informs the operator of faulty components. The FMI describes the type of failure
that has occurred. When the CID FMI fault is active the DIAG indicator FLASHES.

Only inactive diagnostic faults are stored in the fault log. An active diagnostic alarm fault becomes
inactive when the fault is no longer occurring. An active diagnostic shutdown fault becomes inactive
when the fault is no longer occurring and the engine control switch (ECS) is turned to OFF/RESET.
Active diagnostic alarm faults and diagnostic shutdown faults are indicated when "DIAG" is
FLASHING. When the faults become inactive "DIAG" is ON CONTINUOUSLY. The GSC+ stores
a maximum of 12 diagnostic fault codes in the fault log. If an additional diagnostic fault becomes
inactive, the GSC+ automatically clears the earliest inactive diagnostic fault code. The GSC+ then
places the newinactive diagnostic fault code in the fault log.

The GSC+ automatically clears any inactive diagnostic fault codes that have been stored in the fault
log longer than 750 hours. For example, if a CID FMI fault code is logged at 10 hours, then the
GSC+ clears the fault code when the hour meter is at 760 hours. If a CID FMI fault code is logged at
20 hours, then the fault code remains logged until the hour meter is at 770 hours. This feature
prevents old fault codes from clogging the fault log, if service personnel have forgotten to clear the
log after correcting faults.

When an active diagnostic fault changes to an inactive diagnostic fault, the GSC+ will function in
the following manner.

1. The diagnostic fault is recorded in the fault log of the GSC+.

2. If no other active faults are present the DIAG indicator will stop FLASHING and the DIAG
indicator remains on CONTINUOUSLY.

3. The fault alarm indicator or the shutdown fault is turned OFF.

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 31/08/2010
Pesquisa de Mídia - RENR1200 - Electronic Modular Control Panel II+ (EMCP II+... Página 2 de 2

Procedure To View The Fault Log


ote: For a list of all diagnostic fault codes, seeTesting And Adjusting, "Diagnostic Fault Codes".

ote: Service Mode cannot be entered when the ECS is in the AUTO position.

ote: Any active shutdown fault must be made inactive in order to access service mode. A
FLASHING shutdown indicator indicates that a shutdown fault exists. To temporarily change a
shutdown fault from an active shutdown fault to an inactive shutdown fault, turn the ECS to the
OFF/RESET position. To permanently change a shutdown fault from an active shutdown fault to an
inactive fault, the fault must not be occurring. The ECS must also be turned to the OFF/RESET
position. If the jumper that electrically connects terminal 6 to terminal 9 is not installed on the ECS,
then the GSC+ will not power up in OFF/RESET and any active shutdown fault must be corrected
before entering service mode.

1. Press the "SERVICE MODE" key in order to enter Service Mode. "OP 1" is showing on the
lower display. See Systems Operation, "Service Mode"for more information.

2. Press "SELECT" key. If more than one fault code is present then the fault codes begin
scrolling on the display. The number of occurrences is shown above the "COUNT" indicator.
The lower display shows the hour meter data of the first occurrence and the last occurrence of
each fault.

3. Press "SELECT" key. The fault codes stop scrolling.

4. Press "SCROLL RIGHT" key. If more than one count of a fault code is logged then the first
occurrence with a corresponding hour meter data is showing on the lower display.

5. Press "SELECT" key. Fault codes continue scrolling.

6. Press "EXIT" key. "OP 1" is showing on lower display.

7. Press "EXIT" key. The display is now in normal mode.