Академический Документы
Профессиональный Документы
Культура Документы
1.0 Standardization
o Rated leakage current (standard flash) 8/20 μs; Peak value usually 5, 10, 20 kA
o 4/10 μs, 1/9 μs, …
o About five
o Incoming line and outgoing line
o Two panels for two transformers
o busbar coupling
o Phase of generation
o Development phase
o Saturation phase - strongest internal activity
o Reduction phase - strongest external activity, often with heavy rain
o Total duration approx. 1h
Why are small-peak-up flashes so dangerous to humans and animals, high-peak-level lightning not
necessarily?
o Small lightning currents <100 A: small voltage drop across the body
o Lightning does not jump – deadly
o When tension above the body exceeds the dielectric strength of air, the flash bounces off the
body into the ground
o Decisive: lightning current
o Body resistance ≈ 500 Ω
o Power turnover in the body can be deadly (current flow)
Sensation threshold 1 mJ
Lethal energy ≈ 350 mJ (overhead lines: 10 J (?))
What is the internal impedance of the arc in the flash?
o Hypothesis: When the leader's head has approached the objects on the earth except for a
certain end break distance hb, the catch discharge bridges the end breakthrough distance in the
shortest possible path.
o Lightning discharges, catch discharge comes from an object on earth
o The higher the lightning current of the first partial flash, the larger the final breakdown distance
hb and the larger the protection space: With larger current, the plasma channel is larger and
there are more charges available, these are dissipated; the conductivity is higher, the resistance
is lower and thus less voltage drops over the flash; it leaves more residual voltage for the
rollover to earth or the potential at the top of the flash rises and the shelter is larger
−î
o ℎ𝑏 = 2 ∗ î + 30 ∗ (1 − 𝑒 6,8 ), î in kA
How do lightning discharges on overhead lines work?
o Criterion: Peak value of the voltage across the insulator must be less than the lightning impulse
withstand voltage of the equipment BIL: Û𝐼𝑠𝑜𝑙𝑖𝑒𝑟𝑢𝑛𝑔 <Û𝐵𝐼𝐿
o UBIL from table, BIL = Basic lightning impulse insulation level
o Insulation not loaded with chained voltage: peak value of conductor to ground = voltage of
conductor to ground * √2 = (Rated voltage ∗ √2)/ √3
o Û𝐼𝑠𝑜𝑙𝑖𝑒𝑟𝑢𝑛𝑔 =Û𝐿𝐸 + Û𝑀𝑎𝑠𝑡
4
Volume sphere 𝑉𝐾 = 3 π𝑟 3 , surface sphere 𝐴𝐾 = 4π𝑟 2 ,, smallest surface area at given vol.
o Occur in gas-insulated switchgear (GIS) when the switch contacts of the earthing switch move
towards or away from each other due to multiple ignitions of the arc
o Flashbacks occur especially when restarting
o Steep voltage increase and reflection at the bushing
What is the single-pole ground fault? How big is the factor δ there?
Draw and explain the course of current and voltage when switching short-circuit currents via circuit
breakers.
o U curve of the applied AC voltage at 50 Hz, inductive character of the net at high currents phase
shift of 90 °
o 𝑈𝐿 curve of arc voltage (100 V - 2 kV)
o 𝑈𝐸 transient recovery voltage
o 𝑖𝑘 Course of the short circuit current through the
circuit breaker
o Short-circuit currents from the network flow to
the fault location, light arc temperature up to
25,000 K.
o arc is cooled by gas, but arc resistance increases
due to heat extraction = "competition" between
reconsolidation of the switching path (cooling)
and voltage increase
o Electricity goes faster to zero than 𝑖𝑘
o From t1 no more arc, but hot gas between the contacts
o The contacts are connected to U, so the potential at the two contacts has to settle on it, TRV
oscillates - internal overvoltage in the LS, not in the network
o Voltage gradient du / dt up to 20 kV / μs
o Residual conductivity causes a residual current 𝑖𝑝𝑎 , which should be limited
What is the stored energy in capacitor and coil?
1
o Coil: 𝑊𝐿 = ∗ 𝐿 ∗ 𝐼 2 , [𝑊𝐿 ] = H*A² = (Vs/A)*A² = VAs = Ws = J
2
o Unit [L] = Vs / A = Ωs
o Component equation uL (t) = L * di / dt
1
o Kondensator: 𝑊𝐶 =2∗𝐶∗𝑈 2 ,, [WC] = F*V² = (As/V)*V² = VAs = Ws = J
o Unit [C] = As / V
o Component equation ic (t) = C * du / dt or C = Q / U
o plate capacitor C = ε * A / d
2π ∗ ε ∗ l Q 𝑟 𝑄
o Cylinder capacitor / coaxial cable 𝐶 = ln (r2/r1) with 𝑈 = 2π ∗ l ∗ ε ∗ ε0
* ln ( 𝑟𝑎 ) and 𝐶 = 𝑈
𝑟 𝑖
Draw and explain the voltage curve for ground faults (single line faults).
How do you determine the ground faults δ and κ from the drawing?
o The higher the voltage level, the more likely a rigidly earthed star point
o Arc suppression coil = Petersen coil
What are the special features of surge arresters in the high voltage range?
o 𝑈𝑚 rated voltage
o 𝑈𝑐 = 𝑈𝑛,𝑛𝑒𝑡𝑧 Max. Continuous operating voltage (𝑈𝑚 / √3)
o 𝑈𝑟 Last possible operational voltage = measurement voltage of the
arrester, 1.25 * 𝑈𝑐
o 𝑈𝑇𝑂𝑉 Temporary overvoltage = √3 * 𝑈𝑐 = 𝑈𝑚 (?)
o T TOV strength factor
o TOV Capability: Short term overvoltage load, slightly larger than UTOV
o 𝑈𝑝𝑠 Switching Impulse Protection Level, Upl Lightning Strike
o Voltage protection level - voltage to be measured via arrester, when
nominal discharge current such as 8/20 μs flows over it
o 𝑈𝑤𝑠 switch-surge voltage, 𝑈𝑤𝑙 lightning impulse voltage
o Auslegeregel: factor 1.4 between Ups / Upl and Uws / Uwl - 110 kV: 550 kV Lightning impulse
withstand voltage → 𝑈𝑝 = 550 kV / 1.4 = 380 kV
What shape does the resistive current flow have and why?
o Uref high current gradient, therefore sharp course of the resistive current (?)
How is the reflection factor defined?
o Traveling waves: current and voltage not only time, but also location dependent
𝑍 −𝑍
o Reflection factor voltage 𝑟𝑢 = 𝑍𝐸𝑛𝑑𝑒 +𝑍𝐾 = -𝑟𝑖 = reflection factor current
𝐸𝑛𝑑𝑒 𝐾
o Open end
o voltage 𝑟𝑢 = 1, current 𝑟𝑖 = -1
o Ex. with transformer: 10 kΩ against characteristic impedance of overhead line
o short circuit
o voltage ru = -1, current ri = 1
o eg termination with cable, low impedance
o Exception: dielectrically short termination with ZEnde = Zline, then no reflection: Wandering
waves only on lines, not behind them
o Protection level Up depending on the lightning impulse withstand voltage of the equipment BIL
o Ur = 1.25 Uc of the arrester as a function of the system voltage
o permanent operating voltage
o Selection of the arrester depending on the neutral point
o Rigid earthed star point, single-pole fault - overvoltage up to 1.1 * Un → 1.25 with 15%
buffer
o Isolated neutral point, single-pole fault - overvoltage up to √3 * 𝑈𝑚
o Energy absorption capacity depending on cable length and cable capacity
o Energy that an arrester can absorb without becoming thermally unstable
o Normally, release the heat to the environment
o Red: cooling capacity over surface
o Blue: temperature the arrester would accept (power (?))
o operating point left stable, because power dissipation
higher than cooling capability (the other way round (?))
o arrester takes over the energy, with long cables large: 𝑊𝐶 =
1
* 𝐶 * 𝑈 2 and 𝐶 ~ 𝑙
2
o Influencing factors: frequency of discharges conditions,
material, ambient temperature, height, diameter
o Solution: increase the diameter or several arresters parallel
o Economic aspects
R ′+ jωL′ L′′
o Characteristic impedance 𝑍𝑤 = √ 𝐺 + jωC′ , 𝑓ü𝑟 𝐻𝑆 𝑍𝑤 = √ C ′
o Overhead line: Zw = 250 - 400 Ω
o Cable: Zw = 40 - 60 Ω
o v = c / √εr ≈ 200 m / μs with dielectric constant εr ≈ 2.25 (VPE) (air: 300 m / μs)
Image 1
picture 2
o Arrester already starts to conduct, when the incoming wave is 0.5 * UP, as the reflec- tion UP is
applied to the arrester then the returning wave cuts off
o For an incoming wave with Up already exists a negative wave with nearly UP
o Overall, the voltage at the transformer in the protected area of the active and functional
arrester can thus reach a maximum of Up
o "Backward traveling wave from transformer to surge voltage at surge arrestor before TW
reaches UP at surge arrester"
What changes in the voltage characteristic of the surge arrester, if there is still a cable behind it?
o Cable has less characteristic impedance, so broken wave is smaller than Up and almost nothing
is reflected back to the output conductor
o Propagation speed in the cable lower, 200 m / μs
How does the voltage curve at the surge arrester behave at a "faster" surge current, eg 4/10? (?)
o At 4/10 surge current behind a steeper rise, higher voltage at the same current
o arrester has inductivities / supply line to the arrester has inductances, so that the voltage drop is
higher