TROUBLESHOOTING GUIDE FOR BUTTERFLY VALVES

PROBLEM CAUSES REMEDIES


Leakage between valve • Packing leak • Clean packing bore and
and actuator replace packing

Bottom trunnion leaks • Packing or gasket leak • Replace bottom shaft


packing, O-ring or
gasket

Valve leaks when closed • Disc not fully closed or • Adjust actuator closed
past fully closed position stop
• Disc edge wear or • Clean and/or repair disc
damage edge
• Rubber seat wear or • Adjust or replace valve
damage seat (Bonded seat
valves 20” or below
must be returned to the
factory for repair)
Chainwheel jams • Poorly fitting chain • Replace with correct
chain
Valve hard to operate • Foreign material in • Remove obstructions
valve
• Corroded actuator parts • Clean and grease
actuator
• Loose actuator • Apply loctite or Omni-fit
locking compound and
tighten bolts
Automatic valve does not • No power source • Check incoming power
actuate source and replace
fuses or rest pressure
• Improper signal • Check actuating signal
sequence
• Burned out or impaired • Check and repair or
component replace solenoids,
motors and relay
devices