2. The drive contains high voltage that can cause electric shock resulting in personal injury or
loss of life.
4. Wait at least 3 minutes after turning off the AC Input power to the drive. If the bus capacitor
discharge circuit fails, high voltage can remain in the drive a long time after the AC power
is removed.
1
Contents
2
User selection guide - iG specification
3
User selection guide - iG specification
4
INSTALLATION
1. Installation
1.1 Inspection
l Inspect the drive for any physical damage that may have occurred during its
delivery. If any parts of the drive are missing or damaged, contact your LG
distributor immediately.
l Verify the nameplate of the iG drive. Verify that the drive unit matches your order
and packing slip. The nomenclature of LG drive is as follows.
SV 008 iG -2 U
LG Drives
Maximum applicable motor capacity ( 10kW)
Series name of the drive
Input voltage (2:230V or 4:380/460V)
UL Listed (Open Type Power Conversion Equipment,
suitable for mounting within another enclosure)
5
INSTALLATION
1.3 Mounting
l The drive must be mounted vertically with sufficient room (horizontal and vertically)
from adjacent equipment.
iG Drives
6
INSTALLATION
ADJUSTABLE
G Drives
FREQUENCY DRI
VE
S SPAEC
VECTOR
V CONTROL
C
MenuOperatingInstruction Caution
LG Industrial Systems
7
INSTALLATION
G Drives
ADJUSTABLE
FREQUENCY DRI
VE
SPAEC
S VECTOR
V CONTROL
C
MenuOperatingInstruction Caution
LG IndustrialSystems
8
INSTALLATION
G Drives
ADJUSTABLE
FREQUENCY DRI
VE
S SPVECTOR
AEC
V CONTROL
C
MenuOperatingInstruction Caution
LG IndustrialSystems
9
INSTALLATION
G Drives
ADJUSTABLE
FREQUENCY DRI
VE
SPAEC
S
VECTOR
V
CONTROL
C
MenuOperatingInstruction Caution
LG Industrial Systems
10
STANDARD CONFIGURATION & WIRING
R (S) T B1 B2 U V W
Symbol Function
R
AC line input terminals, 200/230V class, 380/460V class
(S)
1 Phase input Terminals: R and T
T
B1
External Dynamic Braking resistor terminals
B2
U
V 3-phase output terminals
W
! Warning :
The normal stray capacitance between the drive frame, power devices inside the drive, and
AC line can provide a high independence shock hazard. Do not apply power to the drive if the
drive frame (Ground terminal ) is not grounded properly.
11
STANDARD CONFIGURATION & WIRING
MO EXTG RX CM P1 P2 P3 I FM 5G
Symbol Function
30A Relay output terminal for fault signal (Normal open contact)
30B Relay output terminal for fault signal(Normal close contact)
30C Relay output terminal for fault signal(Common terminal)
12
STANDARD CONFIGURATION & WIRING
DB RES. (OPTION)* 4
MCCB B1 B2 MOTOR
1 Phase U
R
230V
V IM
or S
3 Phase W
230V/460V T
Forward run/stop +
FX (Forward command) FM FM Output frequency*2
Reverse run/stop Digital pulse output
RX (Reverse command) (0-10V)
Emergency stop/Jog 5G
BX/JOG (Emergency stop / Jog)
Fault reset
RST (Reset)
Multi-speed 1
P1
Multi-speed 2 P2 (Multi-function input)
Factory "Multi-speed”
Multi-speed 3
P3
CM (Common for
sequence input) 30A Fault output
30C Less than AC 250V, 1A
Less than DC 30V, 1A
30B
Shield Wire (Power supply for
VR Speed signal input)
+11V, 10mA MO
10 k Ω Output Multi-function output
V1 Speed signal input)
(
(Factory "Frequency reaching time”
1/2 Watt 0-10V Input
DC24V, 50mA
4 ~ 20 mA I (Current speed input)
Common for MO
4-20mA Input
EXTG
250 ohm
*3
5G (Common for VR, V1, I )
Speed signal input
Caution) *1. display main terminals(ratings are depend on the input voltage),
display control terminals(ratings are DC24V except specified).
*2. Output voltage can be set up to 12V. (Refer to H13 in Function Group 2)
*3. Analog speed command can be set voltage, current, and both of them.(see Function code F18)
*4. Refer to DB resistor specifications.
13
STANDARD CONFIGURATION & WIRING
230 V Class
Resistor Resistor Average Permissible Continuous
H.P. Drive Model Capacity Value Braking Braking Braking
[Watt] [Ohms] Torque [%] Duty [%] Time [sec]
1/2 SV004iG-2
300 100 150 25 60
1 SV008iG-2(1)*
5 SV037iG-2
400 50 100 10 30
5.4 SV040iG-2
460 V Class
Resistor Resistor Average Permissible Continuous
H.P. Drive Model Capacity Value Braking Braking Braking
[Watt] [Ohms] Torque [%] Duty [%] Time [sec]
1/2 SV004iG-4
400 200 150 15 30
1 SV008iG-4
5 SV037iG-4
400 100 100 10 20
5.4 SV040iG-4
SV040iG-2 SV040iG-4
14
KEY-PAD
3. Key-pad
3.1 Functions
UP Arrow Key
FUNC Key
-. Move code in Main Group
-. Start data change mode
-. Increase the code in FU1, FU2
-. Complete data change
-. Increase the data in data
mode
change mode
Display
DOWN Arrow Key
-. Frequency, Current etc.
-. Move code in Main Group
-. Decrease the code in FU1, FU2
-. Decrease the data in data
change mode
FUNC
STOP
RUN RESET
RUN LED
-. ON during operation
STOP/RES ET Key
FWD LED
-. Stop button
-. Blink when accel /
-. Reset button when trip
decel in forward run
takes place
-. ON during forward
run with normal speed
SET LED RUN Key
-. ON when data -. Run command key
REV LED
change mode starts -. Direction of run is set by
-. Blink when accel /
-. OFF when data Main Group
decel in reverse run
change mode
-. ON during reverse
completes
run with normal speed
15
USING KEY-PAD
1)
FUNC
FUNC
2)
FUNC
1)
Keypad displays the speed reference
when ‘Run’ is not engaged, and the speed
output during ‘Run’ sequence.
2)
Keypad displays ‘nOn’ during normal
FUNC
operation, and fault information when trip
takes place.
16
DATA SETTING
FUNC FUNC
RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET
FUNC FUNC
RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET
FUNC FUNC
RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET
STOP STOP
RESET RESET
-. When a fault takes place, Main Group displays the fault information. User can monitor the
frequency and Current at the time of drive fault using UP and DOWN arrow Keys.
-. To reset the drive, press ‘STOP/RESET’ key.
• In order to save the fault data in the drive fault history, the drive must be reset before
turning off the input power.
17
DATA SETTING
FUNC FUNC
RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET
FUNC FUNC
18
PARAMETER LIST
nOn Trip display OC,Ov,Lv, Display the kind of trip, driving nOn X 26
OLt,OH, frequency and output current
EtH,EXt, caused during operation
bX,CPU
1)
Factory setting value
2)
It is possible to set or change the parameters while driving. ( Y : Yes, N : No, X : Impossible
to set data)
19
PARAMETER LIST
Function Group 1
Display Function Range Remarks F Unit R Page
F1 Command 0-1 0 : Keypad, 1: Terminal (refer to 0 N 27
frequency setting F18)
F2 Run/Stop 0-2 0 : Key-pad 1 N 27
selection 1 : Fx = FWD, Rx = REV
2 : Fx = Run/Stop,
Rx = REV/FWD
F3 Starting frequency 0 - 5.00 0 Hz N 28
F4 Max. frequency 40.0 - 400 60.0 Hz N 28
F5 Base frequency 40.0 - 400 60.0 Hz N 28
F6 V/F pattern 0-2 0 : Linear 0 N 28
selection 1 : 2.0
2 : User V/F ( refer to F14)
F7 Hold time 0.0 - 10.0 Hold time for starting frequency 0.0 sec N 29
20
PARAMETER LIST
Function Group 1
Display Function Range Remarks F Unit R Page
F 21 Analog input bias 0 - 100 Analog input volt. Bias 0 % N 33
F 22 Analog input 0-1 0 : Direct (Max. Freq. with 10V 0 N 34
direction setting input)
1 : Inverse(Max. Freq. with 0V
input)
F 23 High limit freq. 0 - 400 Operational Max. Freq. 60.0 Hz N 34
F 24 Low limit freq. 0 - 400 Operational Min. Freq. 0.00 Hz N 34
F 25 Jump freq. 0 - 400 Impossible to drive within 0.00 Hz N 35
preset freq. Range
F 26 Jump band 0 - 30.0 Band setting of jump freq. 0.00 Hz N 35
F 27 DC braking freq. 0.00 - 20.0 DC brake starting freq.(refer to 5.00 Hz Y 36
F13)
F 28 DC braking volt. 0 - 20 % Value within the Max. Output 5 % Y 36
voltage setting
F 29 DC braking block 0.0 - 5.0 Free run time before DC brake 0.0 sec Y 36
Time activation
F 30 DC braking time 0.0 - 20.0 DC braking time 2.0 Y 36
F 31 Slip compensation 0 - 1 Slip compensation selection 0 Y 37
(1: Active)
F 32 Freq. of rated 0.00 - 5.00 Refer to nameplate of motor 3.00 Hz Y 37
motor slip
F 33 Rated motor 0.1 - 60.0 Refer to nameplate of motor 3.6 A Y 37
current
F 34 Motor no-load 0.1 - 60.0 Motor current with no load 1.6 A Y 37
current
F 35 Drive model setting 08.1- 40.2 Ex.) 08.2 N 37
04.4 - 40.4 08.1 : 0.75kW, 230V(1phase)
08.2 : 0.75kW, 230V(3phase)
37.4 : 3.7kW, 460V(3phase)
F 36 Retry Number 0 - 10 Number of retrial attempt 0 Y 38
F 37 Retry time 0.0 - 10.0 Time delay between retries 0.5 sec Y 38
F 38 Relay mode 0-3 0 :Non-driving during Lv and 0 Y 38
Retry
1 : Non-driving during Lv Trip
2 : Non-driving during Retry
3 : Driving in all Trips
21
PARAMETER LIST
Function Group 1
Display Function Range Remarks F Unit R Page
F 39 Stall mode 0-7 0 : No stall Prevention 0 Y 39
1 : Accel., 2 : Normal run
3 : Accel.+ Normal run
4 : Decel.
5 : Accel.+Decel.
6 : Decel.+ Normal run
7 : Accel.+ Decel.+ Normal run
F 40 Stall level 30 - 170 Current based on stall mode 170 % Y 39
operation
( 100% : drive rated current)
F 41 Over load level 30 - 150 Terminal output in overload 150 % Y 40
(refer to H2)
100%:drive rated current
F 42 Over load time 0.1 - 30.0 Overload warning signal output 10.0 sec Y 40
time
F 43 Over current time 0 - 60.0 “Olt” trip occurs after preset 60.0 sec Y 40
time when there is 180% load
of drive rated current
F 44 ETH selection 0-1 Set electronic thermal 1 Y 41
Protection (“1”)
F 45 ETH level 30 - 150 ETH trip occurs when there is 150 % Y 41
more current than preset level.
22
PARAMETER LIST
Function Group 1
Display Function Range Remarks F Unit R Page
F 54 Parameter read 0-1 1:Display “F54” after copying 0 N 44
parameter from the drive to the
Key-pad
F 55 Parameter write 0-1 1:Display “F55” after copying 0 N 44
parameter from the key-pad to
the drive
F 56 Parameter 0-1 1:Display “F56” after initializing 0 N 45
initialize the parameter to the factory
setting value
F 57 Parameter Lock U(L) 0 - 99 U: Unlock, Password : 12 U0 N 45
L : Lock, Password : 12
F 58 AVR Selection 0-1 0: Not selected 1 N 46
1: Selected
rt Return to Main Group X
Function Group 2
Display Function Range Remarks F Unit R Page
H1 Multi-Input mode 0-3 0 : 8 Steps operation ( P1, P2, 0 N 47
selection P3 )
1 : 4 Steps operation ( P1, P2 )
+ External fault signal ( P3 )
2 : 4 Steps operation ( P1, P2 )
nd
+ 2 Accel./Decel. ( P3 )
3 : 2 Steps operation ( P1 )
nd
+ 2 Accel./Decel. ( P2 )
+ External fault signal ( P3 )
( refer to H 3 ~ H 11 )
H2 Multi-Function 0-4 0 :Frequency reaching time 0 N 48
Output mode (Normal open)
selection 1 :Frequency reaching time
(Normal close)
2 :Stall operation signal
3 :Overload signal
4 :Under-voltage(Uv) signal
5 :Run/Stop signal
H3 Step 2 Freq. 0 - 400 10.0 Hz Y 48
23
PARAMETER LIST
Function Group 2
Display Function Range Remarks F Unit R Page
H4 Step 3 Freq. 0 - 400 20.0 Hz Y 48
H5 Step 4 Freq. 0 - 400 30.0 Hz Y 48
H6 Step 5 Freq. 0 - 400 40.0 Hz Y 48
H7 Step 6 Freq. 0 - 400 50.0 Hz Y 48
H8 Step 7 Freq. 0 - 400 60.0 Hz Y 48
H9 Step 8 0 - 400 30.0 Y 48
nd
H 10 2 Accel. Time 0 - 999 Acceleration at preset time with 20.0 Sec N 49
the input of P3 ( H1=2 ) or P2 (
H1=3 )
nd Deceleration at preset time with
H 11 2 Decel Time 0 - 999 the input of P3 ( H1=2 ) or P2 ( 20.0 Sec N 49
H1=3 )
0 :Freq. (10V at Max Freq.)
H 12 Multi-Meter mode 0 - 2 1 :Output Volt. ( 10V at 220V ) 0 Y 49
selection 2 :Output current (10V at 180 %
of the drive rated current )
H 13 Multi Meter Adjust 0 - 120 120 % : 12 V output 100 % Y 49
H 14 FDT Freq. 0 - 400 Freq. reaching signal setting 0 % N 50
Freq.(H2)
H 15 FDT Band 0 - 30.0 Freq. reaching signal Band 0 % N 50
setting
H 16 BX / JOG 0-1 0 : BX Selection 0 N 50
Selection 1 : JOG Selection
H 17 JOG Frequency 0 - 400 Frequency for Jog drive 5.0 Hz X 50
H 18 Input terminal External terminal status RX, X 51
signal FX, RST, P3, P2, P1
H 19 Fault history 1 1st Trip, Freq. and current data X 52
H 20 Fault history 2 2nd Trip, Freq. and current data X 52
H 21 Version No. ROM version No. X
rt Return to Main Group X
24
MAIN GROUP
5. Description of Parameters
5.1 Main Group
Frequency Reference
Max. freq.
time
Accel. time Decel. time
25
MAIN GROUP
Display range : 0 ~ 60 A
Function related : F35
l Displays the output current level of the drive. It is necessary to confirm the drive capacity
setting before its operation. It displays correct current ONLY if the drive setting (F35) and
the capacity shown on the nameplate match exactly the same.
Fault Indicator
The kinds of trip : Oc, OLt, Ov, Lv, OH, EtH, Ext, CPU
Function related : F35, F43, F44, H1
l It shows <nOn> during normal run as shown above. When a fault takes place, the keypad
displays the level of trip, frequency, and current data that were recorded at the time of fault.
See the contents of the drive trip and its measure for more details.
Direction setting
26
FUNCTION GROUP 1
Forward Forward
Reverse Reverse
FX-CM ON FX-CM ON
RX-CM ON RX-CM ON
<< When F2 is set to ‘1’ >> << When F2 is set to ‘2’ >>
27
FUNCTION GROUP 1
28
FUNCTION GROUP 1
l 1 : Use preset variable torque curve which has a square reduction(2.0) of the output
voltage and the output frequency. It is used for fan and pump, etc.
l 2 : Used for special purpose. It is possible for the users to set the ratio of the output voltage
and the output frequency voluntarily. It is also possible to set 2nd points of the frequency
and the voltage between the Starting frequency and the Base frequency. Therefore, four
points of User V/F pattern in total can be constructed. See from F14 to F17 for more
details.
Hold time
Output volts
DC Brak ing
Voltage
Output freq.
Hold time
RUN ON
29
FUNCTION GROUP 1
! Warning: If boost value is set too high, it can cause the motor to overheat
.
Output req.
S Curve Linear
100 %
31
l It is possible for the user to construct V/F pattern in accordance with load characteristics.
Be sure to set F6 to <2>.
FUNCTION GROUP 1
l F16 and F17 should be set to a value either higher than or the same as F14 and F15.
Output volts
! Caution: Be sure not to overheat 100% normal V/F
motor by making too much deviation from
normal V/F pattern.
F17
F15
Preset freq.
l 2 : Set the command frequency
Max. freq.
reference using both 4 to 20mA
and 0 to 10V.
4 mA 20 mA
<< Current input >>
32
33
FUNCTION GROUP 1
10V
time
Max.
l Input Bias : This sets the offset value for the freq.
50%
input signal.
0%
l If it is set to 50%, the target frequency is set to
<maximum frequency / 2> for the input signal of
0V(4mA) 10V(20mA)
0V (4mA).
34
FUNCTION GROUP 1
Max. Max.
freq. freq.
l This is to limit the output frequency of the drive. In case the set target frequency is not
within the range of the highest and lowest limit, the drive will run at the highest and lowest
limit frequency.
l It has a normal acceleration and deceleration rate below the lowest limit.
Max. freq.
High limit
Low limit
preset freq.
35
FUNCTION GROUP 1
Driving
freq.
Increasing
Decreasing
preset freq.
preset freq.
36
FUNCTION GROUP 1
Caution : There is a possibility that over-current trip takes place, if the block time of DC
brake is set to 0 sec since the DC voltage flows directly to the motor without free-run range.
37
FUNCTION GROUP 1
Setting range : 0 ~ 5 Hz
l Rated slip : It is set on the basis of the rated number of rotations shown on the motor slip
and the number of poles. If the rated number of rotation is 1740rpm(based on 60Hz), rated
slip can be calculated as follows.
Rated slip frequency = ( 1800 - 1740 ) x No. of pole / 120 = 2 Hz
38
FUNCTION GROUP 1
Auto Retry
Setting range : 0 ~ 10
Output freq. trip
Function related : F48 ~ F50
l The number of retry : Number of retrial attempts
by the drive after resetting itself from a trip.
t t time
l Retry time : Time delay before the drive resets
t : retry time
the trip and then engages retry..
l This is to prevent the motor from stopping itself due to a trip. If there is a trip, it is desirable
to get into normal run by using speed search functions (F48 - F50) along with retry
sequence. If the trip condition still exists after a complete set of retries, the drive stops
generating the output. In this case, the drive must be reset by using ‘RST’ terminal or the
Keypad of the drive. This feature enables hoist and crane to over-ride nuisance trips for its
continuous operation.
Setting range : 0 ~ 3
l 0 : The relay does not close when there is a Lv (low input voltage) trip and during the auto
retry sequence. However, it will close when the retry sequence has been completed and
the fault condition remains.
l 1 : The relay does not close in the state of Lv (low input voltage) trip.
l 2 : The relay does not close during auto retry sequence.
l 3 : The relay closes for every trip that occur.
l This function is used to set the operation mode of the fault relay in case of drive trip. Select a value
among 0 - 2, if there is no need for fault relay operation for Lv trip or during auto retry.
39
FUNCTION GROUP 1
Setting range : 0 ~ 7
Output
Function related : F35 current
l 0 : Stall prevention disable.
l 1 : Prevents stall during Accel.
l 2 : Prevents stall during Steady speed. stall level
Output DC Link
current voltage
stall level
Output Output
freq. freq.
time time
<< Preventing stall during normal speed >> << Preventing stall during Decel. >>
40
FUNCTION GROUP 1
MO-EXTG ON
Setting range : 0 ~ 30 sec
t t/2 time
l Warning time : If the output current is
over the warning level, the Multi-Function Output terminal (MO) is turned ON after this
preset warning time. The MO terminal is turned OFF after half of the warning time when the
output current is below the warning level.
l Drive output will cease if the drive output current lasts for more than preset time in excess
of current limit level (180% of the drive rated current).
41
FUNCTION GROUP 1
l Current limit level is shown below and the amount of current is in RMS value.
l 1 : ETH selection
l ETH level : This is the ratio of rated motor and drive output current times constant ‘k’.
l Motor type : Set to <0>, if a fan is attached to the motor shaft. If separate power drives the
motor fan, set to <1>.
l It is recommended to consider methods for separate motor cooling effect, especially when
operating at low speed. ETH level is set according to the rated current shown on motor’s
nameplate. The standard value of ETH operation is 60Hz, 1 min. Based on ETH level
setting value.
l Example :
42
FUNCTION GROUP 1
If the drive is 2.2kW (11Amp.) and the motor is 2.2kW (8.6Amp.), the ETH level is set
to 86% when running with 60Hz. Drive will cease output and make ETH trip if the output
current lasts more than 1 minute over 8.6 Ampere.
l Retry selection in IPF : The drive will engage in to Auto Retry mode after instantaneous
power failure(IPF). This will enable the hoist to lift its load without interruption during
instantaneous power failure.
l Accel./Decel. Time: Defines the accelerating and decelerating time during the speed
search sequence.
Input
power
Setting range : 0 ~ 5 sec
! Caution : This is suitable for the load with a high inertia moment. In case load is with a
high friction, it is recommended to use H51 (Reset Restart)
43
FUNCTION GROUP 1
Reset Restart
Power On Start
44
FUNCTION GROUP 1
l Carrier frequency can be adjusted to decrease audible noise from the motor. However, if
set too high, there can be increased electrical noise from the drive, leakage current, and
heating of the drive due to switching loss.
l Parameter read : This is to copy the parameters of the Main Group into the Key-pad.
l Parameter write : This is to copy the parameter stored in the Key-pad into the Main Group
of the drive.
l This function can be used to easily copy a parameter list to one or more drives. The
display of the key-pad will change from <1> to <F54(or F55)> if the transfer of data is
successful, while it displays <Err> when error occurs. In this case, press the FUNC key for
key-pad to display <0> again.
Read
iG Key-pad
iG drive
Key-pad
Write
Drive main unit
45
FUNCTION GROUP 1
Initializing of parameters
l This is to set all the parameters to the original factory setting values. Once the initializing
has completed, the display will change from <1> to <F56>.
! Caution : The capacity setting of the drive is to set <08.2> after initialization
sequence. Be sure to reset the drive ‘s capacity to that of the name plate data of the
drive.
Protection of parameters
l Setting protection function : The original factory setting doesn’t have protection function
and <57> displays <U0>. With the input of secret number <12>, the protection of
parameters is enabled.
FUNC FUNC
RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET
FUNC
FUNC FUNC
RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET RUN FWD REV SET
FUNC
46
FUNCTION GROUP 1
l This is to protect the preset parameters by using a secret number. And it is impossible to
change the parameters using the Key-pad, if the protection of parameters is already preset.
AVR Selection
47
FUNCTION GROUP 2
Setting range : 0 ~ 3
Function related : H3 ~ H11
l 0 : Use 8 different step speeds by using terminals ‘P1’, ‘P2’, and ‘P3’. The frequency of
each step is set via H3 and H9.
st nd rd th th th th th
1 2 3 4 5 6 7 8
speed speed speed speed speed speed speed speed
FX / RX ON ON ON ON ON ON ON ON
P1 OFF ON OFF ON OFF ON OFF ON
P2 OFF OFF ON ON OFF OFF ON ON
P3 OFF OFF OFF OFF ON ON ON ON
l 1 : Use 4 different step speeds using terminals as ‘P1’ and ‘P2’, while terminal ‘P3’ is used
as the external fault signal terminal. If terminal P3 is ON, the drive cuts off the output and
displays <Ext>.
l 2 : Use 4 different step speeds using terminals as ‘P1’ and ‘P2’, while terminal P3 is used
nd
as the 2 accelerating and decelerating trigger terminal. As shown in the picture below, if
‘P3’ is <OFF>, the drive accelerates according to the time set in ACC of Main Group, while
it accelerates according to the time set in ‘H10’ if P3 is ON.
l 3 : Use 2 different step speeds using ‘P1’,
nd
while terminal ‘P2’ is used for the ‘2
accelerating and decelerating time’, and Output freq.
‘P3’ is used for external fault signal input
terminal.
time
FX/RX ON
P3 ON
48
FUNCTION GROUP 2
Setting range : 0 ~ 4
Function related : F39, F41, H14, H15
l 0 : When the output frequency of the drive reaches ‘FDT’ value, ‘MO’ terminal (normally
closed, B) is turned ‘ON’. (refer to H14).
l 1 : When the output frequency of the drive reaches ‘FDT’ value, ‘MO’ terminal (normally
open, A) is turned ‘OFF’. (refer to H14)
l 2 : MO terminal is turned ‘ON’, while stall prevention is under way. (refer to F39)
l 3 : MO terminal is turned ‘ON’, when output current exceeds overload warning level. (refer
to F41)
l 4 : MO terminal is turned ‘ON’, when the input voltage falls below under-voltage level (Lv).
l 5 : MO terminal is turned ‘ON’, when the drive is running.
Output freq.
4
Setting range : 0 ~ Max. Freq. 3
2
Function related : H1
1
P2 ON ON
P3 ON
49
FUNCTION GROUP 2
Setting range : 0 ~ 2
Function related : H13
l 0 : Generates drive frequency output in the form of 0 to 10V at which 10V representing the
maximum frequency.
l 1 : Generates drive output voltage in the form of 0 to 10V at which 10V representing the
maximum drive output voltage.
l 2 : Generates drive output voltage in the form of 0 to 10V at which 10V representing the
maximum drive output current of 180%..
l It is possible to adjust the level of multi-function meter, Based on the output of 10V being
100% value, there will be an output of 12V if actual value is 120%.
5.5ms time
50
FUNCTION GROUP 2
l This sets frequency detection level. If drive output frequency is over the preset level, multi-
functional output terminal is turned ‘ON/OFF’. ‘H2’ should be set to <0> or <1>.
Setting range : 0 ~ 30 Hz
Function related : H14
l This sets the band of frequency detection level.
Output freq. detection freq. band Output freq. detection freq. band
MO-EXTG ON MO-EXTG ON ON
<< When H2 is set to ‘0’ >> << When H2 is set to ’1’ >>
JOG / BX Selection
51
FUNCTION GROUP 2
JOG-CM ON
FX-CM ON
RX-CM ON
l It is possible to monitor the condition of input terminals by using 7-segment LED of the
keypad. For instance, if FX and P2 terminals are ON (active), LED displays as below.
ON
OFF
RX FX RST P3 P2 P1
52
FUNCTION GROUP 2
Fault History 1, 2
l Drive collects and saves fault histories that occur during its operation. If the trip occurs
during its running sequence, Main Group displays trip information. If trip is removed by
using RESET key, information such as the trip content, frequency output, and current at the
time of the trip are saved in ‘H17’. It is possible to get the information about the frequency
and by using FUNC keys.
53
PROTECTIVE FUNCTION
Current limit Drive output is cut off, if the current reached over 180% of the drive’s
protection rated current during the time set at F43. (refer to F43).
Heat-Sink over-heat Drive output is cut off. Overheat caused by failed cooling effect is
detected by the temperature element which is attached to a heat-sink.
ETH Drive output is cut off when there is any over-current 100% greater
than that of rated current (F44 - F46). Overload capacity: 150% / 1
min.
External fault signal External Trip terminal is set. Check ‘H1’.
CPU error It cuts off the output of the drive when there is an error in main CPU
caused by system noise. It is possible to remove the error by pressing
STOP/RESET key.
Communication Error in the communication between the main unit and the key-pad,
error which has no influence to the drive operation. It can be removed by
replacing the key-pad.
54
TROUBLE SHOOTING
6. Trouble shooting
Protective
Causes Measures
Functions
Over-current l Faster Acceleration and Extend Acceleration and
2
protection Deceleration time than load GD Deceleration time.
l Larger load than the rating of the Upgrade the drive capacity.
drive
l Sudden ‘Run’ sequence in to Restart drive after motor stops.
coasting motor..
Over-voltage l Too short Deceleration time Extend Deceleration time.
2
protection compare to load GD
l Large regenerative energy on the Use larger regenerative
drive’s load side. resistor.
l Too high voltage source. Check the power voltage.
Current limit l Larger load than the drive’s Reset the motor and the drive
protection rating. capacity in accordance with load.
l Mistaken setting of the drive Reset the drive capacity.
capacity(F35)
l Mistaken setting of V/F pattern. Adjust V/F pattern.
Heat-Sink l Failed cooling fan or an alien Remove the alien substance or
overheat substance. replace the cooling fan.
l The abnormal condition in the Check the heat-sink.
cooling system.
l High ambient temperature. Lower the temperature below
40°C.
Electronic l Larger load than the rated Upgrade the drive capacity.
thermal current.
l Low ETH level. Adjust ETH level.
l Mistaken setting of the drive Reset the drive capacity
capacity.(F35)
l Mistaken setting of V/F pattern. Adjust V/F pattern.
External trip l Existence of External trip. Remove the failed circuit
signal connected with P3 (external trip
signal terminal) or check the
cause of external trip signal.
Under-voltage l Low voltage source. Check the power voltage.
protection l Larger load than the power Upgrade power capacity.
capacity.
l Failed or bad magnetic contactor Replace magnetic contactor.
in power.
55
MAINTENANCE
7. Maintenance
Since the iG series is an industrial electronic product with advanced semiconductor
element, it is likely to be influenced by temperature, humidity, and vibration and also there
can be some trouble caused by aging parts.
To avoid them, it is recommended to perform routine inspection.
7.1 Precautions
l Be sure to check the drive power input while performing maintenance.
l Be sure to operate only after checking discharge of power, because bus capacity in
electronic circuit is still charged even after the power is turned off.
l It is possible to measure correct output voltage only by using rectifier voltage meter.
Other voltage meters including digital voltage meter are likely to display error value
caused by high frequency PWM output voltage of the drive.
56
Functions Added (available from October 1, 1999)
Up-Down Operation Function (S/W Version: V3.3) : Drive output frequency can be
increased or decreased easily using Up-Down operation function.
Setting range: 0 ~ 4
Related functions: H3 ~ H11, F2, F4, F23, F24
Output Freq.
nd st
2 acceleration time (H10) 1 deceleration time (ACC)
Max. Freq.
(F4)
time
P1-CM
ON ON ON
P2-CM
ON ON ON
P3-CM
ON
FX-CM
ON
60