TIMBER STRUCTURE CALCULATIONS

----------------------------------------------------------------------------------------------------------------------------- -----------
CODE: EN 1995-1:2004/A2:2014
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----------
CODE GROUP:
MEMBER: 667 Timber Beam_667 POINT: 3 COORDINATE: x = 1.00 L =
0.501 m
----------------------------------------------------------------------------------------------------------------------------- -----------
LOADS:
Governing Load Case: 26 COMB3 (1+2+3)*1.35+5*1.50
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL GL24h
gM = 1.25 f m,0,k = 24.00 MPa f t,0,k = 19.20 MPa f c,0,k = 24.00 MPa
f v,k = 3.50 MPa f t,90,k = 0.50 MPa f c,90,k = 2.50 MPa E 0,moyen = 11500.00 MPa
E 0,05 = 9600.00 MPa G moyen = 650.00 MPa Service class: 1 Beta c = 0.10
----------------------------------------------------------------------------------------------------------------------------- -----------

SECTION PARAMETERS: MK 28c80


ht=80.0 cm
bf=28.0 cm Ay=1493.33 cm2 Az=1493.33 cm2 Ax=2240.00 cm2
tw=14.0 cm Iy=1194666.67 cm4 Iz=146346.67 cm4 Ix=456308.9 cm4
tf=14.0 cm Wy=29866.67 cm3 Wz=10453.33 cm3
----------------------------------------------------------------------------------------------------------------------------- -----------
STRESSES ALLOWABLE STRESSES
Sig_t,0,d = N/Ax = -4.12/2240.00 = -0.02 MPa f t,0,d = 9.95 MPa
Sig_m,y,d = MY/Wy= -313.54/29866.67 = -10.50 MPa f m,y,d = 11.52 MPa
Sig_m,z,d = MZ/Wz= -1.46/10453.33 = -0.14 MPa f m,z,d = 12.43 MPa
Tau y,d = 1.5*1.42/2240.00 = 0.01 MPa f v,d = 1.68 MPa
Tau z,d = 1.5*76.16/2240.00 = 0.51 MPa
Tau tory,d = 0.00 MPa, Tau torz,d = 0.01 MPa
-------------------------------------------------------------------------------------------------------------------------------- --------
Factors and additional parameters
km = 0.70 kh = 1.08 kmod = 0.60 Ksys = 1.00 kcr = 0.67
----------------------------------------------------------------------------------------------------------------------------------------

LATERAL BUCKLING PARAMETERS:


lef = 0.451 m Lambda_rel m = 0.13
Sig_cr = 1375.42 MPa k crit = 1.00
----------------------------------------------------------------------------------------------------------------------------- -----------
BUCKLING PARAMETERS:

About Y axis: About Z axis:


----------------------------------------------------------------------------------------------------------------------------- -----------
VERIFICATION FORMULAS:
Sig_t,0,d/f t,0,d + Sig_m,y,d/f m,y,d + km*Sig_m,z,d/f m,z,d = 0.92 < 1.00 (6.17)
Sig_m,y,d/(kcrit*f m,y,d) = 10.50/(1.00*11.52) = 0.91 < 1.00 (6.33)
(Tau y,d/kcr+Tau tory,d/kshape)/f v,d = 0.01 < 1.00 (Tau z,d/kcr+Tau torz,d/kshape)/f v,d = 0.46 < 1.00
(6.13-4)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS

Deflections (LOCAL SYSTEM):


u fin,y = 0.00 cm < u fin,max,y = L/200.00 = 0.25 cm Verified
Governing load case: (1+0.6)*1 + (1+0.6)*2 + (1+0.6)*3 + (1+0*0.6)*4
u fin,z = 0.01 cm < u fin,max,z = L/200.00 = 0.25 cm Verified
Governing load case: (1+0.6)*1 + (1+0.6)*2 + (1+0.6)*3 + (1+0*0.6)*4

Displacements (GLOBAL SYSTEM):


----------------------------------------------------------------------------------------------------------------------------- -----------
Section OK !!!

----------------------------------------------------------------------------------------------------------------------------- -----------
CODE: EN 1995-1:2004/A2:2014
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----------
CODE GROUP:
MEMBER: 723 Timber Beam_723 POINT: 3 COORDINATE: x = 1.00 L =
1.013 m
----------------------------------------------------------------------------------------------------------------------------- -----------
LOADS:
Governing Load Case: 26 COMB3 (1+2+3)*1.35+5*1.50
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL GL24h
gM = 1.25 f m,0,k = 24.00 MPa f t,0,k = 19.20 MPa f c,0,k = 24.00 MPa
f v,k = 3.50 MPa f t,90,k = 0.50 MPa f c,90,k = 2.50 MPa E 0,moyen = 11500.00 MPa
E 0,05 = 9600.00 MPa G moyen = 650.00 MPa Service class: 1 Beta c = 0.10
----------------------------------------------------------------------------------------------------------------------------- -----------

SECTION PARAMETERS: MK 28x100


ht=100.0 cm
bf=28.0 cm Ay=1866.67 cm2 Az=1866.67 cm2 Ax=2800.00 cm2
tw=14.0 cm Iy=2333333.33 cm4 Iz=182933.33 cm4 Ix=602655.6 cm4
tf=14.0 cm Wy=46666.67 cm3 Wz=13066.67 cm3
----------------------------------------------------------------------------------------------------------------------------- -----------
STRESSES ALLOWABLE STRESSES
Sig_c,0,d = N/Ax = 13.02/2800.00 = 0.05 MPa f c,0,d = 11.52 MPa
Sig_m,y,d = MY/Wy= 530.09/46666.67 = 11.36 MPa f m,y,d = 11.52 MPa
Sig_m,z,d = MZ/Wz= 0.35/13066.67 = 0.03 MPa f m,z,d = 12.43 MPa
Tau y,d = 1.5*-0.49/2800.00 = -0.00 MPa f v,d = 1.68 MPa
Tau z,d = 1.5*9.22/2800.00 = 0.05 MPa
Tau tory,d = 0.00 MPa, Tau torz,d = 0.00 MPa
----------------------------------------------------------------------------------------------------------------------------------- -----
Factors and additional parameters
km = 0.70 kh = 1.08 kmod = 0.60 Ksys = 1.00 kcr = 0.67
----------------------------------------------------------------------------------------------------------------------------------------

LATERAL BUCKLING PARAMETERS:


lef = 0.912 m Lambda_rel m = 0.21
Sig_cr = 559.48 MPa k crit = 1.00
----------------------------------------------------------------------------------------------------------------------------- -----------
BUCKLING PARAMETERS:

About Y axis: About Z axis:


----------------------------------------------------------------------------------------------------------------------------- -----------
VERIFICATION FORMULAS:
(Sig_c,0,d/f c,0,d)^2 + Sig_m,y,d/f m,y,d + km*Sig_m,z,d/f m,z,d = 0.99 < 1.00 (6.19)
Sig_m,y,d/(kcrit*f m,y,d) = 11.36/(1.00*11.52) = 0.99 < 1.00 (6.33)
(Tau y,d/kcr+Tau tory,d/kshape)/f v,d = 0.00 < 1.00 (Tau z,d/kcr+Tau torz,d/kshape)/f v,d = 0.05 < 1.00
(6.13-4)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS

Deflections (LOCAL SYSTEM):


u fin,y = 0.00 cm < u fin,max,y = L/200.00 = 0.51 cm Verified
Governing load case: (1+0.6)*1 + (1+0.6)*2 + (1+0.6)*3 + (1+0*0.6)*4
u fin,z = 0.02 cm < u fin,max,z = L/200.00 = 0.51 cm Verified
Governing load case: (1+0.6)*1 + (1+0.6)*2 + (1+0.6)*3 + (1+0*0.6)*4

Displacements (GLOBAL SYSTEM):


----------------------------------------------------------------------------------------------------------------------------- -----------
Section OK !!!

----------------------------------------------------------------------------------------------------------------------------- -----------
CODE: EN 1995-1:2004/A2:2014
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----------
CODE GROUP:
MEMBER: 787 Timber Beam_787 POINT: 3 COORDINATE: x = 1.00 L =
1.259 m
----------------------------------------------------------------------------------------------------------------------------- -----------
LOADS:
Governing Load Case: 26 COMB3 (1+2+3)*1.35+5*1.50
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL GL24h
gM = 1.25 f m,0,k = 24.00 MPa f t,0,k = 19.20 MPa f c,0,k = 24.00 MPa
f v,k = 3.50 MPa f t,90,k = 0.50 MPa f c,90,k = 2.50 MPa E 0,moyen = 11500.00 MPa
E 0,05 = 9600.00 MPa G moyen = 650.00 MPa Service class: 1 Beta c = 0.10
----------------------------------------------------------------------------------------------------------------------------- -----------

SECTION PARAMETERS: MK 28x180


ht=180.0 cm
bf=28.0 cm Ay=3360.00 cm2 Az=3360.00 cm2 Ax=5040.00 cm2
tw=14.0 cm Iy=13608000.00 cm4 Iz=329280.00 cm4 Ix=1188042.2 cm4
tf=14.0 cm Wy=151200.00 cm3 Wz=23520.00 cm3
----------------------------------------------------------------------------------------------------------------------------- -----------
STRESSES ALLOWABLE STRESSES
Sig_c,0,d = N/Ax = 137.21/5040.00 = 0.27 MPa f c,0,d = 11.52 MPa
Sig_m,y,d = MY/Wy= 1014.56/151200.00 = 6.71 MPa f m,y,d = 11.52 MPa
Sig_m,z,d = MZ/Wz= 0.19/23520.00 = 0.01 MPa f m,z,d = 12.43 MPa
Tau y,d = 1.5*0.09/5040.00 = 0.00 MPa f v,d = 1.68 MPa
Tau z,d = 1.5*-154.65/5040.00 = -0.46 MPa
Tau tory,d = 0.00 MPa, Tau torz,d = 0.00 MPa
------------------------------------------------------------------------------------------------------------------------------- ---------
Factors and additional parameters
km = 0.70 kh = 1.08 kmod = 0.60 Ksys = 1.00 kcr = 0.67
----------------------------------------------------------------------------------------------------------------------------------------

LATERAL BUCKLING PARAMETERS:


lef = 1.133 m Lambda_rel m = 0.30
Sig_cr = 261.78 MPa k crit = 1.00
----------------------------------------------------------------------------------------------------------------------------- -----------
BUCKLING PARAMETERS:
About Y axis: About Z axis:
----------------------------------------------------------------------------------------------------------------------------- -----------
VERIFICATION FORMULAS:
(Sig_c,0,d/f c,0,d)^2 + Sig_m,y,d/f m,y,d + km*Sig_m,z,d/f m,z,d = 0.58 < 1.00 (6.19)
Sig_m,y,d/(kcrit*f m,y,d) = 6.71/(1.00*11.52) = 0.58 < 1.00 (6.33)
(Tau y,d/kcr+Tau tory,d/kshape)/f v,d = 0.00 < 1.00 (Tau z,d/kcr+Tau torz,d/kshape)/f v,d = 0.41 < 1.00
(6.13-4)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS

Deflections (LOCAL SYSTEM):


u fin,y = 0.00 cm < u fin,max,y = L/200.00 = 0.63 cm Verified
Governing load case: (1+0.6)*1 + (1+0.6)*2 + (1+0.6)*3 + (1+0*0.6)*4
u fin,z = 0.01 cm < u fin,max,z = L/200.00 = 0.63 cm Verified
Governing load case: (1+0.6)*1 + (1+0.6)*2 + (1+0.6)*3 + (1+0*0.6)*4

Displacements (GLOBAL SYSTEM):


----------------------------------------------------------------------------------------------------------------------------- -----------
Section OK !!!