Вы находитесь на странице: 1из 5

Power quality

troubleshooting at the
service panel
Application Note

Voltage sags, tripping breakers,


overheated electrical panels, and
excessive voltage levels are all
indications of possible trouble in
an electrical distribution system.
It is helpful to understand that
these symptoms are telling us
something is wrong with the
power system. But where oh
where do you begin the search
to isolate the exact cause of
these power quality problems?
Just like cars have a single
connection point to monitor vital
functions, the electrical system
has a similar connection point:
the electrical service panel. As a
common point for branch circuit
distribution, the service panel is
also a convenient place to take
the pulse of your electrical sys-
tem. A number of problems can
be located right in the service
panel itself. For problems else-
where in the system, measure-
ments at the service panel can
tell you where to look next.
Some problems can be caught by
a quick visual inspection, while
others require that measure-
ments be taken.

Finding the cause of the


problem
This article outlines a step-by-
step process for locating and
Note fixing potential trouble spots.
1. Voltage level (steady state)
Prior to making any measurements, always familiarize yourself and voltage stability (sags)
with the equipment you will be using. Read the instrument users 2. Current balance and loading
manual paying particular attention to the WARNING and CAU- 3. Harmonics
TION sections. Do not use the measurement instruments in appli- 4. Grounding
cations for which they are not intended. Always be aware that if 5. Hot spots: loose connections/
the equipment is used in a manner not specified by the manufac- terminals
turer, the protection provided by the equipment may be impaired. 6. Bad or marginal branch circuit
breakers

From the Fluke Digital Library @ www.fluke.com/library


Depending on the voltage and
measurement requirements, you
can use a variety of tools for
power quality troubleshooting,
from digital multimeters to Downstream (Load)
handheld single and three Load V
phase power quality analyzers red
that perform many calculations
automatically. I
black
Voltage level and
Upstream (Source)
stability
The first step in checking to see V
M
if voltage levels and stability are
I
the culprits is to measure voltage
levels of the branch circuits,
phase-to-neutral, at the load side
of the branch circuit breakers.
Figure 1. Isolating source of disturbance.
Note: For safety’s sake, when
making voltage measurements
always keep a circuit breaker swell/surge), as well as the aver-
between you and the fault cur- age value of all the cycles in the
rent ampacity of the feeders. sample period. The sample
If voltage levels are low at the period is the elapsed time
breaker, they’ll be even lower at between one point and the next.
the receptacle. This could be The analyzer allows you to select
caused by low tap settings at the the sample time you want, with
transformer. Other likely culprits one second being the minimum
include loose connections, long period (this corresponds to a
feeder runs, and overloaded recording time of four minutes).
transformers, which create The cursor can be moved to the
excessively high source imped- desired point on the trend and,
ance (impedance from the load along with the min/max/average
to the source). Source impedance values, the real-time stamp of
and voltage drop are two sides the event is displayed.
Figure 2. Voltage on top, current on the
of the same coin. bottom. Real-time stamp on top.
On a three phase power qual-
If intermittent voltage sags are ity analyzer, the dips and swells
suspected, start at the panel to function can measure all three
isolate the cause of sags: Are the Connect the instrument’s volt- phases simultaneously (Figure 3).
sags the result of loads on the age probes and current clamps
same branch circuit or are they on the load side of the breaker,
caused by loads elsewhere in as shown in Figure 1. Using a
the distribution system (including single phase analyzer’s Sags &
utility-generated sags)? We can Swells mode, voltage events can
start to isolate the source of be trended on the top half-
the sag with a multi channel screen and current events on the
recording instrument, such as a bottom half-screen (Figure 2).
Fluke power quality analyzer, Each point on the trendplot (240
that can trend voltage and cur- total points for the full-screen
rent simultaneously. trend) represents three values in
the sample period: The lowest
single cycle (min or sag), the
highest single cycle (max or Figure 3. Voltage dip on three phases.

2 Fluke Corporation Power quality troubleshooting at the service panel


Upstream, downstream Current balance and So how do you measure for
loading CF? You need a true-rms DMM or
What information are you clamp, and in addition, the meter
looking for from the trendplots? To check current balance and needs to be able to measure the
• If a voltage sag occurs simul- loading, measure each feeder peak value of the current wave-
taneously with a current phase as well as current on each form. Harmonics analyzers or
surge, the sag was caused by branch circuit. When making ScopeMeter® test tools will also
a load on the branch circuit these measurements, it is criti- give you this measurement.
(Figure 2). In other words, the cally important to use a true-rms A three phase power quality
cause of the sag was down- clamp or true-rms digital multi- analyzer will calculate crest fac-
stream of the measurement meter (DMM) with a clamp-on tor and balancing automatically
point and therefore can be accessory. An average responding (Figure 4).
thought of as a load-related clamp-on meter will not provide
disturbance. an accurate measurement as the
• If, on the other hand, the volt- combination of fundamental and
age sag coincides with a very harmonic current makes this a
small change in current, the distorted waveform. A lower-cost
sag was likely caused by average-sensing meter will tend
something upstream of the to read low, which would lead
measurement point and can you to assume that the circuits
be thought of as a source- are more lightly loaded than they
related disturbance. Typical actually are. Here’s what we’re
source-related disturbances looking for when making this
are heavily loaded three- measurement:
phase motors started across- • The loading among the three Figure 4. Crest factor (CF).
the-line or sags originating on phases should be as balanced
the utility feed. If the sag is as possible. Unbalanced cur-
deep and approaches an out- rent will return on the neutral
age, the cause is more likely and, as we shall see, the neu-
to be the utility. The event tral already has enough to
probably reflects a fault and deal with.
breaker trip followed by auto- • Neither feeder nor branch cir-
matic breaker reclosure. cuits should be loaded to the
maximum allowable limit.
There should be some derating
to allow for harmonics.

As a safe and conservative rule-of-thumb, a short-cut formula


used for derating of transformers serving single-phase dc power
supply loads can be applied to conductors:
Harmonic Derating Factor (HDF) = 1.4 = (1.4) (RMS)
Crest Factor Amps Peak

This is a pretty straightforward


concept. Crest Factor (CF) is the
ratio of peak to rms. For a sine
wave, that value is 1.4. So for a
sine wave, which by definition
has no harmonic content and no
distortion, HDF = 1, meaning that
no derating is necessary. It only
goes downhill from there. If CF =
2, which is a more likely value for
branch circuits in offices, then
HDF = 1.4 / 2 = 0.70. So a con-
ductor rated for 20 A should only
be loaded to 70 percent capacity,
or 14 A max.

3 Fluke Corporation Power quality troubleshooting at the service panel


Harmonics
To check for the presence and
level of harmonics, measure
current on the feeder neutral.
This will typically be in the 80 to
130 percent range of the feeder
current, due to the fact that the
third harmonic will add up in the
neutral. Figure 5a shows some
readings that were made in an
office, at a lightly loaded panel.
These waveforms were captured
with a single phase power qual-
ity analyzer. Note that the neutral
current (Figure 5b) is far in excess
of what would be expected from
unbalanced currents alone.
Although most of us are
Figure 5a. Top screen shows waveform and rms amplitude of feeder phase current, bottom
increasingly aware of the fact screen shows amplitude of third harmonic.
that third harmonic currents (also
called triplen or zero sequence)
generated by non-linear, single-
phase loads add up in the neu-
tral, we often wonder why.
Figure 6 tries to explain this
phenomenon with an idealized
graphic. Basically, while there is
a 120-degree phase shift
between the three phases of the
fundamental, the third harmonic
on all three feeders are in-phase
with each other. That is, they all
reach their peaks and zero- Figure 5b. Neutral current.
crossing points at about the
same time (in reality, there is
some phase shift, but it is very percent of them had neutral cur-
little as compared with higher rent in excess of 100 percent of
order harmonics, and therefore phase current! The strong recom-
there is not much cancellation). mendation from the power qual-
This means that, first of all, the ity community therefore is that
triplens have nowhere to go but the neutral be double the size of
the neutral, and secondly, on the the phase conductor.
neutral all the peaks and all the Count the black and white
valleys add up. wires and if there are more black
The size of the feeder neutral than white wires, there is a good
conductor becomes a matter of possibility of shared neutrals. At
concern. The neutral must now that point, we should definitely
return not only unbalanced fun- measure the branch neutral cur-
damental current, but the sum of rents. Basically, the same thing
all the third harmonic current. is probably happening on the
The 2002 NEC 310.15(8)(4)(c) branch circuit as on the feeder
states that “On a four-wire, level; i.e., third harmonic cur-
three-phase wye circuit where rents will add up and possibly
the major portion of the load overload the shared neutral con-
consists of nonlinear loads, har- ductor. This is a distinct fire haz-
monic currents are present in the ard. The neutral, after all, has no
neutral conductor; the neutral circuit breaker to protect it.
shall therefore be considered. In A neutral ground voltage
effect, this requires that the neu- measurement will also show if
tral conductor at least equal the the neutral is too heavily loaded,
size of the phase conductor. But or if its source impedance is too
this may well be inadequate: For great. The neutral ground volt- Figure 6. Why third harmonic adds up on the neutral.
example, a 1990 survey of 146 age is usually in the 0.25 V third harmonic in each feeder is in-phase. There is no
sites nationwide found that 22.6 range at the panel, while the vector cancellation as there is with the fundamental
currents (which are 120 degrees out-of-phase).

4 Fluke Corporation Power quality troubleshooting at the service panel


actual value depends on the dis- more grounds, the better. In any energy. Emissivity is the
tance to the transformer. Any- case, remove all illegal neutral opposite of light reflection, in
thing above 0.5 V should be ground bonds - no exceptions. the sense that darker, non-
noted, and investigation made This is also a good time to polished surfaces have higher
about whether loads fed from check the tightness of conduit emissivity. Furthermore, most
that panel have experienced connections, especially if the low-cost infrared instruments
problems. What if, under normal conduit is being used exclusively are fixed at an emissivity of
loading, the neutral ground volt- as the grounding conductor. The 0.95, and the closer the sur-
age is close to zero? That leads recommended practice is for a face being measured comes to
us to the problem of illegal neu- green wire to be installed. this level of emissivity, the
tral ground bonds. more accurate the measure-
Hot spots ment. That’s why the surface
Grounding Poor connections and the result-
of black electrical tape will
result in more accurate read-
Neutral ground bonds in subpan- ing heat losses are the single ings than polished metal.
els are a violation of the NEC as greatest source of system ineffi-
well as of power quality per- ciency (according to a 1995
formance wiring, but they are study by the then Washington Circuit breakers
also quite common. Neutral State Energy Office). From the A lot of people don’t think of
ground bonds should be made at power quality point of view, breakers as having finite life-
the transformer (although the loose terminations are a major times. In reality, contacts and
NEC permits it to be made at the contributor to excessive source springs wear out. Measurements
main panel). In any case, it impedance. Fortunately, they are of circuit breaker voltage drop
should never be made down- easy to locate with a simple can help us determine the condi-
stream of the main panel, infrared thermometer. tion of the breaker. Measure
whether at a subpanel or a Infrared (IR) measurements across the line-to-load side of
receptacle. When a neutral with tools like the Fluke 60 the branch breaker. If the voltage
ground bond is made at a sub- Series are a safe and effective drop exceeds 100 mV, the
panel or receptacle, the ground technique for non-contact detec- breaker should be replaced. In
path becomes a parallel return tion of panel hot spots. However, the 35 to 100 mV range, read-
path for normal load current there are some key concepts that ings should be documented and
resulting in measurable current are crucial to understand if we’re trended.
on the ground. making these measurements: In summary, the service panel
What is normal ground cur- • How big or small an area are is the crossroad of the building’s
rent and what is abnormal? A we measuring? electrical system and the place
logical approach is to measure Optical resolution is the ratio where an experienced electrical
the neutral current and then the of the distance from the troubleshooter can start down
current on the green wire. If the measured object to the sam- the right path to locate and fix
neutral current is, let’s say, 70 A, pling spot size. If the ratio is any problems.
and the ground current is 2 A, 4:1, it means that if you are
the ground current is more likely four inches from the surface Fluke would like to thank
to be normal leakage (and there- being measured, you’re meas- Steve Uhrich of Valley Electric,
fore unavoidable). If the neutral uring a spot with a one-inch Mt. Vernon, WA, for sharing his
is 40 A and the ground current is diameter. experience and insight in the
20 A, there are likely to be some • Handheld infrared probes like writing of this article.
hard-wired neutral ground the Fluke 80PK-IR are most
bonds. The smaller the ratio of easily used for comparative
neutral to ground current, the temperature measurements,
more likely that an illegal neutral not absolute measurements. Fluke. Keeping your world
ground bond exists. Neutral For example, if we scan a up and running.
ground bonds can also exist in series of breakers or lugs with
receptacles and even in load the probe, we can easily
equipment, so we might have to determine if one is signifi- Fluke Corporation
PO Box 9090, Everett, WA USA 98206
use this same technique to cantly hotter than another.
measure for individual branch • If we really need to make Fluke Europe B.V.
PO Box 1186, 5602 BD
circuit ground currents. accurate measurements of Eindhoven, The Netherlands
If an illegal neutral ground absolute temperature with For more information call:
bond is found in one panel at a lower cost infrared instru- In the U.S.A. (800) 443-5853 or
site, it’s a good bet we’ll find it ments, the process gets more Fax (425) 446-5116
at others as well. The installer complicated. The short story is In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
may have been thinking that all that electrical tape should be In Canada (800) 36-FLUKE or
panels are wired like residential used to cover any highly pol- Fax (905) 890-6866
service panels, or that the quick- ished metallic surfaces. The From other countries +1 (425) 446-5500 or
est way to reduce neutral ground issue here is emissivity. Emis- Fax +1 (425) 446-5116
Web access: http://www.fluke.com
voltage was to install a jumper. sivity indicates the ability of
Or maybe he just felt that the an object to emit infrared ©2004 Fluke Corporation. All rights reserved.
Printed in U.S.A. 10/2004 1989143 A-US-N Rev B

5 Fluke Corporation Power quality troubleshooting at the service panel

Вам также может понравиться