In this state, the flow switch sensor is always on state position. When the
emergency fire case, the sprinkler heads are ruptured. So the water flow through the
flow switch sensor and sent the signal to pump control panel. In another state position,
the flow switch sensor is sent the signal to pump control panel when the pressure
leakage within the pipe.
The pressure switch is measured the water pressure in riser pipe of the fire
sprinkler system. In this simulation the pressure switch is used as a bar sensor. In
normal operation, over the 5.5 bar sensor the jockey pump is operated to restore the
pressure.
In emergency fire case, the sprinkler heads are ruptured and water flow
through the sprinkler heads and to limit and control the growth and expansion of fire.
So the water pressure drops in pipe. Between 3.5 bar sensor range, the pressure switch
sent the data to pump control panel to operate the fire pump 1.
When the pressure drop continuously under the 3.5 bar, 1 bar sensor range
sensor sent the data to pump control panel to operate the fire pump 2.
After emergency fire case, the operator presses the stop button. So the fire
pump operation system is reached the normal state. The flow switch is sense the water
flow in the pipe.