Вы находитесь на странице: 1из 2

   

 > Products > Products and Services for Factories and Plants > Products > Pressure Gauges (Pressure Sensors) and Differential Pressure Gauges (Differentia > 
Electronic Pressure and Differential Pressure Transmitters > AT9000 Advanced Transmitter SuperAce > Remote­sealed Differential Pressure Transmitters

Remote­sealed Differential Pressure Products

Transmitters Pressure Gauges (Pressure
Sensors) and Differential
Pressure Gauges (Differential
pressure sensors)

Electronic Pressure and
Differential Pressure
Transmitters

Differential Pressure
Specifications Transmitter/Pressure
Transmitters AT9000
Advanced Transmitter
SuperAce

AT9000 SuperAce Remote­sealed Differential Pressure Transmitters (JTE series) are used to measure the
Differential
differential pressure (flow rate, fluid level, etc.) of very hot as well as highly corrosive and condensable fluids. Pressure
We offer an extensive lineup, including small bore flange models starting at 40 mm and models for high Transmitter
temperature (including high temperature high vacuum) applications.
Flange­Mounted
Differential
Pressure
Remote­sealed Differential Pressure Transmitters
Transmitters

Main specifications Remote­sealed
Differential
Pressure
Model JTE929* JTE930*
Transmitters

Measurement span 2.5 to 100 kPa 35 to 700 kPa Sanitary Differential


Pressure / Pressure

Setting range ­100 to 100 kPa ­100 to 700 kPa Transmitters

Reference accuracy Gauge Pressure
(Varies by material and ±0.15% ±0.15% Transmitters
measurement span)
Remote­sealed
Silicone oil (for the following models: general purpose, high temperature, high Gauge Pressure
Fill fluid temperature vacuum, and high temperature high vacuum) Transmitters

Fluorine oil (oxygen and chlorine models)
Absolute Pressure
Waterproof and dust­proof Transmitters
IEC IP66/IP67
construction
Remote­Seal
Explosion­proof Absolute Pressure
TIIS explosion proof (Exd IICT4)
construction Transmitters

Range of operating
Silicone oil: ­40 to 280 °C (varies with fill fluid)
temperatures for liquid part
Fluorine oil: ­10 to 120 °C Related Information
(Varies with pressure)

Range of operating Case Studies
Silicone oil for general purpose and high temperature models: from 2 kPa abs
pressures for liquid part
High temperature vacuum and high temperature high vacuum models: from 0.13 Document Download
(Varies with temperature)
kPa abs
Fluorine oil: from 53 kPa abs Terms and Conditions
Sitemap
Wetted material SUS316 (diaphragm SUS316L), Hastelloy C, Tantalum

Power 17.9 to 42 V DC

4 to 20 mA DC (SFN communication)
Output signal
4 to 20 mA DC (HART® communication)

Flush models: 80 mm, 50 mm, 40 mm. Protruding models: 100 mm, 80 mm, 50
Flange bore
mm

Page Top 

Feel free to contact us for consultation or inquiries regarding these products.

Online Inquiries

Inquiry Form

Trademark Information Usage Policy Sitemap

Вам также может понравиться