irant operates several generat- and water monitor on the suspect trans-
ing plants in North America, former. The selected IED (Intelligent
Asia and the Caribbean. In late Electronic Device), a Calisto monitor Table 1: DGA results - Nov. 11, 2001
2001, routine DGA (Dissolved Gas from Morgan Schaffer Systems in Dissolved gases Concentration
Analysis) performed on a Mirant Mid- Montreal, Canada, was installed. Figure (ppm)
Atlantic 650 MVA GSU built in 1969, 1 describes the main features of the
lead the electrical maintenance crew to instrument which continuously measures Hydrogen 392
believe an incipient fault was developing the concentration of dissolved hydrogen Methane 594
in the transformer. Table 1 provides an in oil in ppm. Dissolved water content is Carbon monoxide 736
example of the DGA values obtained at also continuously measured and can be Carbon dioxide 5900
that time. reported in ppm, %RS (Relative Ethylene 260
Routine DGA tests during the 6- Saturation) at 25°C, or %RS at a specific Ethane 260
month period following the above-men- transformer oil temperature if this value Acetylene n/d
tioned analysis showed no significant is available as an input to the monitor (4-
changes in fault gas concentrations. 20 mA or Jtype thermocouple input).
However, the decision was made to As opposed to other sensors of this i.e. the circulating oil is either cooled or
increase the DGA testing frequency and type, the Calisto monitor features its own heated to a set point prior to making dis-
to install an on-line dissolved hydrogen oil circulation and conditioning system, solved hydrogen and water measure-
Figure 2A: Transformer sup- Figure 2B: Transformer return Figure 3: Mounting of
ply valve valve enclosure
IED INSTALLATION
As the IED continuously circulates
oil to get access to representative dielec-
tric fluid from the transformer, connec- Calisto, from Morgan Schaffer Systems, is
tion to independent supply and return a highly accurate IED designed to detect
valves on the transformer is required. incipient faults and to monitor moisture
Figures 2A and 2B provide details on the content in critical oil-filled transformers.
connections of the oil supply and return
lines and Figure 3 provides an overview
of the enclosure mounting. Standard cop-
per tubing and off-the-shelf fittings are
used to make the oil line connections.
TRANSFORMER REPORT
Dissolved gases May 30, 2002 July 8, 2002 Sept. 17, 2002