COMMISSIONING AND
MAINTENANCE GUIDE
Commissioning and Maintenance P12y/EN CM/C22
CONTENT
4. SETTING CHECK 10
4.1 Settings 10
4.2 Measurements 10
4.2.1 MiCOM P125 10
4.2.2 MiCOM P126 11
4.2.3 MiCOM P127 11
4.3 Thresholds validation 12
4.3.1 MiCOM settings 12
4.3.2 MiCOM P125 Settings 12
4.3.3 MiCOM P126 Settings 13
4.3.4 MiCOM P127 settings 14
4.3.5 Earth current and neutral voltage test 15
4.4 Final checks 19
P12y/EN CM/C22 Commissioning and Maintenance
5. MAINTENANCE 20
5.1 Equipment failure 20
5.1.1 Minor fault 20
5.1.2 Major fault 20
5.1.3 Hardware and software faults 20
5.2 Method of repair 21
5.2.1 Replacing the active part 21
5.2.2 Replacing the complete relay 21
5.2.3 Changing the battery (MiCOM P126 & P127 only) 21
5.3 Problem solving 22
5.3.1 Password lost or not accepted 22
5.3.2 Communication 22
5.4 MiCOM relay no longer responds 22
5.4.1 A remote command is not taken in account 23
Commissioning and Maintenance P12y/EN CM/C22
• Extracting the settings applied to the relay using the appropriate setting software
(preferred method)
P1 S1
P2 S2
Other ends
of electrical cables
P0041ENa
P1 S1 _
+ mA
+
_
P2 S2
P0043ENa
OP. PARAMETERS/Inputs
Input MiCOM P12x models
Satuts. cell value
Opto input 1
P125, P126, P127 0000001
22-24 Terminals
Opto input 2
P125, P126, P127 0000010
26-28 Terminals
Opto input 3
P125, P126, P127 0000100
17-19 Terminals
Opto input 4
P125, P126, P127 0001000
21-23 Terminals
Opto input 5
P126, P127 0010000
25-27 Terminals
Opto input 6
P126, P127 0100000
58-60 Terminals
Opto input 7
P126, P127 1000000
57-59 Terminals
Commissioning and Maintenance P12y/EN CM/C22
OP. PARAMETERS/Relay
OUTPUT RELAYS MiCOM P125 range
Status. cell value
WD Relay Terminals 35-37 P125, P126 and P127 Normal close
RL 1 Change over type.
Terminals : P125, P126 and P127 00000001
2 Common -4 NC-6 NO
RL 2 Change over type.
Terminals : P125, P126 and P127 00000010
8 Common -10 NC-12 NO
RL 3 Terminals 14-16 P125, P126 and P127 00000100
RL 4 Terminals 18-20 P125, P126 and P127 00001000
RL 5 Terminals 1-3 P125, P126 and P127 00010000
RL 6 Terminals 7-8 P125, P126 and P127 00100000
RL 7 Terminals 9-11 P126 and P127 01000000
RL 8 Terminals 13-15 P126 and P127 10000000
4. SETTING CHECK
The setting checks must ensure that all relay settings have been correctly applied to the
relay for the specific application.
Transfer the setting file to the relay using a laptop PC running the appropriate software via
the RS232 front port or the RS485 rear port.
This is the preferred setting transfer method, because it is faster and there are fewer margins
for errors.
If the setting software is not used, the relay settings must be checked manually via the relay
front panel interface.
The commissioning checks are as follows:
1. Settings verify and delivery to customer
2. Validation of the measurements
3. Validation of the thresholds and associated timers.
4.1 Settings
Log the settings on the commissioning test sheets.
4.2 Measurements
The MiCOM P125 P126 P127 relays measure phase and earth currents, phase (phase to
phase) voltage, zero sequence voltage as a True RMS value up to the 10th harmonics. The
value(s) indicated take account of the phase and/or earth CT ratio and VT ratio.
WARNING : MiCOM P125 P126 P127 RELAYS HAVE 1 AND 5 A CURRENT INPUTS,
AND 57 –130V OR 220 – 480V VOLTAGE INPUT.
CHECK THAT THE INJECTED CURRENT AND VOLTAGE ARE
COMPATIBLE WITH THE SELECTED RANGE.
• Apply current to input terminals 55-56 (Ien=1A) or 47-48 (Ien=5A) and verify the IN
value shown on the LCD taking in account the relevant nominal current.
• Apply earth voltage to 39-40 terminals and verify in measurements menu the UN value
shown on LCD.
• Log the results to the Commissioning test sheets (Applied value and relay value
displayed).
Commissioning and Maintenance P12y/EN CM/C22
• Note the select phase and earth CTs ratio and neutral VT ratio.
• Apply current to input terminals 49-50 (In=1A) or 41-42 (In=5A) and verify the IA value
shown on the LCD.
• Apply current to input terminals 51-52 (In=1A) or 43-44 (In=5A) and verify the IB value
shown on the LCD.
• Apply current to input terminals 53-54 (In=1A) or 45-46 (In=5A) and verify the IC value
shown on the LCD.
• Apply current to input terminals 55-56 (Ien=1A) or 47-48 (Ien=5A) and verify the IN
values on the LCD in relay measurement menu.
• Apply earth voltage to 73-74 terminals and verify the UN values on the LCD in relay
measurement menu.
• Log the results to the Commissioning test sheets (Applied values and relay values
displayed).
4.2.3 MiCOM P127
• Note the select phase and earth CTs ratio, phase voltage VTs ratio and neutral
voltage VTs ratio.
• Apply current to input terminals 49-50 (In=1A) or 41-42 (In=5A) and verify the IA value
shown on the LCD.
• Apply current to input terminals 51-52 (In=1A) or 43-44 (In=5A) and verify the IB value
shown on the LCD.
• Apply current to input terminals 53-54 (In=1A) or 45-46 (In=5A) and verify the IC value
shown on the LCD.
• Apply current to input terminals 55-56 (Ien=1A) or 47-48 (Ien=5A) and verify the IN
values on the LCD in relay measurement menu.
• Apply voltage to inputs terminals 69-70 and 71-72 and verify the UAB and UBC values
in relay measurement menu on the LCD.
• Apply current to input terminals 55-56 (Ien=1A) or 47-48 (Ien=5A) and verify the IN
value in relay measurement menu on the LCD.
• Apply voltage to inputs terminals 73-74 and verify the UN value in relay measurement
menu on the LCD.
Log the results to the Commissioning test sheets (Applied values and relay values
displayed).
P12y/EN CM/C22 Commissioning and Maintenance
Configuration Menu
Transfo. Ratio
E/Gnd CT primary 1A
E/Gnd CT Sec 1A
E/Gnd VT primary 0.100 kV
E/Gnd VT Sec 100.0 V
Protection Menu
Ie> Yes
Ie> 1 Ien
tIe> DT or IDMT or RI
tIe> (if DT) 10 s
Curve (if IDMT) IEC VI or IEEE VI
TMS value (if IDMT) 1
K value (if RI) 1
Ue>>>> 10 V
tUe>>>> 10 s
Automation Menu
TRIP tIe> YES
TRIP tUe>>>> YES
Commissioning and Maintenance P12y/EN CM/C22
Configuration menu
Transfo. Ratio
Line CT primary 1A
Line CT Sec 1A
E/Gnd CT primary 1A
E/Gnd CT Sec 1A
E/Gnd VT primary 0.100 kV
E/Gnd VT Sec 100.0 V
Protection Menu G1
I> Yes
I> 1 In
tI> DT or IDMT or RI
tI> (if DT) 10 s
Curve (if IDMT) IEC VI or IEEE VI
TMS value (if IDMT) 1
K value (if RI) 1
Ie> Yes
Ie> 1 In
tIe> DT or IDMT or RI
tIe> (if DT) 20 s
Curve (if IDMT) IEC VI or IEEE VI
TMS value (if IDMT)1 K value (if RI)1
Ue>>>> 10V
tUe>>>> 10 s
Automation Menu
TRIP tI> YES
TRIP tIe> YES
TRIP tUe>>>> YES
P12y/EN CM/C22 Commissioning and Maintenance
CONFIGURATION
General Options
2Vpp+Vr
Transfo. Ratio
Line CT primary 1A
Line CT Sec 1A
E/Gnd CT primary 1A
E/Gnd CT Sec 1A
Line VT primary 0.100 kV
Line VT Sec 100.0 V
E/Gnd VT primary 0.100 kV
E/Gnd VT Sec 100.0 V
Protection Menu G1
I> Yes
I> 1 In
tI> DT or IDMT or RI
tI> (if DT) 10 s
Curve (if IDMT) IEC VI or IEEE VI
TMS value (if IDMT) 1
K value (if RI) 1
U> Yes
U> 20V
tU> 10 s
Ie> Yes
Ie> 1 In
tIe> DT or IDMT or RI
tIe> (if DT) 20 s
Curve (if IDMT) IEC VI or IEEE VI
TMS value (if IDMT)1 K value (if RI)=1
Ue>>>> 10 V
tUe>>>> 10 s
Automation Menu
TRIP tI> YES
TRIP tU> YES
TRIP tIe> YES
TRIP Ue>>>> YES
Commissioning and Maintenance P12y/EN CM/C22
• Supply the relay, inject current and voltage with magnitude greater then Ie> and
Ue>>>> setting value.
• If the time delay tIe> is short, gradually increases injection current up to the value of
the Ie> threshold.
• If the time delay tIe> is long, inject 0.95 x I threshold and check that there is no
tripping. Then inject 1,1 x Ie threshold and check the trip.
• Gradually decreases the injected current and record the value of the drop out Ie>
threshold.
• Checks:
• Trip LED on
• Ie>, tIe>
• Supply the relay inject a current equal to 2 x Ie> threshold into one of the earth current
inputs. Repeat the operation for various current values (n x Ie threshold with n ranging
from 4 to 10, for example). Check that the values measured correspond to those
indicated in the table below (for TMS=1).
P12y/EN CM/C22 Commissioning and Maintenance
IEC curves
IEEE/ANSI curves
Checks:
• Trip LED on
• If the time delay tI> is short, gradually increase the injection current up to the value of
the I> threshold.
• If the time delay tI> is long, inject 0.95 x I threshold and check that there is no tripping.
Then inject 1,1 x I threshold and check the trip.
• Gradually decrease the injected current and record the value of the drop out off (I>
threshold).
Commissioning and Maintenance P12y/EN CM/C22
Checks:
• Trip LED on
• Apply a current into one of the phases and measure the time delay tI> by pre-setting
the current above the I> threshold (I injected > 2 x I threshold).
• Apply a current onto one of the phases and measure the time delay tI> by pre-setting
the current above the I> threshold (I injected > 10 x I threshold).
Checks:
• Alarm message on the LCD display for I> after that the setting trip delay time is
expired.
• Alarm LED flashes > after that the setting trip delay time is expired.
• Trip LED on after that the setting trip delay time is expired.
• I> threshold LED on (if programmed) > after that the setting trip delay time is expired.
• Trip output closes > after that the setting trip delay time is expired..
• I> threshold output closes (if programmed) > after that the setting trip delay time is
expired.
Delay type: Inverse time (IDMT)
Used threshold for this test:
• I>, tI>
• Supply the relay, inject a current equal to 2 x I> threshold into one of the earth current
inputs. Repeat the operation for various current values (n x Ie threshold with n ranging
from 4 to 10, for example). Check that the values measured correspond to those
indicated in the table below (for TMS=1).
IEC curves
IEEE/ANSI curves
RI electromechanical curve
For other injected current values, compare the values found with the theoretical values
calculated according to the formula of the curves.
NOTE : Equations of IEC, IEEE/ANSI and RI curves are given in chapter
P12y/EN TD of this Technical Guide.
Checks:
• Trip LED on
• If tU> time delay is short, gradually raise the injection voltage up to the value of U>
threshold.
• If U> time delay is long, inject 0.95 x U> threshold setting and check there is no trip.
Then inject 1.1 x U> threshold setting and check the trip output is close.
• Gradually lower the injected current and note the value of the drop out U> threshold.
Commissioning and Maintenance P12y/EN CM/C22
Checks:
• Alarm message on the LCD display for U> after that the setting trip delay time is
expired.
• Alarm LED flashes after that the setting trip delay time is expired.
• Trip LED on, after that the setting trip delay time is expired.
• U> threshold LED on (if programmed) > after that the setting trip delay time is expired.
• Trip output closes U> after that the setting trip delay time is expired..
• U> threshold output closes (if programmed) after that the setting trip delay time is
expired.
4.4 Final checks
1. Remove all test or temporary shorting leads, etc… If it is necessary to disconnect any
of the external wiring from the relay in order to perform the wiring verification tests, it
should be ensured that all connections are replace in accordance with the relevant
external connection or scheme diagram.
2. If a MMLG test block is installed, remove the MMLB01 test plug and replace the
MMLG cover so that the protection is put into service.
3. For MiCOM P126 and P127 models, ensure that all event, fault and disturbance
records, alarm and LEDs have been reset before leaving the relay.
4. If the relays are in a new installation or the circuit breaker has been just maintained,
the circuit breaker maintenance and current counters should be zero. These counters
(only P126 & P127) have to be reset using relevant command in RECORD/CB
Monitoring menu (refer to User Guide).
P12y/EN CM/C22 Commissioning and Maintenance
5. MAINTENANCE
5.1 Equipment failure
MiCOM P125, P126 and P127 relays are full digital and permanent self-diagnosing. Any
failure of software or hardware elements is instantly detected. As soon as an internal fault is
detected, depending on its type (minor or major), an alarm message is displayed as a priority
on the front panel LCD before the fault LED is illuminated (fixed or flashing) and the
watchdog relay is closed (if the fault is a major one).
An equipment failure (major or minor) cannot be acknowledged on the front panel (using the
dedicated tactile button keypad). Only the disappearance of the cause will acknowledge the
fault and hence reset the fault LED.
5.1.1 Minor fault
Regarded by the MiCOM P125, P126 and P127 relays as a minor fault is a communication
failure. If the communication is in fault, MiCOM P125, P126 and P127 protection and
automation modules are not affected.
Message :
"COMM.ERROR" : Communication fault
Cause :
Hardware or software failure of the communication module
Action :
Withdraw the active part and return it to the factory for repair.
Alternative :
If communication is not used, disable communication in the COMMUNICATION menu
(Communication ? = No).
5.1.2 Major fault
Major fault for MiCOM P125, P126 and P127 relays are all software and hardware failures
except the communication faults. As soon as this type of failure is detected, the watchdog
(WD) is closed and all operations are stopped (protection, automation, communication).
5.1.3 Hardware and software faults
Messages :
"EEPROM ERROR DATA" : Data zone in fault
"EEPROM ERROR CALIBR." : Calibration zone in fault
"CT ERROR" : Analogue channel in fault
"RAM ERROR" : Ram supplied by battery in fault (see below of this Commissioning and
Maintenance Guide)
Cause :
Hardware or software failure
Action :
Restart the protection software.
If the software fault still remain after restart, withdraw the active part and return the module
to the factory for repair.
Commissioning and Maintenance P12y/EN CM/C22
• Gently extract the battery from its socket. If necessary, use a small screwdriver.
• Ensure that metal terminals in the battery socket are free from corrosion, grease and
dust.
• The replacement battery should be removed from its packaging and placed into the
battery holder, ensure that the polarity markings on the battery agree with those
adjacent to the socket.
NOTE : Only use a type 1/2AA lithium battery with a nominal voltage of 3.6 V.
P12y/EN CM/C22 Commissioning and Maintenance
• Ensure that the battery is securely held in its socket and that the battery terminals are
making good contact with the metal terminals of the socket.
BLANK PAGE