Selection and application guide

The information provided in this brochure contains merely


general descriptions or characteristics of performance
Siemens Energy & Automation, Inc. Subject to change without prior notice
Industry Sector
3333 Old Milton Parkway
Alpharetta, GA 30005
Order No.: RPSA-POMOD-0409
Printed in USA
© 2009 Siemens Energy & Automation, Inc.
which in case of actual use do not always apply as described
or which may change as a result of further development
of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the
Power Mod™ with QuickSystem™
1-800-964-4114 terms of contract.

info.sea@siemens.com All product designations may be trademarks or product

www.sea.siemens.com/powermod
names of Siemens AG or supplier companies whose use by Answers for industry.
third parties for their own purposes could violate the rights
of the owners.
One-pole AFCI Two-pole AFCI

$PNCJOBUJPO5ZQF"'$*
NSiemens offers multiple ways to save the contractor time and money.

NThe industry’s only Combination Type AFCI that visually indicates


overcurrent, arc fault, and arc fault to ground conditions.

NThe industy’s first two-pole Combination Type AFCI for shared


neutral circuits.

NOn-board memory: Trip indications are stored for up to 30 days allowing


the contractor to diagnose the cause of a tripped CAFCI after the
trip occurred.
1PXFS.PEt

Siemens is proud to introduce Power Mod™ with QuickSystem™ - a new robust and feature-
rich line of modular metering designed with the contractor in mind. Power Mod features a
unique combination of labor saving features to aid the contractor while installing the product.
QuickSystem encompasses every step of installation of the product - from mounting the product
on the wall to plugging in the tenant circuit breaker - these five key features were specifically
engineered to decrease installation time. Power Mod offers a wide range of products to meet
applications for virtually every need.

From our new underground only mains for EUSERC applications to our exclusive six high 225
Amp Residential Meter Stack - Siemens can meet your multi family metering needs. Quality
and service are keystones of the Power Mod line. Siemens Power Mod has been tested to all
applicable UL and ANSI standards as well as Siemens’ own rigorous internal specifications.
Every module offers 1200 Amp thru-bussing as a standard feature. Every meter stack offers
fully rated vertical bussing. All of this delivered at a competitive time and price to other, lower
rated products.

*OUSPEVDUJPO
www.sea.siemens.com/powermod


Power Mod
QuickSystem™ Features
Contractor-focused features, robust quality, dependable service, and exclusive products define Siemens Power Mod. The new
standard in multi family metering. QuickSystem showcases the key strengths of Power Mod through five labor saving features:

Siemens
exclusive
QuickConnect™ feature

A Siemens exclusive feature, QuickConnect reduces


bussing connections from many to one - ensuring a single
reliable connection instead of multiple connections.

QuickTorque™

Eliminates the need for time consuming torque readings,


this breakaway nut provides the correct indication of
torque of the QuickConnect. When tightened, the outer
head twists off at the proper torque for connection,
leaving a single nut for future maintenance.

Siemens
exclusive
QuickBolt™ feature

A Siemens exclusive feature, QuickBolt eliminates the


requirement to line up mechanical connections - instead
bolts remain retracted until the openings line up- allowing
the bolts to protrude through automatically. Springs push
the bolts through and provide positive pressure to keep
bolts in place while wingnuts are attached and tightened.

Siemens
exclusive
QuickRoll™ feature

A Siemens exclusive feature, QuickRoll eliminates the


typical metal brackets for mounting modules to the wall.
Instead of metal scraping metal, QuickRoll allows the
module to glide down the mounting rail via a durable
nylon wheel inside a mounting bracket.

QuickPhase™

Each individual meter position can be phased indepen-


dently according to the users needs. QuickPhase allows
the user the ultimate flexibility to adjust to each individual
application.

s | Power Mod™ with QuickSystem™


1-2
1PXFS.PE
Product Information

4JFNFOT.PEVMBS.FUFSJOHJODMVEFTBOBTTPSUNFOUPGNPEVMFUZQFTUIBUDBOCFDPOÙHVSFEUPNFFUBXJEFSBOHFPGSFTJEFOUJBMBOE
DPNNFSDJBMHSPVQNFUFSJOHBQQMJDBUJPOT

4JFNFOTNPEVMBSNFUFSJOHQSPWJEFTGPSTJOHMFQIBTF UISFFXJSF 7"$UISFFQIBTF GPVSXJSF:
BQQMJDBUJPOT BOEUISFFQIBTFJOPVU 7PMUNBYEFMUBTZTUFNT5IFDSPTTCVTUIBUDPOOFDUTEFWJDFTJTBMVNJOVNBOEIBTB
"NQDPOUJOVPVTDVSSFOUSBUJOH

"UZQJDBMBQQMJDBUJPOSFRVJSFTBNBJOEFWJDFNPEVMFBOEPOFPSNPSFSFTJEFOUJBMPSDPNNFSDJBMNFUFSTUBDLT%FQFOEJOHPOUIF
BQQMJDBUJPOBEEJUJPOBMNPEVMFTTVDIBTQVMMCPY UBQCPY PSBTQBDFSNBZCFSFRVJSFE

2VJDL$POOFDUt
5IFUJNFTBWJOH2VJDL$POOFDUt 2$
QSPWJEFTBTJOHMFDPOOFDUJPOGPSQIBTF OFVUSBM BOE
HSPVOEqBMMUJHIUFOFECZBTJOHMFOVUUIBUJTFYUFSOBMMZBDDFTTJCMF#FWFMFEFEHFTPOUIF2$
BMMPXGPSFBTZQPTJUJPOJOHPGUIFKPJOU'BDUPSZJOTUBMMFE2VJDL#PMUtTQSJOHMPBEFECPMUTBSF
MPDBUFEKVTUBCPWFBOECFMPXUIF2$PQFOJOHUPDPNQSFTTUIFTVSSPVOEJOHHBTLFUTUPHFUIFS
UPGPSNBXBUFSUJHIUTFBM'PSFYUSBTUBCJMJUZBEEJUJPOBMOVUTBOECPMUTBCPWFBOECFMPX
2VJDL#PMUTBSFJODMVEFEBTBNFBOTPGQIZTJDBMMZKPJOJOHUIFNFUFSTUBDLTUPHFUIFSCPUI
BCPWFBOECFMPXUIF2$PQFOJOH

#VT$POTUSVDUJPO
6ONFUFSFECVTJTTVSSPVOEFECZBCBSSJFSBOEBMMJOBDDFTTJCMFCVTDPOOFDUJPOTBSF
XFMEFEGPSNBYJNVNTUSFOHUI"MMPUIFSDPOOFDUJPOT2VJDL$POOFDUtBOENFUFSTPDLFU
DPOOFDUJPOT BSFCPMUFEBOEBDDFTTJCMF

/FVUSBM(SPVOE1SPWJTJPOT
Siemens 8...PEVMF/FVUSBM(SPVOE1SPWJTJPOTBSFMPDBUFEPOUIFCPUUPNFOEPGUIFNFUFS
exclusive NPEVMFT"MMHSPVOETBOEOFVUSBMTNBZCFSFMPDBUFEUPUIFUPQPGUIFFODMPTVSFJGBUPQFYJU
feature JTOFFEFE&BDINFUFSNPEVMFIBTIBMGTIFBSTUPIFMQMPDBUFBÙFMEDVULOPDLPVUJGBUPQFYJU
JTQSFGFSSFE

5FOBOU#SFBLFS1SPWJTJPOT
&BDI"NQNFUFSTPDLFUIBTBQSPWJTJPOGPSBQPMF"NBYQMVHJOUZQF24DJSDVJU
CSFBLFS5IFDPNQBDU24CSFBLFSÙUTJOUXPJODIFTBOESFEVDFTFODMPTVSFTJ[FMJNJUFEUPUBM
NPVOUJOHTQBDFSFRVJSFE4JOHMFSJHIUIBOECFOEXJSJOHTBWFTUJNFBOEXJSF*OTFSUB"
21JOUPB"NQ24TMPUXJUIPVUDPOWFSTJPOLJUTPSÙMMFSQMBUFT(FOFSPVTHVUUFSTQBDF
BMMPXTGPSXJSJOHGPSUPQ CPUUPN PSCBDLPGUIFNFUFSNPEVMF&BDINFUFSDPWFSJT
FNCPTTFEUPQSPWJEFBMPDBUJPOGPSUIFVOJU BQBSUNFOU
OVNCFS

8...PEVMFGBDUPSZQIBTJOHJTBTGPMMPXT
(BOH"# #$
(BOH"# #$ $"
(BOH"# #$ $" "#
(BOH"# #$ $" "# #$
(BOH"# #$ $" "# #$ $"
"OZQPTJUJPODBOCFBEKVTUFEUPBOZQIBTF

s | Power Mod™ with QuickSystem™



Power Mod
Features

Siemens Power Mod offers a wide array of modules to meet the needs of almost any 240V application. Modules are grouped and
categorized by function and type to facilitate the selection and ordering process. The basic modules are:
Standard Breaker Modules (type WB)
These modules are designed for line and load side applications ranging from 200 to 2000 Amps at 240V
AC Max. For 1200 Amp and below modules compression lug landing pads can be field installed and devices
are rated for overhead and underground feed. 1600-2000 Amp models feature dedicated feed to minimize
width and come with factory installed studs to which mechanical or compression lugs can be installed.
A wide variety of lug options for AL and CU wire are available to help minimize cost and customize the
module to your specifications. All modules in this family feature the four most basic QuickSystem features:
QuickConnect, QuickBolt, QuickRoll, and QuickTorque.

EUSERC-Compliant Breaker-Pullbox Combination Modules (type WEB)


These modules are designed for 240V AC Max line side, bottom feed applications, up to 1200 Amps, in
those areas that subscribe to the EUSERC standard, require compression lugs, or require separate
compartments for the breaker and line side terminals. NEMA II stud pattern bolts are standard on every
unit enabling compression or mechanical lug use. Each module features a removable ground trough to
facilitate pulling the grounding conductor through the pull section. Multiple ground lugs are included
with every device. All modules in this family feature the four most basic QuickSystem features:
QuickConnect, QuickBolt, QuickRoll, and QuickTorque.

Standard Switch Modules (type WS)


Switch modules are designed for line and load side applications ranging from 400 to 1200 Amps at 240V
AC Max. For modules at 800 Amps and below NEMA II stud pattern bolts are factory installed enabling
a wide variety of compression and mechanical lug options. 400-800 Amp modules feature the exclusive
invertibility feature - allowing the user to simply rotate the enclosure to accommodate top or bottom feed.
A wide variety of lug options for AL and CU wire are available to help minimize cost and customize the
module to your specifications. All modules in this family feature the four most basic QuickSystem features:
QuickConnect, QuickBolt, QuickRoll, and QuickTorque. Class T fuse provisions are standard.

EUSERC-Compliant Switch-Pullbox Combination Modules (type WES)


These modules are designed for 240V AC max line side, bottom feed applications, up to 1200 Amps, in
those areas that subscribe to the EUSERC standard or, require compression lugs. NEMA II stud pattern bolts
are standard on every unit enabling compression or mechanical lug use. Each module features a removable
ground trough to facilitate pulling the grounding conductor through the pull section. Multiple ground lugs
are included with every device. All modules in this family feature the four most basic QuickSystem features:
QuickConnect, QuickBolt, QuickRoll, and QuickTorque. Class T fuse provisions are standard.

Standard Tap Box Modules (type WTB)


Tap box modules are designed for line side main lug only or load side remote feed applications ranging
from 400-1600 Amps at 240V AC. NEMA II stud pattern bolts are factory installed enabling a wide variety
of compression and mechanical lug options. All modules in this family feature the exclusive invertibility
feature - allowing the user to simply rotate the enclosure to accommodate top or bottom feed. A wide
variety of lug options for AL and CU wire are available to help minimize cost and customize the module to
your specifications. All modules in this family feature the four most basic QuickSystem features:
QuickConnect, QuickBolt, QuickRoll, and QuickTorque.

s | Power Mod™ with QuickSystem™


1-4
1PXFS.PE
Features

&64&3$$PNQMJBOU5BQCPY1VMMCPY$PNCJOBUJPO.PEVMFT UZQF8&5

5IFTFNPEVMFTBSFEFTJHOFEGPSNBJOMVHPOMZ7"$.BYMJOFTJEF CPUUPNGFFEBQQMJDBUJPOT VQUP


"NQT JOUIPTFBSFBTUIBUTVCTDSJCFUPUIF&64&3$TUBOEBSE SFRVJSFDPNQSFTTJPOMVHT PSSFRVJSF
NPSFXJSFCFOETQBDFUIBOBTUBOEBSEUBQCPY/&."**TUVEQBUUFSOCPMUTBSFTUBOEBSEPOFWFSZVOJU
FOBCMJOHDPNQSFTTJPOPSNFDIBOJDBMMVHVTF"MMNPEVMFTJOUIJTGBNJMZGFBUVSFUIFGPVSNPTUCBTJD
2VJDL4ZTUFNGFBUVSFT2VJDL$POOFDU 2VJDL#PMU 2VJDL3PMM BOE2VJDL5PSRVF
3FTJEFOUJBM.FUFS4UBDLT UZQF8..

3FTJEFOUJBMTUBDLNPEVMFTBSFBWBJMBCMFJO"NQBOE"NQQFSQPTJUJPONPEVMFT5XPUISPVHITJY
QPTJUJPOEFWJDFTJOBOE"NQBSFBWBJMBCMFJOSJOH SJOHMFTTXJUIBOEXJUIPVUIPSOCZQBTT.PEVMFT
XJUIUISFFQIBTFUISPVHICVTIBWFUIF2VJDL1IBTFGFBUVSFXIJDIFOBCMFTÙFMEQIBTJOHQFSQPTJUJPO
BMMPXJOHUIFVTFSUPDVTUPNJ[FUIFTUBDLUPUIFJSTQFDJÙDOFFET"NQNPEVMFTVTFUIFOFX24UZQF
CSFBLFSXIJDIFMJNJOBUFTNVMUJQMFCFOETJOUFOBOUTFSWJDFDPOEVDUPSTBOEBMMPXTGPS"NQDPOWFSTJPO
XJUIPVUUIFOFFEGPSDPTUMZBOEMBCPSJOUFOTJWFDPOWFSTJPOLJUT"MMNPEVMFTJOUIJTGBNJMZGFBUVSFUIF
DPNQMFUF2VJDL4ZTUFNGFBUVSFTFU2VJDL$POOFDU 2VJDL#PMU 2VJDL3PMM 2VJDL1IBTFBOE2VJDL5PSRVF

$PNNFSDJBM.FUFS4UBDLTXJUI-FWFS#ZQBTT UZQF8.-

-FWFSCZQBTTDPNNFSDJBMNFUFSTUBDLTBSFBWBJMBCMFXJUI7"$NBYTJOHMFBOEUISFFQIBTFUFOBOUNBJO
QSPWJTJPOT5IJTGBNJMZPGGFST"NQXJUIUISFFQIBTFUFOBOUNBJOTXJUIVQUPGPVSQPTJUJPOT "NQ
XJUITJOHMFBOEUISFFQIBTFUFOBOUNBJOTXJUIVQUPGPVSQPTJUJPOT BOE"NQXJUITJOHMFBOEUISFF
QIBTFUFOBOUNBJOTVQUPUXPQPTJUJPOT$PNNFSDJBMUZQF8.-TUBDLTVTFUIF-BOEJT(ZSUZQF)2
MFWFSCZQBTTXIJDIIBTMFEUIFJOEVTUSZGPSGPSUZZFBSTJORVBMJUZBOEQFSGPSNBODF4UBDLTXJUITJOHMF
QIBTF"NQQSPWJTJPOTDBOCFDPOWFSUFEUP"NQXJUIPVUUIFOFFEGPSDPTUMZBOEMBCPSJOUFOTJWF
DPOWFSTJPOLJUT"MMNPEVMFTJOUIJTGBNJMZGFBUVSFUIFGPVSCBTJD2VJDL4ZTUFNGFBUVSFT2VJDL$POOFDU 
2VJDL#PMU 2VJDL3PMM BOE2VJDL5PSRVF
&64&3$$PNQMJBOU$PNNFSDJBM.FUFS4UBDLTXJUI5FTU#MPDL#ZQBTT UZQF8.5

5FTUCMPDLCZQBTTDPNNFSDJBMNFUFSTUBDLTBSF&64&3$DPNQMJBOUBOEBSFBWBJMBCMFXJUITJOHMFQIBTFBOE
UISFFQIBTFPVUQVUUFOBOUNBJOQSPWJTJPOT5IJTGBNJMZPGGFST"NQUFOBOUNBJOTXJUITJOHMFBOEUISFF
PVUQVUXJUIVQUPUISFFQPTJUJPOT4UBDLTXJUITJOHMFQIBTF"NQQSPWJTJPOTDBOCFDPOWFSUFEUP
"NQXJUIPVUUIFOFFEGPSDPTUMZBOEMBCPSJOUFOTJWFDPOWFSTJPOLJUT"MMNPEVMFTJOUIJTGBNJMZGFBUVSFUIF
GPVSCBTJD2VJDL4ZTUFNGFBUVSFT2VJDL$POOFDU 2VJDL#PMU 2VJDL3PMM BOE2VJDL5PSRVF

$PNNFSDJBM.FUFS4UBDLTXJUI,#BTF.FUFS4PDLFUT UZQF8.,

,#BTFJTBCPMUJONFUFSTPDLFUEFTJHOFEBOEQSPWJEFEFYDMVTJWFMZCZ-BOEJT(ZS6UJMJUZBDDFQUBODFWBSJFT
TPQMFBTFDIFDLGPSBQQSPWBMQSJPSUPVTJOHPOFPGUIFTFEFWJDFT,#BTFDPNNFSDJBMNFUFSTUBDLTBSF
BWBJMBCMFXJUI7"$NBYTJOHMFBOEUISFFQIBTFUFOBOUNBJOQSPWJTJPOT4JOHMFQIBTFJOBOEPVUEFWJDFT
VUJMJ[FUIF,NFUFSTPDLFU5ISFFQIBTFJOBOETJOHMFQIBTFPVUEFWJDFTVTFUIF,NFUFSTPDLFUBOEUISFF
QIBTFJOXJUIUISFFQIBTFPVUVUJMJ[FUIF,NFUFSTPDLFU"MMEFWJDFTBSFPGGFSFEJOPOFQPTJUJPOBOE
"NQDPOÙHVSBUJPOT5IF,NPEVMFTBSFPGGFSFEXJUIUXPQPTJUJPOTBU"NQTQFSQPTJUJPO"MM
NPEVMFTJOUIJTGBNJMZGFBUVSFUIFGPVSCBTJD2VJDL4ZTUFNGFBUVSFT2VJDL$POOFDU 2VJDL#PMU 2VJDL3PMM 
BOE2VJDL5PSRVF

"DDFTTPSJFT
5IF1PXFS.PEGBNJMZPGGFSTBXJEFWBSJFUZPGBDDFTTPSJFTUPDVTUPNJ[FUIFQSPEVDUTUPZPVSQBSUJDVMBS
BQQMJDBUJPO5IJTGBNJMZJODMVEFT
4QBDFSTVTFEUPQVUEJTUBODFCFUXFFOBNBJOBOETUBDLXIFSFSFRVJSFEPSKVTUUPFYUFOEUIFMFOHUI
PGUIFMJOFVQ
&MCPXT/&."SBUFEEFWJDFTEFTJHOFEUPUVSOBMJOFVQBSPVOEBOJOTJEFDPSOFS
1VMMCPYFT&64&3$DPNQMJBOUVOEFSHSPVOEQVMMTFDUJPOGPSVTFXJUITUBOEBSECSFBLFSBOETXJUDIVOJUT
-VHTUIFXJEFTUBSSBZPGMVHPQUJPOTJOUIFJOEVTUSZGPDVTJOHPOPGGFSJOHUIFNPTUFDPOPNJDBMTPMVUJPO
GPSZPVSBQQMJDBUJPO
.JTDÙFMEJOTUBMMBCMFUIKBXLJUT IVCT SFQMBDFNFOUQBSUT

s | Power Mod™ with QuickSystem™



Power Mod configuration
Configuration Tips

The service feed for a Modular Metering configuration can be on the end of the configuration or in the middle.

Here are a few configuration issues to keep in mind.

J Configurations are limited by the continuous current J All meter stack horizontal bussing must match the
ratings for the main device and the cross bus. All cross output (three phase or single phase) of the main
buses are aluminum with 1200 Amp continuous current disconnect module.
rating. For center fed applications, the total current in the
main device may exceed 1200 Amps if the main device is J Each meter stack comes with a QuickConnectTM and a
rated accordingly, but the cross bus current on either side mounting rail. A QuickConnect is needed for each cross
of the main device cannot exceed 1200 Amps. bus connection.

J Pullboxes have provisions for field installed lugs for J Utilities have varying requirements for equipment height,
incoming and outgoing conductors. These modules cover types, and bypass types. Therefore, utility acceptance
should be used for underground service feeds when should be obtained prior to installation of any modules.
inspecting authorities require the service to be split.
Pullboxes do not have horizontal cross bus. If a J Order a circuit breaker tenant main for each meter position.
connection to cross bus is needed a tap box (type WTB,
WET) should be used. J Circuit breakers must be single phase or three phase
to match the output of the meter stack. Refer to the
J 200 to1200 Amp standard breaker modules accept Siemens Speedfax catalog for circuit breaker series
combination feed allowing service conductors to enter rating information.
the top or bottom of the enclosure. 1600 to 2000 Amp
standard breaker modules have dedicated top or bottom J Standard tapboxes and circuit breakers (type WTB, WB)
feed. 400 to 800 Amp switch modules are invertible for may be used as a service entrance module or a load side
top or bottom feed. 1200 Amp switches are bottom feed feed for remote equipment. An additional QuickConnect
only. All standard tapboxes are invertible for top or must be ordered when using these devices on the load
bottom feed. Invertible units come with two sets of two side to feed remote equipment.
QuickBoltsTM on both sides of the unit. The QuickBolts on
the left side must be removed by taking off two mounting J Tapboxes provide a direct connection to the cross bus
screws on each QuickBolt assembly. and do not provide any overcurrent protection. Tapboxes
should neverbe used to feed other main devices (WS, WB,
J A spacer is commonly required between a meter stack and WES, WEB) as this would bypass the overcurrent protection.
the main disconnect module (or tapbox) for a EUSERC
installation. A spacer can also be used to extend the length
of the lineup when needed.

s | Power Mod™ with QuickSystem™


1-6
Power Mod configuration
Examples

Configuration Examples: The following illustration shows a few configuration examples. Other configurations are also possible.
For simplicity, only one or two meters stacks are shown for each configuration, but additional meter stacks can be added as long as
the cross bus and main device specifications are not exceeded.

Meter Stack Meter Stack Meter Stack

Incoming Incoming
Service Service Incoming
Service

Busway Spacer
Tap (when needed)
Stack

Main Breaker or Main Breaker or


Fusible Switch Fusible Switch Main Breaker or Fusible Switch
Requires an additional QuickConnect™ Requires an additional QuickConnect™

Modular metering example with service


entrance on the end in an area that
requires a spacer.

Meter Stack Meter Stack Meter Stack

Incoming Incoming
Service Service

Tapbox

Main Breaker
This configuration has no main disconnect 1600/2000
and can only be used when there are Modular metering example with service entrance
six or fewer disconnects in the center
(Center-fed configurations are used when the required
Modular metering example with service current exceeds 1200 Amps.)
entrance on the end.

s | Power Mod™ with QuickSystem™


1-7
Contents

Residential Meter Stacks 2-1

Standard Circuit Breaker Mains 3-1

Circuit Breaker - Pullbox-Combinations 4-1

Standard Switch Mains 5-1

Switch - Pullbox-Combinations 6-1

Standard Tapboxes 7-1

Tapbox - Pullbox-Combinations 8-1

Lever Bypass Meter Stacks 9-1

K-Base Meter Stacks 10-1

Test Block Bypass Meter Stacks 11-1

Accessories 12-1
Power Mod™

Power Mod’s core offering of Residential Meter Stacks,


type WMM, offers the widest product offering and
flexibility in the industry. Each meter stack houses the
QuickSystem™ features to maximize productivity and
minimize labor costs. To aid in productivity and labor
cost reductions our 225 Amp meter stacks feature a new
breaker - the “QS”. The QS breaker adds to the Siemens
exclusive feature set on our new 225 Amp Residential
Meter Stacks.

Benefits of the “QS” include:


J An exclusive 6 high 225 Amp meter stack at the
same height as our 125 Amp meter stack - 225 to
125 conversion: No conversion kit needed.
J Single right hand bend wiring - saves time and wire
J 100K AIC offered from 100 up to 225 Amps

Siemens Residential Meter Stacks are packed with features


inside and out: our exclusive knock out plate offers
flexibility when pulling wires to the stack, new breaker
supports keep breakers level and straight, moveable
neutrals and grounds to save wire, and all of the
QuickSystem features all designed with the contractor
in mind.

Residential Meter Stacks quick reference

J 2-6 gang
J 125/225 Amp per position
J 1200 Amp thru-bus rating
J UL standard 67
J UL file no. E27100
J AIC rating (65k & 100k)
J Voltage:
- Single phase 120/240V AC max.
- Three phase in single phase out
 120/208V AC max.
 240/120V AC max.
J All swing latches and rivets are stainless steel.
J NEMA 3R rated
J G90 galvanized steel
J ANSI 61 paint

Residential Meter Stacks


www.sea.siemens.com/powermod

1
Power Mod Residential Meter Stacks
QuickSystem Features

QuickRoll™

A Siemens exclusive feature, QuickRoll eliminates the typical metal brackets for
mounting modules to the wall. Instead of metal scraping metal, QuickRoll allows the
module to glide down the mounting rail via a durable nylon wheel inside a mounting
bracket.

QuickConnect™

A Siemens exclusive feature, QuickConnect reduces bussing connections from many to


one - ensuring a single reliable connection instead of multiple connections.

QuickTorque™

Eliminates the need for time consuming torque readings, this breakaway nut provides
the correct indication of torque of the QuickConnect. When tightened, the outer
head twists off at the proper torque for connection, leaving a single nut for future
maintenance.

QuickBolt™

A Siemens exclusive feature, QuickBolt eliminates the requirement to line up


mechanical connections - instead bolts remain retracted until the openings line
up- allowing the bolts to protrude through automatically. Springs push the bolts
through and provide positive pressure to keep bolts in place while wingnuts are
attached and tightened.

QuickPhase™

Each individual meter position can be phased independently according to the users
needs. QuickPhase allows the user the ultimate flexibility to adjust to each individual
application.

s | Power Mod™ with QuickSystem™


2-2
Power Mod Residential Meter Stacks
QuickSystem Features

Siemens
exclusive
feature

QuickRoll™

Siemens
exclusive
feature

QuickConnect™

QuickTorque™

Siemens
exclusive
feature

QuickBolt™

QuickPhase™

s | Power Mod™ with QuickSystem™


2-3
1PXFS.PE3FTJEFOUJBM.FUFS4UBDLT
Features

Sturdy steel base pan


Provides reinforcing durable support
for each tenant main breaker.

2 pole up to 225A @ 100kAIC


Fits in 2 inch – compact width reduces
enclosure size limiting total mounting
space required.

Rigid molded side wall


Provides reinforcing vertical support for
each tenant main breaker.

Main breaker retainer


Ensures secure connection for breaker
wiring.

Insert a 125A QP into a 225A


without conversion kits or filler plates.

Moveable neutral
Allows for top or bottom configuration
helping save length needed for wire.

Connecting cross bus rated at


1200amps

Barrel lock capable covers


Accepts common utility barrel locks to
protect against unauthorized usage.

Lockable breaker cover

s | Power Mod™ with QuickSystem™



1PXFS.PE3FTJEFOUJBM.FUFS4UBDLT
Features

Front accessible and Mounting ears


field installable 5th jaw Pivot factory installed
Located in 6 or 9 o’clock mounting ears to minimum
position. Factory installed in or maximum position to
9 o’clock position. All provide additional stability
connections are front when mounting equipment
onto wall.
accessible.

Field phase each meter


socket to balance the load Ring or ringless covers
between phases. More Ring to ringless kits available
flexible than phasing the to make last minute cover
entire stack. changes for specified utility
requirements.

Keeping the contractor in


mind, torque values are
molded on each meter
socket for quick reference.
Apartment no. emboss
Provides convenience and
Removable back end KO organization.
plate
Keeping the contractor in
mind, simplifies and speeds
up pulling wire. Entire
plate can be removed to
allow ample space for wire.
Knockouts in the plate can
be removed before or after
stack installation.

Rain channel
Moveable to simplify wiring.

Moveable ground
Allows for top or bottom
configuration helping save
on wire costs.

s | Power Mod™ with QuickSystem™



1PXFS.PE3FTJEFOUJBM.FUFS4UBDLT
Catalog numbers

Residential 4-jaw ring type meter stacks: 1-phase, 3-wire SN, incoming and outgoing1

Max. Field
Dimensions (inches) /
Meter tenant installed KO
Catalog positions breaker Breaker Maximum 5th jaw drawing Schematic
number per stack (Amps) provision AIC3 Height Width Depth assembly2 no. no.

WMM21125 2 Position 65,000 34.31 13.09 8.09 ECMF5 KA-12 SA-12


WMM31125 3 Position QP, QPH, 65,000 43.31 13.09 8.09 ECMF5 KA-13 SA-13
HQP, MP-T,
WMM41125 4 Position 125 65,000 52.31 13.09 8.09 ECMF5 KA-14 SA-14
MP-HT,
WMM51125 5 Position MP-MT 65,000 61.31 13.09 8.09 ECMF5 KA-15 SA-15
WMM61125 6 Position 65,000 70.31 13.09 8.09 ECMF5 KA-16 SA-16
WMM21225 2 Position QS, QSH, 100,000 34.31 16.22 8.09 ECMF5 KA-22 SA-12
WMM31225 3 Position QSHH, HQS, 100,000 43.31 16.22 8.09 ECMF5 KA-23 SA-13
HQSH, QP,
WMM41225 4 Position 225 0
100,000 52.31 16.22 8.09 ECMF5 KA-24 SA-14
QPH, HQP,
WMM51225 5 Position MP-T, MP-HT, 100,000 61.31 16.22 8.09 ECMF5 KA-25 SA-15
WMM61225 6 Position MP-MT 100,000 70.31 16.22 8.09 ECMF5 KA-26 SA-16

Residential 4-jaw ringless type meter stacks: 1-phase, 3-wire SN, incoming and outgoing1

Max. Dimensions (inches)/ Field


Catalog Catalog Meter tenant installed KO
number number positions breaker Breaker Maximum 5th jaw drawing Schematic
(No bypass) (Horn bypass) per ptack (Amps) provision AIC 3 Height Width Depth assembly2 no. no.

WMM21125R WMM21125RB 2 Position 65,000 34.31 13.09 8.09 ECMF5 KA-12 SA-12
WMM31125R WMM31125RB 3 Position QP, QPH, 65,000 43.31 13.09 8.09 ECMF5 KA-13 SA-13
HQP, MP-T,
WMM41125R WMM41125RB 4 Position 125 65,000 52.31 13.09 8.09 ECMF5 KA-14 SA-14
MP-HT,
WMM51125R WMM51125RB 5 Position MP-MT 65,000 61.31 13.09 8.09 ECMF5 KA-15 SA-15
WMM61125R WMM61125RB 6 Position 65,000 70.31 13.09 8.09 ECMF5 KA-16 SA-16
WMM21225R WMM21225RB 2 Position QS, QSH, 100,000 34.31 16.22 8.09 ECMF5 KA-22 SA-12
WMM31225R WMM31225RB 3 Position QSHH, HQS, 100,000 43.31 16.22 8.09 ECMF5 KA-23 SA-13
HQSH, QP,
WMM41225R WMM41225RB 4 Position 225 0
QPH, HQP, 100,000 52.31 16.22 8.09 ECMF5 KA-24 SA-14
MP-T,
WMM51225R WMM51225RB 5 Position MP-HT, 100,000 61.31 16.22 8.09 ECMF5 KA-25 SA-15
WMM61225R WMM61225RB 6 Position MP-MT 100,000 70.31 16.22 8.09 ECMF5 KA-26 SA-16

/ Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
0 225A available in lower three positions only.
1 NOT for use on 3-phase, 4-wire delta systems.
2 5th jaw can be isolated if needed.
3Max AIC determined by maximum AIC of tenant breakers. Higher ratings may be achieved through approved series rating combinations.

s | Power Mod™ with QuickSystem™



1PXFS.PE3FTJEFOUJBM.FUFS4UBDLT
Catalog numbers

Residential 5-jaw ring type meter stacks: 3-phase, 4-wire SN, incoming and 1-phase, 3 wire SN outgoing1
Max.
Dimensions (inches)/
Meter tenant Factory KO
Catalog positions breaker Breaker Maximum stack phasing drawing Schematic
number per stack (Amps) provision AIC3 Height Width Depth phases/sockets4 no. no.

WMM22125J 2 Position 65,000 34.31 13.09 8.09 AB, BC KA-12 SA-32


WMM32125J 3 Position QP, QPH, 65,000 43.31 13.09 8.09 AB, BC, CA KA-13 SA-33
HQP, MP-T,
WMM42125J 4 Position 125 65,000 52.31 13.09 8.09 AB, BC, CA, AB KA-14 SA-34
MP-HT,
WMM52125J 5 Position MP-MT 65,000 61.31 13.09 8.09 AB, BC, CA, AB, BC KA-15 SA-35
WMM62125J 6 Position 65,000 70.31 13.09 8.09 2-AB, 2-BC, 2-CA KA-16 SA-36
WMM22225J 2 Position QS, QSH, 100,000 34.31 16.22 8.09 AB, BC KA-22 SA-32
QSHH, HQS,
WMM32225J 3 Position 100,000 43.31 16.22 8.09 AB, BC, CA KA-23 SA-33
HQSH,
WMM42225J 4 Position 2250 QP,QPH, 100,000 52.31 16.22 8.09 AB, BC, CA, AB KA-24 SA-34
HQP, MP-T,
WMM52225J 5 Position 100,000 61.31 16.22 8.09 AB, BC, CA, AB, BC KA-25 SA-35
MP-HT,
WMM62225J 6 Position MP-MT 100,000 70.31 16.22 8.09 2-AB, 2-BC, 2-CA KA-26 SA-36

Residential 5-jaw ringless type meter stacks: 3-phase, 4-wire SN, incoming and 1-phase, 3 wire SN outgoing1

Max.
Catalog Catalog Meter tenant Dimensions (inches)/ Factory KO
number number positions breaker Breaker Maximum stack phasing dwg. Schematic
(no bypass) (Horn Bypass) per stack (Amps) provision AIC 3 Height Width Depth phases/socket4 no. no.

WMM22125RJ WMM22125RJB 2 Position 65,000 34.31 13.09 8.09 AB, BC KA-12 SA-32
WMM32125RJ WMM32125RJB 3 Position QP, QPH, 65,000 43.31 13.09 8.09 AB, BC, CA KA-13 SA-33
HQP, MP-T,
WMM42125RJ WMM42125RJB 4 Position 125 65,000 52.31 13.09 8.09 AB, BC, CA, AB KA-14 SA-34
MP-HT,
WMM52125RJ WMM52125RJB 5 Position MP-MT 65,000 61.31 13.09 8.09 AB, BC, CA, AB, BC KA-15 SA-35
WMM62125RJ WMM62125RJB 6 Position 65,000 70.31 13.09 8.09 2-AB, 2-BC, 2-CA KA-16 SA-36
WMM22225RJ WMM22225RJB 2 Position QS, QSH, 100,000 34.31 16.22 8.09 AB, BC KA-22 SA-32
WMM32225RJ WMM32225RJB 3 Position QSHH, HQS, 100,000 43.31 16.22 8.09 AB, BC, CA KA-23 SA-33
HQSH,
WMM42225RJ WMM42225RJB 4 Position 2250 QP, QPH, 100,000 52.31 16.22 8.09 AB, BC, CA, AB KA-24 SA-34
HQP, MP-T,
WMM52225RJ WMM52225RJB 5 Position MP-HT, 100,000 61.31 16.22 8.09 AB, BC, CA, AB, BC KA-25 SA-35
WMM62225RJ WMM62225RJB 6 Position MP-MT 100,000 70.31 16.22 8.09 2-AB, 2-BC, 2-CA KA-26 SA-36

/ Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
0 225A available in lower three positions only.
1 Approved for use on 3-phase, 4-wire delta systems.
2 5th jaw can be isolated if needed.
3Max AIC determined by maximum AIC of tenant breakers. Higher ratings may be achieved through approved series rating combinations.
4Residential Stacks are field phaseable

s | Power Mod™ with QuickSystem™



3-1/4

2-9/32

(6) KOs 1, 1-1/4, 1-1/2, 2"


13-3/32

Power Mod Residential Meter Stacks


8-3/32

125A knockout diagrams


O 36" TO
M OF BOTTOM OF
43-5/16 QUICK ROLL 52-5/16
ROLL
KET BRACKET
36" TO 36" TO 36" TO
BOTTOM OF BOTTOM OF BOTTOM OF
43-5/16 QUICK ROLL 52-5/16 QUICK ROLL
QUICK ROLL
BRACKET BRACKET BRACKET
34-5/16
9" 9"
TYP. TYP.
34-5/16
24-3/8 TO 27" TO 9" 24-3/8 TO 9" 9"
CROSS BUS BOTTOM OFTYP. CROSS BUS TYP. TYP.
36" TO
CENTER QUICK ROLL CENTER
BOTTOM OF
BRACKET 43-5/16
9"
24-3/8 TO QUICK ROLL 24-3/8 TO 24-3/8 TO
12-5/32 BRACKET 12-5/32
CROSSTYP.
BUS CROSS BUS CROSS BUS
2-13/16 CENTER 2-13/16 CENTER CENTER
36" TO
2-13/32 12-5/32
15-3/8 TO 2-13/32 12-5/32 BOTTOM OF 12-5/32
CROSS BUS 9" QUICK ROLL 52-5/16
/16 CENTER 2-13/16 2-13/16
BRACKET 2-13/16
TYP.
(6) KOs 1, 1-1/4, 1-1/2, 2" (6) KOs 1, 1-1/4, 1-1/2, 2"
2-13/32 2-7/16
12-5/32 2-13/32 2-7/16 2-13/32 2-13/32
REMOVABLE PLATE REMOVABLE PLATE
2-13/16 24-3/8 TO
1-5/8 TYP. 1-5/8 TYP.
CROSS BUS
(6) KOs 1, 1-1/4, 1-1/2, 2-13/32
2" CENTER(6) KOs 1, 1-1/4, 1-1/2, 2" (6) KOs 1, 1-1/4, 1-1/2, 2"
2-7/16 12-31/32
REMOVABLE PLATE 2-7/16 12-31/32
REMOVABLE PLATE 2-7/16 REMOVABLE PLATE 9" 2-7/16
TYP.
12-5/32
1-5/8 TYP. 1-5/8 TYP. 1-5/8 TYP. 1-5/8 TYP.
(6) KOs 1, 1-1/4, 1-1/2, 2"
2-13/16 24-3/8 TO 12-31/32
12-31/32 2-7/16 REMOVABLE PLATE 12-31/32
CROSS BUS
2-13/32 CENTER
1-5/8 TYP.
12-31/32 12-5/32
(6) KOs 1, 1-1/4, 1-1/2, 2"
2-7/16 REMOVABLE PLATE 2-13/16

1-5/8 TYP. 2-13/32


KA-12
12-31/32
1/4 WMM21125XX (6) KOs 1, 1-1/4, 1-1/2, 2"

WMM22125XXX KA-13 2-7/16 REMOVABLE PLATE


2-9/32
1-5/8 TYP.
(6) KOs 1, 1-1/4, 1-1/2, 2"
WMM31125XX
12-31/32
WMM32125XXX
KA-14
WMM41125XX
WMM42125XXX

13-3/32

13-3/32 8-3/32

8-3/32

61-5/16

125 Amp Typical Top View

36" TO
70-5/16
BOTTOM OF
QUICK ROLL
BRACKET

36" TO
BOTTOM OF
9"
QUICK ROLL
TYP.
BRACKET

3-1/4 24-3/8 TO
CROSS BUS
CENTER
2-9/32
9"
12-5/32 TYP.
(6) KOs 1, 1-1/4, 1-1/2, 2" 2-13/16
24-3/8 TO
2-13/32 CROSS BUS
125 Amp Typical Bottom View CENTER

(6) KOs 1, 1-1/4, 1-1/2, 2" 12-5/32


2-7/16 REMOVABLE PLATE
2-13/16
1-5/8 TYP.
2-13/32
12-31/32

KA-15 2-7/16
(6) KOs 1, 1-1/4, 1-1/2, 2"
REMOVABLE PLATE

WMM51125XX 1-5/8 TYP.

WMM52125XXX 12-31/32

KA-16
WMM61125XX
WMM62125XXX

s | Power Mod™ with QuickSystem™


2-8
16-3/32 16-3/32

Power Mod Residential Meter Stacks


225A knockout diagrams

36" TO 36" TO
BOTTOM OF BOTTOM OF 34-5/16
QUICK ROLL 43-5/16 QUICK ROLL 52-5/16
27" TO 36" TO 36" TO 36" TO 36" TO
BRACKET BRACKET
BOTTOM OF BOTTOM OF BOTTOM OF BOTTOM OF BOTTOM OF
QUICK ROLL QUICK ROLL QUICK ROLL 43-5/16 43-5/16
QUICK ROLL 52-5/16 QUICK ROLL
BRACKET BRACKET 9" BRACKET BRACKET BRACKET
34-5/16
TYP.
27" TO
TTOM OF 9" 9"
36" TO
CK ROLL TYP. TYP.
15-3/8 TO BOTTOM OF
RACKET QUICK ROLL 52-5/16
CROSS BUS 9" 9" 9" 9"
24-3/8 TO CENTER TYP. 24-3/8 TO TYP. TYP. BRACKET TYP.
CROSS BUS CROSS BUS
CENTER 12-5/32CENTER
24-3/8 TO 24-3/8 TO 24-3/8 TO 24-3/8 TO
15-3/8 TO 2-13/16 CROSS BUS CROSS BUS CROSS BUS CROSS BUS
CROSS BUS 12-5/32 CENTER CENTER 12-5/32 CENTER CENTER
CENTER 2-13/32
2-13/16 2-13/16 9"
12-5/32 12-5/32 12-5/32 12-5/32 TYP.
2-13/32 2-13/32
2-13/16 2-13/16
(6) KOs 1, 1-1/4, 1-1/2, 2" 2-13/16 2-13/16 2-13/16
2-7/16 24-3/8 TO
REMOVABLE PLATE
2-13/32 2-13/32 2-13/32 CROSS BUS
2-13/32 2-13/32
1-5/8(6)
TYP.
KOs 1, 1-1/4, 1-1/2, 2" (6) KOs 1, 1-1/4, 1-1/2, 2" CENTER
2-7/16 REMOVABLE PLATE 2-7/16 REMOVABLE PLATE
16-3/32
12-5/32
1-5/8 TYP. (6) KOs 1, 1-1/4, 1-1/2, 2" 1-5/8 TYP. (6) KOs 1, 1-1/4, 1-1/2, 2" (6) KOs 1, 1-1/4, 1-1/2, 2" (6) KOs 1, 1-1/4, 1-1/2, 2"
2-7/16 2-7/16 2-7/16 REMOVABLE PLATE REMOVABLE PLATE 2-7/16 2-7/16
16-7/32
REMOVABLE PLATE 2-13/16 REMOVABLE PLATE

1-5/8 TYP.
16-3/32 KA-22 1-5/8 TYP.
16-3/32
1-5/8 TYP. 1-5/8 TYP. 1-5/8 TYP.
2-13/32
16-3/32 16-3/32 16-3/32 16-3/32
WMM21225XX
WMM22225XXX 2-7/16
(6) KOs 1, 1-1/4, 1-1/2, 2"
8-3/32 KA-23 REMOVABLE PLATE

1-5/8 TYP.
WMM31225XX 16-3/32
WMM32225XXX
KA-24
WMM41225XX
WMM42225XXX

16-7/32

8-3/32

61-5/16

225 Amp Typical Top View

70-5/16
36" TO
BOTTOM OF
4" TYP. QUICK ROLL
BRACKET
2" TYP.
36" TO
2-3/16 BOTTOM OF
QUICK ROLL
9" BRACKET
TYP.

3-1/4 24-3/8 TO
CROSS BUS
CENTER 9"
2-9/32 TYP.
12-5/32
2-13/16 24-3/8 TO
(6) KOs 1-1/2, 2, 2-1/2" CROSS BUS
2-13/32 CENTER
225 Amp Typical Bottom View 12-5/32
(6) KOs 1, 1-1/4, 1-1/2, 2"
2-7/16 2-13/16
REMOVABLE PLATE

1-5/8 TYP. 2-13/32

16-3/32
(6) KOs 1, 1-1/4, 1-1/2, 2"
2-7/16
KA-25 REMOVABLE PLATE

1-5/8 TYP.
WMM51225XX 16-3/32

WMM52225XXX
KA-26
WMM61225XX
WMM62225XXX

s | Power Mod™ with QuickSystem™


2-9
Power Mod Residential Meter Stacks
Schematics

Equip.
Grd. Equip.
Grd.

Equip.
Grd.

SA-12
WMM21125XX
WMM21225XX Equip.
Grd.

SA-13
WMM31125XX Equip.
WMM31225XX Grd.

Equip.
Grd.

Equip.
Grd.

Equip.
Equip. Equip. Grd.
Grd. Grd.

SA-14 SA-15 SA-16


WMM41125XX WMM51125XX WMM61125XX
WMM41225XX WMM51225XX WMM61225XX

s | Power Mod™ with QuickSystem™


2-10
Power Mod Residential Meter Stacks
Schematics

Equip.
Grd. Equip.
Grd.

A B C
A B C

A A A A
N N N N
B B
B B
C C
C C

Equip.
Grd.

SA-32 Equip.
Grd.
WMM22125XXX
WMM22225XXX
SA-33
WMM32125XXX Equip.
WMM32225XXX Grd.

A B C
Equip.
Grd.

A B C
Equip.
Grd.

A B C

A A
A A A A N N
N N N N B B
B B B B C C
C C C C

Equip. Equip. Equip.


Grd. Grd. Grd.

SA-34 SA-35 SA-36


WMM42125XXX WMM52125XXX WMM62125XXX
WMM42225XXX WMM52225XXX WMM62225XXX

s | Power Mod™ with QuickSystem™


2-11
Catalog Number Logic Example

W M M 2 1 125 R J B

Horn Bypass
Amperage
Enclosure B = Horn Bypass
Position 125 Installed
WMM = Residential
Meter Stack 2 = 2 Position 225 Blank = No Horn Bypass
Installed
3 = 3 Position

4 = 4 Position Jaws

5 = 5 Position J = 5th Jaw Installed

6 = 6 Position Blank = No 5th Jaw


Cover

Phase R = Ringless

1 = Single Phase Blank = Ring Type

2 = Three Phase In/


Single Phase Out
Power Mod™

Standard breaker modules (type WB) offer a balance


between functionality, feature, and size constraints.

Features include:
J QuickSystem™ features
J Compression lug landing pads (field install up to
1200 Amps, standard feature up to 2000 Amps)
J Combination overhead and underground feed up to
1200 Amps, dedicated overhead or underground feed
up to 2000 Amps
J 750kcmil AL wire options
J 65K AIC standard, 100K AIC available for all models
J Removable blank bottom endwall
J Externally accessible breaker handle with padlock
capability
J Broad ampacity ratings up to 2000 Amps with
non-standard amperages available (such as 700,
900, etc.)
J Field installable shunt trips

Standard Circuit Breaker Mains quick reference

J 200-2000A
J 1200A thru-bus rating
J UL Standard # UL67
J UL file # E27100
J AIC rating (65k & 100k)
J Voltage:
- Single phase 120/240V AC max
- Three phase 240V AC max
J All swing latches and rivets are stainless steel.
J NEMA 3R rated
J G90 galvanized steel
J ANSI 61 paint

Standard Circuit Breaker Mains


www.sea.siemens.com/powermod
Power Mod Standard Circuit Breaker Mains
Features

4” hub opening
Siemens/Landis & Gyr HD type hubs

External main
service disconnect
Provides safety with quick
convenient access to disconnect
made externally. Eliminates taking
time to remove cover to disconnect.

Connecting cross bus rated


1200 Amps

Siemens
exclusive
feature

QuickConnect™
QuickConnect reduces bussing
connections from many to
one - ensuring a single reliable
connection instead of multiple
connections.

QuickTorque™
Eliminates the need for time
consuming torque readings, this
breakaway nut provides the correct
indication of torque of the Quick-
Connect. When tightened, the
outer head twists off at the proper
torque for connection, leaving a
single nut for future maintenance.

Isolated and insulated neutral


Grounds and neutrals can be
separated for load-side
applications for 400-1200 Amp
devices.

Combination overhead and underground feed up


to 1200 Amps, dedicated overhead or underground
feed up to 2000 Amps

s | Power Mod with QuickSystem


3-2
1PXFS.PE4UBOEBSE$JSDVJU#SFBLFS.BJOT
Features

Back View:
Mounting ears
Pullbox opening
Pivot factory installed mounting
6” knockout for aligning a separate ears to minimum or maximum
pullbox if required. position to provide additional
stability when mounting

Siemens
exclusive
feature

QuickRoll™
QuickRoll eliminates the typical metal
brackets for mounting modules to the
wall. Instead of metal scraping metal
QuickRoll allows the module to glide
down the mounting rail via a durable
nylon wheel inside mounting bracket.

Compression lug landing pad


Factory installed lugs are standard on
200-1200 Amp devices. A field
installable compression lug landing pad
is also available.
NEMA II studs for use with compression
and mechanical lugs are standard on
1400-2000 Amp devices.

Field installable shunt trips


Shunt trips are offered as a field
installed option for applications that
require tripping the main remotely.

Siemens
exclusive
feature
QuickBolt™
QuickBolt eliminates the requirement
to line up mechanical connections -
instead bolts remain retracted until the
openings lineup - allowing the bolts to
protrude through automatically.
Springs push the bolts through and
provide positive pressure to keep bolts
in place while wingnuts are attached
and tightened.

Removable bottom endwall


The bottom of every enclosure is blank
and removable which allows the user
to cut knockouts after conduits and the
device are installed.

s | Power Mod™ with QuickSystem™



Power Mod Standard Circuit Breaker Mains
Catalog numbers

Circuit breaker service entrance modules: 1-phase, 3-wire SN, 120/240V AC


Dimensions (inches)a
Catalog Catalog Factory installed KO
number number Ampere Service Breaker line side drawing
(65k AIC) (100k AIC)b rating feed typee Height Width Depth connections no.

(2) 3/0-500 kcmil CU


WB1250Cb WB1250CU 250 OH/UG JXD6 39.19 15.20 11.03 KB-1
(2 )4/0-500 kcmil AL
(2) 3/0-500 kcmil CU
WB1300Cb WB1300CU 300 OH/UG JXD6 39.19 15.20 11.03 KB-1
(2 )4/0-500 kcmil AL
(2) 3/0-500 kcmil CU
WB1350Cb WB1350CU 350 OH/UG JXD6 39.19 15.20 11.03 KB-1
(2 )4/0-500 kcmil AL
(2) 3/0-500 kcmil CU
WB1400C WB1400CU 400 OH/UG JXD6 39.19 15.20 11.03 KB-1
(2 )4/0-500 kcmil AL
(2) 3/0-500 kcmil CU
WB1600C WB1600CU 600 OH/UG LXD6 39.19 15.20 11.03 KB-1
(2 )4/0-500 kcmil AL
WB1700Cb WB1700CU 700 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil KB-2

WB1800C WB1800CU 800 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil KB-2

WB1900Cb WB1900CU 900 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3

WB11000C WB11000CU 1000 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3

WB11200C WB11200CU 1200 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3

WB11400Tbcd WB11400TUcd OH PXD6 72.06 31.34 14.66 KB-4


1400
WB11400Bbcd WB11400BUcd UG PXD6 72.06 31.34 14.66 KB-5
3 Sets of 2 Studs
WB11600Tcd WB11600TUcd OH PXD6 72.06 31.34 14.66 KB-4
1600
WB11600Bcd WB11600BUcd UG PXD6 72.06 31.34 14.66 KB-5
(lugs not included)
WB12000Tcd WB12000TUcd OH RXD6 72.06 31.34 14.66 KB-4
2000
WB12000Bcd WB12000BUcd UG RXD6 72.06 31.34 14.66 KB-5

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
b 100K and non-standard amperage devices require additional lead time. Please contact sales office for details on lead time.
c 1200 amp maximum feed per side - must be used as a center fed main.
d Lugs not included. Refer to page 3-6 for lug size options. Lug kits available for 750 conductor size.
e All breakers have a non-interchangeable trip unit.

s | Power Mod™ with QuickSystem™


3-4
1PXFS.PE4UBOEBSE$JSDVJU#SFBLFS.BJOT
Catalog numbers

Circuit breaker service entrance modules: 3-phase, 4-wire SN, 240V AC max

Catalog Catalog Dimensions (inches)/ Factory installed KO


number number Ampere Service Breaker line side drawing
(65k AIC) (100k AIC)0 rating feed type3 Height Width Depth connections no.

(2) 3/0-500 kcmil CU


WB3250C 0 WB3250CU 250 OH/UG JXD6 39.19 15.20 11.03 KB-1
(2 )4/0-500 kcmil AL
(2) 3/0-500 kcmil CU
WB3300C 0 WB3300CU 300 OH/UG JXD6 39.19 15.20 11.03 KB-1
(2 )4/0-500 kcmil AL
(2) 3/0-500 kcmil CU
WB3350C 0 WB3350CU 350 OH/UG JXD6 39.19 15.20 11.03 KB-1
(2 )4/0-500 kcmil AL
(2) 3/0-500 kcmil CU
WB3400C WB3400CU 400 OH/UG JXD6 39.19 15.20 11.03 KB-1
(2 )4/0-500 kcmil AL
(2) 3/0-500 kcmil CU
WB3600C WB3600CU 600 OH/UG LXD6 39.19 15.20 11.03 KB-1
(2 )4/0-500 kcmil AL
WB3700C 0 WB3700CU 700 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil KB-2

WB3800C WB3800CU 800 OH/UG MXD6 61.19 24.19 11.03 (3) 1/0-500 kcmil KB-2

WB3900C 0 WB3900CU 900 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3

WB31000C WB31000CU 1000 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3

WB31200C WB31200CU 1200 OH/UG NXD6 61.19 24.19 11.03 (4) 1/0-500 kcmil KB-3

WB31400T012 WB31400TU12 OH PXD6 72.06 31.34 14.66 KB-4


1400
WB31400B012 WB31400BU12 UG PXD6 72.06 31.34 14.66 KB-5
3 Sets of 2 Studs
WB31600T12 WB31600TU12 OH PXD6 72.06 31.34 14.66 KB-4
1600
WB31600B12 WB31600BU12 UG PXD6 72.06 31.34 14.66 KB-5
(lugs not included)
WB32000T12 WB32000TU12 OH RXD6 72.06 31.34 14.66 KB-4
2000
WB32000B12 WB32000BU12 UG RXD6 72.06 31.34 14.66 KB-5

/ Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
0 100K and non-standard amperage devices require additional lead time. Please contact sales office for details on lead time.
1 1200 amp maximum feed per side - must be used as a center fed main.
2 Lugs not included. Refer to page 3-6 for lug size options. Lug kits available for 750 conductor size.
3 All breakers have a non-interchangeable trip unit.

s | Power Mod™ with QuickSystem™



Power Mod Standard Circuit Breaker Mains
Lug selector catalog numbers

Standard breaker Breaker lug landing pad


lug kits lug kits

Wire size  500 kcmil 600 kcmil 750 kcmil 350 kcmil 500 kcmil 600 kcmil 750 kcmil

Amperage # Conductors

400 1 n/a n/a LK11750 * n/a n/a LK11600N2 n/a

2 LK12500*^ n/a n/a LK12350N2 n/a n/a n/a

600 2 LK12500*^ n/a n/a LK12350N2 n/a n/a n/a

800 2 n/a n/a n/a n/a n/a LK12600N2 LK12750N2


1 Phase
3 LK13500*^ n/a LK13750* n/a LK13500N2 n/a n/a

1200 3 n/a n/a LK13750* n/a n/a n/a LK13750N2

4 LK14500*^ n/a n/a n/a LK14500N2 n/a n/a

1600 5 n/a LK15600N2 LK15750N2 n/a n/a n/a n/a

2000 6 n/a n/a LK16750N2 n/a n/a n/a n/a

400 1 n/a n/a LK31750* n/a n/a LK31600N2 n/a

2 LK32500*^ n/a n/a LK32350N2 n/a n/a n/a

600 2 LK32500*^ n/a n/a LK32350N2 n/a n/a n/a

800 2 n/a n/a n/a n/a n/a LK32600N2 LK32750N2

3 Phase 3 LK33500*^ n/a LK33750* n/a LK33500N2 n/a n/a

1200 3 n/a n/a LK33750* n/a n/a n/a LK33750N2

4 LK34500*^ n/a n/a n/a LK34500N2 n/a n/a

1600 5 n/a LK35600N2 LK35750N2 n/a n/a n/a n/a

2000 6 n/a n/a LK36750N2 n/a n/a n/a n/a

* Lug kits - Sentron breaker lugs

s | Power Mod™ with QuickSystem™


3-6
Power Mod Standard Circuit Breaker Mains
Knockout diagrams

15-7/32 15-7/32
7" 4-3/32 7" 4-3/32

3-3/4 3-3/4

11-1/32 11-1/32
2 TYPE "HD" HUB 2 TYPE "HD" HUB
OPENINGS - 4" MAX OPENINGS - 4" MAX
FACTORY INSTALLED FACTORY INSTALLED
COVER PLATES COVER PLATES

8-15/16 8-15/16

39-3/16 39-3/16

27-15/32 TO
BOTTOM OF 27-15/32 TO
QUICK ROLL 19-1/4 BOTTOM OF
BRACKET QUICK ROLL
BRACKET 19-1/4
15-25/32 TO 17-1/4 15-25/32 TO
CROSS BUS CROSS BUS
CENTER CENTER

12-19/32 12-19/32

REMOVABLE WB1600CU REMOVABLE


BOTTOM BOTTOM
ENDWALL 8-17/32 ENDWALL 8-17/32
OPENING OPENING

KB-1 KB-2 KB-3


WB3250XX WB1250XX WB3700XX WB1700XX WB3900XX WB1900XX
WB3300XX WB1300XX WB3800XX WB1800XX WB31000XX WB11000XX
WB3350XX WB1350XX WB31200XX WB11200XX
WB3400XX WB1400XX
WB3600XX WB1600XX

31-11/32

31-11/32 14-21/32
6
3

6 TYPE "HD" 4" MAX 14-21/32


HUB OPENINGS
FACTORY INSTALLED
COVER PLATES

18-5/32

27-3/8 TO 29-3/8 TO
PHASE NEUTRAL
STUDS STUDS
72-1/16
72-1/16
1-3/4 NEMA
} STUD SPACING
1-3/4 NEMA
STUD SPACING }
48-21/32 TO 37-1/32 TO
46-21/32 TO BOTTOM OF CROSS BUS
BOTTOM OF QUICK ROLL CENTER
QUICK ROLL BRACKET
BRACKET 29-3/8 TO 27-3/8 TO
NEUTRAL PHASE
35-1/32 TO STUDS STUDS
CROSS BUS
CENTER

28-5/8
WB31400T
WB31400TU
WB31600T
WB31600TU
WB32000T
WB32000TU WB31400B REMOVABLE
WB31400BU
WB31600B BOTTOM 11-29/32
WB31600BU ENDWALL
WB32000B
WB32000BU OPENING

KB-4 KB-5
WB31400TX WB11400TX WB31400BX WB11400BX
WB31600TX WB11600TX WB31600BX WB11600BX
WB32000TX WB12000TX WB32000BX WB12000BX

s | Power Mod™ with QuickSystem™


3-7
Catalog Number Logic Example

W B 3 4 0 0 C B D

Amperage
Enclosure Incoming Feed
250
W = Outdoor U = 100K AIC rated unit
300
Blank = 65k AIC rated unit
Device 350

BD = Bus Duct
B = Breaker Phase 400

1 = Single Phase 500


Incoming Feed
3 = Three Phase 600
C = Top and bottom feed construction
700
B = Bottom feed construction
800
T = Top feed construction
900

1000

1200

1400

1600

1800

2000
Power Mod™

EUSERC - compliant breaker - pullbox combination


modules (type WEB) offer EUSERC compatibility, a wider
range of lug options, and extra space for pulling in
conductors.

Features include:
J QuickSystem™ features
J Factory installed NEMA II studs
J 750 kcmil AL wire options
J 65K AIC standard, 100K AIC available for all models
J Removable blank bottom endwall
J Externally accessible breaker handle with padlock
capability
J Field installable shunt trips
J Large removable ground wire trough with generous
space for grounding conductors

Circuit Breaker-Pullbox Combinations quick reference

J 400-1200A
J 1200A thru-bus
J UL standard # UL67
J UL file # E27100
J AIC rating (65k & 100k)
J Voltage
- Single phase 120/240V AC Max
- Three phase 240V AC Max
J All swing latches and rivets are stainless steel
J NEMA 3R rated
J G90 galvanized steel
J ANSI 61 paint
J EUSERC drawing numbers 315, 343, and 347

Circuit Breaker - Pullbox Combinations


www.sea.siemens.com/powermod
Circuit Breaker - Pullbox Combinations
Features

Ground lugs
3 ground lugs included for
bonding additional systems.

Connecting cross bus rated


1200 Amps

Siemens
exclusive
feature

QuickConnect™
QuickConnect reduces bussing
connections from many to
one - ensuring a single reliable
connection instead of multiple
connections.

QuickTorque™
Eliminates the need for time
consuming torque readings, this
breakaway nut provides the correct
indication of torque of the Quick-
Connect. When tightened, the
outer head twists off at the proper
torque for connection, leaving a
single nut for future maintenance.

Removable wire trough


Provides extra wire bending room
and eliminate tangles in wire feeds.
Pull on ring to remove trough.

s | Power Mod™ with QuickSystem™


4-2
$JSDVJU#SFBLFS1VMMCPY$PNCJOBUJPOT
Features

Back View:
Mounting ears
External main service disconnect
Pivot factory installed mounting
Provides safety with quick convenient ears to minimum or maximum
access to disconnect made externally. position to provide additional
Eliminates taking time to remove cover stability when mounting.
to disconnect.

Siemens
exclusive
feature
QuickRoll™
QuickRoll eliminates the typical metal
brackets for mounting modules to the
wall. Instead of metal scraping metal
QuickRoll allows the module to glide
down the mounting rail via a durable
nylon wheel inside mounting bracket.

Field installable shunt trips


Shunt trips are offered as a field
installed option for applications that
require tripping the main remotely.

Insulated barrier between breaker


and lugs
Insulated barrier provides protection
from live cross bus parts to meet
specific utility requirements.

Siemens
exclusive
feature
QuickBolt™
QuickBolt eliminates the requirement
to line up mechanical connections -
instead bolts remain retracted until the
openings lineup - allowing the bolts to
protrude through automatically.
Springs push the bolts through and
provide positive pressure to keep bolts
in place while wingnuts are attached
and tightened.

Incoming service terminating lugs


Factory installed NEMA II studs. For
mechanical compression lugs.

Removable bottom endwall


The bottom of every enclosure is blank
and removable which allows the user
to cut knockouts after the device and
conduit is installed.

s | Power Mod™ with QuickSystem™



$JSDVJU#SFBLFS1VMMCPY$PNCJOBUJPOT
Catalog numbers

Combination circuit breaker and pullbox modules: 1-phase, 3-wire SN, 120/240V AC max
Meets EUSERC requirements
Dimensions (inches)/ Line side1
Catalog Catalog connections KO
number number Ampere Service Breaker (lugs not drawing
(65k AIC) (100k AIC)0 rating feed type2 Height Width Depth included) no.

1 set of
WEB1400B WEB1400BU 400 UG JXD6 54.88 28.28 13.06 2 studs EB-1

WEB1600B WEB1600BU 600 UG LXD6 54.88 28.28 13.06 2 sets of EB-2


2 studs

WEB1800B WEB1800BU 800 UG MXD6 59.34 34.22 12.47 EB-3

WEB11000B WEB11000BU 1000 UG NXD6 59.34 34.22 12.47 3 sets of EB-4


2 studs

WEB11200B WEB11200BU 1200 UG NXD6 59.34 34.22 12.47 EB-4

/ Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
0 Non standard module. Has longer ordering lead times, contact sales office for additional ordering information.
1 Lugs not included. Refer to page 4-6 for lug size options. Lug kits available for 750 conductor size
2 All breakers have a non-interchangeable trip unit.

s | Power Mod™ with QuickSystem™



$JSDVJU#SFBLFS1VMMCPY$PNCJOBUJPOT
Catalog numbers

Combination circuit breaker and pullbox modules: 3-phase, 4-wire SN, 240V AC max
Meets EUSERC requirements
Dimensions (inches)/ Line side1
Catalog Catalog connections KO
number number Ampere Service Breaker (lugs not drawing
(65k AIC) (100k AIC)0 rating feed type2 Height Width Depth included) no.

1 set of
WEB3400B WEB3400BU 400 UG JXD6 54.88 28.28 13.06 2 studs EB-1

WEB3600B WEB3600BU 600 UG LXD6 54.88 28.28 13.06 2 sets of EB-2


2 studs

WEB3800B WEB3800BU 800 UG MXD6 59.34 34.22 12.47 EB-3

WEB31000B WEB31000BU 1000 UG NXD6 59.34 34.22 12.47 3 sets of EB-4


2 studs
WEB31200B WEB31200BU 1200 UG NXD6 59.34 34.22 12.47 EB-4

/ Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
0 Non standard module. Has longer ordering lead times, contact sales office for additional ordering information.
1 Lugs not included. Refer to page 4-6 for lug size options. Lug kits available for 750 conductor size
2 All breakers have a non-interchangeable trip unit.

s | Power Mod™ with QuickSystem™



Circuit Breaker - Pullbox Combinations
Lug selector catalog numbers

Circuit breaker-pullbox combination lug kits

Wire Size  500 kcmil 600 kcmil 750 kcmil

Amperage # Conductors
400 1 n/a n/a LK11750N2
2 LK12500N2 n/a n/a
600 2 LK12500N2E n/a LK12750N2
1 Phase
800 2 n/a LK12600N2 LK12750N2
3 LK13500N2 n/a n/a
1200 3 n/a n/a LK13750N2E
4 LK14500N2E n/a n/a

400 1 n/a n/a LK31750N2


2 LK32500N2 n/a n/a
600 2 LK32500N2E n/a LK32750N2
3 Phase 800 2 n/a LK32600N2 LK32750N2
3 LK33500N2 n/a n/a
1200 3 n/a n/a LK33750N2E
4 LK34500N2E n/a n/a

s | Power Mod™ with QuickSystem™


4-6
Circuit Breaker - Pullbox Combination
Knockout diagrams

EB-1 EB-2
WEB1400B WEB1400BU WEB1600B WEB1600BU
WEB3400B WEB3400BU WEB3600B WEB3600BU

34-7/32 34-7/32

12-15/32 12-15/32

32 32

1-3/4" NEMA 1-3/4" NEMA


STUD SPACING STUD SPACING

} } 59-11/32
59-11/32

44-7/8 TO 44-7/8 TO
BOTTOM OF BOTTOM OF
QUICK ROLL QUICK ROLL
BRACKET BRACKET
33-1/4 TO 33-1/4 TO
CROSS BUS CROSS BUS
CENTER 26-25/32 TO CENTER 26-25/32 TO
PHASE AND PHASE AND
NEUTRAL NEUTRAL
STUDS STUDS

29-1/8
29-1/8
REMOVABLE REMOVABLE
BOTTOM BOTTOM
ENDWALL ENDWALL
OPENING OPENING

3/4 KO 3/4 KO
8-5/8 8-5/8

EB-3 EB-4
WEB1800B WEB1800BU WEB11000B WEB11000BU
WEB3800B WEB3800BU WEB11200B WEB11200BU
WEB31000B WEB31000BU
WEB31200B WEB31200BU

s | Power Mod™ with QuickSystem™


4-7
Catalog Number Logic Example

W EB 3 4 0 0 B U

Amperage
Enclosure Incoming Feed

W = Outdoor 400
U = 100K AIC rated unit

Device 600
Blank = 65k AIC rated unit
EB = EUSERC Breaker Phase
800
1 = Single phase Incoming Feed

1000 B = Bottom feed construction


3 = Three phase

1200
Power Mod™

Standard switch modules (type WS) are designed for


flexibility, space savings, & durability.

Features include:
J QuickSystem™ features
J Standard compression lug capability
J Invertibility: 400-800 Amp devices can be rotated to
accommodate the desired incoming feed direction
J 750 kcmil AL wire options for most models
J 100K AIC standard for all models
J Class T fuse provisions
J Front mounted handle - removes the need for spacers
on the side
J Broad ampacity ratings up to 1200 Amps

Standard Switch Mains quick reference

J 400-1200A
J 1200A thru-bus
J UL Standard # UL98
J UL file #E25506
J AIC rating (100k AIC)
J Voltage:
- Single phase 120/240V AC max
- Three phase 240V AC max
J All swing latches and rivets are stainless steel
J NEMA 3R rated
J G90 galvanized steel
J ANSI 61 paint

Standard Switch Mains


www.sea.siemens.com/powermod
Power Mod Standard Switch Mains
Features

Vacubreak switch up to 800A


Molded case switch for 1200A.
Order class T fuse types separately.

Standard compression lug


capability. 750kcmil AL wire
options.

400-800A standard switch


modules are invertible to
change line side feed
connections.

Removable bonding strap


For use in non service entrance
applications.

Pullbox Opening
6” knockout for aligning a separate
pullbox if required.

4” hub openings
Siemens/Landis & Gyr HD type hubs

s | Power Mod™ with QuickSystem™


5-2
Power Mod Standard Switch Mains
Features

Front mounted handle


Saves space by eliminating handles
mounted on the side.

Connecting cross bus rated 1200


Amps

Siemens
exclusive
feature

QuickConnect™ Mounting ear


QuickConnect reduces bussing Pivot factory installed mounting ears
connections from many to to minimum or maximum position
one - ensuring a single reliable to provide additional stability when
connection instead of multiple mounting equipment onto wall.
connections.

QuickTorque™
Eliminates the need for time
consuming torque readings, this
breakaway nut provides the correct in-
dication of torque of the QuickConnect.
When tightened, the outer head twists
off at the proper torque for connection,
leaving a single nut for future
maintenance.

Siemens
exclusive
Siemens
feature
exclusive
QuickBolt™ feature
QuickBolt eliminates the requirement
to line up mechanical connections - QuickRoll™
instead bolts remain retracted until the QuickRoll eliminates the typical metal
openings lineup - allowing the bolts to brackets for mounting modules to the
protrude through automatically. wall. Instead of metal scraping metal
Springs push the bolts through and QuickRoll allows the module to glide
provide positive pressure to keep bolts down the mounting rail via a durable
in place while wingnuts are attached nylon wheel inside mounting bracket.
and tightened.

s | Power Mod™ with QuickSystem™


5-3
Power Mod Standard Switch Mains
Catalog numbers

Fusible switch service entrance modules: 1-phase, 3-wire SN, 120/240V AC, 100k AICd
Dimensions (inches)a
Line KO
Catalog Rating Service Fuse side drawing
number amps feed typed Height Width Depth connections no.

WS1400CUe 400 OH/UGb T 50.13 15.19 16.31 1 set of 2 studs S-1

(lugs not included)


WS1600CUe 600 OH/UGb T 50.13 15.19 16.31 S-1

2 sets of 2 studs
WS1800CUe 800 OH/UGb T 50.13 15.19 16.31
(lugs not included)
S-2
WS11200BUcf 1200 UG T 50.06 20.22 16.06 (4) 250- 500 kcmil S-3

Fusible switch service entrance modules: 3-phase, 4-wire WN, 240V AC Max., 100k AICd
Dimensions (inches)a
Line KO
Catalog Rating Service Fuse side drawing
number amps feed typed Height Width Depth connections no.

WS3400CUe 400 OH/UGb T 50.13 15.19 16.31 1 set of 2 studs S-1

(lugs not included)


WS3600CUe 600 OH/UGb T 50.13 15.19 16.31 S-1

2 sets of 2 studs
WS3800CUe 800 OH/UGb T 50.13 15.19 16.31 S-2
(lugs not included)

WS31200BUcf 1200 UG T 50.06 20.22 16.06 (4) 250-500 kcmil S-3

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusion.
b Module is invertible - rotate device to point hub openings to appropriate feed direction.
c 500 kcmil max wire range size.
d Fuses not included.
e Lugs not included. NEMA II stud pattern lugs must be installed by user or utility. Refer to page 5-5 for lug size options.
f Device uses a molded case switch (looks like a breaker). Class T fuses must be installed in conjunction with the molded case switch for proper operation.

s | Power Mod™ with QuickSystem™


5-4
Power Mod Standard Switch Mains
Lug selector catalog numbers

Fusible switch
lug kits

Wire size  500 kcmil 600 kcmil 750 kcmil

Amperage # Conductors
400 1 n/a LK11600N2 LK11750N2
2 LK12500N2 n/a n/a
600 2 LK12500N2 n/a n/a
1 Phase
800 2 n/a LK12600N2 LK12750N2
3 LK13500N2 n/a n/a
1200 3 n/a n/a n/a
4 LK14500*^ n/a n/a

400 1 n/a LK31600N2 LK31750N2


2 LK32500N2 n/a n/a
600 2 LK32500N2 n/a n/a
3 Phase 800 2 n/a LK32600N2 LK32750N2
3 LK33500N2 n/a n/a
1200 3 n/a n/a n/a
4 LK34500*^ n/a n/a
* Lug kits - Sentron breaker lugs

s | Power Mod™ with QuickSystem™


5-5
Power Mod Standard Switch Mains
Knockout diagrams

S-1
WS1400CU WS3400CU
WS1600CU WS3600CU

S-2
WS1800CU WS3800CU

s | Power Mod™ with QuickSystem™


5-6
Power Mod Standard Switch Mains
Knockout diagrams
20-7/32

16-1/16

18-5/16

50-1/16

35-1/8 TO
BOTTOM OF
23-1/2 TO QUICK ROLL
CROSS BUS BRACKET
CENTER 16-15/16
TO PHASE
15-3/4 TO LUGS
NEUTRAL 15-7/32 TO
LUGS GROUND
LUG

17-23/32 REMOVABLE
BOTTOM ENDWALL

12-23/32

S-3
WS11200BU WS31200BU

s | Power Mod™ with QuickSystem™


5-7
Catalog number logic example

W S 3 4 0 0 C B D

Enclosure
Incoming feed
W = Outdoor
Amperage
U = 100K AIC rated unit
Device 400

S = Switch Phase 600 BD = Bus Duct

1 = Single phase 800

3 = Three phase 1200

Incoming feed

C = Top and bottom feed construction

B = Bottom feed construction


Power Mod™

EUSERC - compliant switch-pullbox combination modules


(type WEB) offer EUSERC compatibility, a wider range of
lug options, and extra space for pulling in conductors.

Features include:
J QuickSystem™ features
J Factory installed NEMA II studs
J Broad ampacity ratings up to 1200 Amps
J 750kcmil AL wire options
J 100K AIC standard for all models
J Removable blank bottom endwall
J Front mounted handle - removes the need for spacers
on the side
J Class T fuse provisions
J Large removable ground wire trough with generous
space for grounding conductors
J Extra ground lugs in each device

Switch-Pullbox Combinations quick reference

J 400-1200A
J 1200A thru-bus
J UL standard # UL98
J UL file # E25506
J AIC Rating (100k AIC)
J Voltage:
- Single phase 120/240V AC max
- Three phase 240V AC max
J All swing latches and rivets are stainless steel.
J NEMA 3R rated
J G90 galvanized steel
J ANSI 61 paint
J EUSERC drawing numbers 315, 343, and 347

Switch-Pullbox Combinations
www.sea.siemens.com/powermod
Power Mod Switch-Pullbox Combinations
Features

Molded case switch, for 1200A


Order Class T fuse types separately.

Removable neutral lug and


ground
When main devices are used in non
service entrance applications, the
bonding strap must be removed to
separate the electrical connection
between the ground and neutral.

Vacubreak switch available up to


800A.

Connecting cross bus rated


1200 Amps on all devices.

Factory installed NEMA II studs


750kcmil Aluminum wire options.

Removable bottom endwall


The bottom of every enclosure is
blank and removable which allows
the user to cut knockouts after the
device and conduit is installed.
Underground feed only (EUSERC
Compliant)
Removable ground trough
Generous wire-pulling room
for grounding conductors.

s | Power Mod™ with QuickSystem™


6-2
Power Mod Switch-Pullbox Combinations
Features

Front Mounted Handles


Removes the need for spacers on the
side.

Ground lugs
3 ground lugs included for bonding
additional systems. Mounting ear
Pivot factory installed mounting ears
to minimum or maximum position
Siemens to provide additional stability when
exclusive mounting equipment onto wall.
feature

QuickConnect™
QuickConnect reduces bussing
connections from many to
one ensuring a single reliable
connection instead of multiple
connections.

QuickTorque™
Eliminates the need for time
consuming torque readings, this
breakaway nut provides the correct
indication of torque of the
QuickConnect. When tightened, the
outer head twists off at the proper Siemens
torque for connection, leaving a single exclusive
nut for future maintenance. feature

QuickRoll™
Siemens QuickRoll eliminates the typical metal
exclusive brackets for mounting modules to the
feature wall. Instead of metal scraping metal
QuickBolt™ QuickRoll allows the module to glide
QuickBolt eliminates the requirement down the mounting rail via a durable
to line up mechanical connections- nylon wheel inside mounting bracket.
instead bolts remain retracted until the
openings lineup - allowing the bolts to
protrude through automatically.
Springs push the bolts through and
provide positive pressure to keep bolts
in place while wingnuts are attached
and tightened.

s | Power Mod™ with QuickSystem™


6-3
Power Mod Switch-Pullbox Combinations
Catalog numbers

Combination fusible switch and pullbox modules: 1-phase, 3-wire SN, 120/240V AC
Meets EUSERC requirements, 100k AIC b
Dimensions (inches) a Line sidec
connections KO
Catalog Rating Service Fuse (lugs not drawing
number Amps feed type c Height Width Depth included) no.

1 set of
WES1400BU 400 UG T 54.06 29.19 15.94 2 studs ES-1

WES1600BU 600 UG T 54.06 29.19 15.94 2 sets of ES-2


2 studs
WES1800BU 800 UG T 54.06 29.19 15.94 ES-2

3 sets of
WES11200BUd 1200 UG T 68.97 34.25 13.47 2 studs ES-3

Combination fusible switch and pullbox modules: 3-phase, 4-wire SN, 240V AC max.
Meets EUSERC requirements, 100k AIC b
Dimensions (inches) a Line sidec
connections KO
Catalog Rating Service Fuse (lugs not drawing
number Amps feed type Height Width Depth included) no.

1 set of
WES3400BU 400 UG T 54.06 29.19 15.94 2 studs ES-1

WES3600BU 600 UG T 54.06 29.19 15.94 2 sets of ES-2


2 studs
WES3800BU 800 UG T 54.06 29.19 15.94 ES-2

3 sets of
WES31200BUd 1200 UG T 68.97 34.25 13.47 2 studs ES-3

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or
hardware protrusions
b Fuses not included
c Lugs not included. NEMA II Stud Pattern lugs must be installed by user or utility. Refer to page 6-5 for Lug size options.
d Device uses a molded case switch (looks like a breaker). Class T fuses must be installed in conjunction with the molded case switch
for proper operation.

s | Power Mod™ with QuickSystem™


6-4
Power Mod Switch-Pullbox Combinations
Lug selector catalog numbers

Wire Size  Switch-Pullbox Combination lug kits

Amperage No. conductors 500 kcmil 600 kcmil 750 kcmil


400 1 n/a n/a LK11750N2
2 LK12500N2 n/a n/a
600 2 LK12500N2E n/a LK12750N2
1 Phase
800 2 n/a LK12600N2 LK12750N2
3 LK13500N2 n/a n/a
1200 3 n/a n/a LK13750N2E
4 LK14500N2E n/a n/a

400 1 n/a n/a LK31750N2


2 LK32500N2 n/a n/a
600 2 LK32500N2E n/a LK32750N2
3 Phase 800 2 n/a LK32600N2 LK32750N2
3 LK33500N2 n/a n/a
1200 3 n/a n/a LK33750N2E
4 LK34500N2E n/a n/a

s | Power Mod™ with QuickSystem™


6-5
Power Mod Switch-Pullbox Combinations
Knockout diagrams

ES-1 ES-2
WES1400BU WES3400BU WES1600BU WES3600BU
WES1800BU WES3800BU

s | Power Mod™ with QuickSystem™


6-6
Power Mod Switch-Pullbox Combinations
Knockout diagrams
34-1/4

13-15/32

26-9/16

1-3/4" NEMA 68-31/32


STUD SPACING

44-7/8 TO
BOTTOM OF
} QUICK ROLL
BRACKET

33-1/4 TO
CROSS BUS
26-13/16 TO CENTER
PHASE AND
NEUTRAL STUDS

29-1/8 3-7/8

(3) 3/4" KOs

8-5/8

REMOVABLE BOTTOM
1-1/8 ENDWALL OPENING

ES-3
WES11200BU WES31200BU

s | Power Mod™ with QuickSystem™


6-7
Catalog number logic example

W ES 3 4 0 0 B U

Enclosure Incoming feed

W = Outdoor U = 100K AIC rated unit

Amperage
Device
400
ES = EUSERC Switch Phase
600 Incoming feed
1 = Single Phase
800 B = Bottom feed construction
3 = Three Phase
1200
Power Mod™

Standard tapbox modules (type WTB) are designed for


versatility, space savings, and flexibility.

Features include:
J QuickSystem™ features
J Standard compression lug capability
J Invertibility: devices can be rotated to accommodate the
desired incoming feed direction
J 750 kcmil AL wire options for most models
J 100K AIC standard for all models
J Broad ampacity ratings from 400 to 1600 Amps
J Line and load capability- service entrance and sub feed
rated

Standard Tapbox quick reference

J 400-1600A
J 1200A thru-bus rating
J UL Standard # UL67
J UL file # E27100
J AIC rating (100K AIC)
J Voltage
- Single phase 120/240V AC max
- Three phase 240V AC max
J All swing latches and rivets are stainless steel.
J NEMA 3R rated
J G90 galvanized steel
J ANSI 61 paint

Standard Tapboxes
www.sea.siemens.com/powermod
Power Mod Standard Tapboxes
Features

Standard compression lug


capability
750 kcmil AL wire options.

Neutral lug with removable


disconnect link
Remove for subfeed use.

4” hub openings
Siemens/Landis & Gyr HD type hubs

s | Power Mod™ with QuickSystem™


7-2
Power Mod Standard Tapboxes
Features

Invertibility
Devices can be rotated to accommodate
the desired incoming feed direction

Connecting cross bus rated


1200 Amps

Siemens
exclusive
feature

QuickConnect™ Mounting ear


QuickConnect reduces bussing Pivot factory installed mounting ears
connections from many to to minimum or maximum position
one- ensuring a single reliable to provide additional stability when
connection instead of multiple mounting equipment onto wall.
connections.

QuickTorque™
Eliminates the need for time
consuming torque readings, this
breakaway nut provides the correct
indication of torque of the
QuickConnect. When tightened, the
outer head twists off at the proper
torque for connection, leaving a single
nut for future maintenance.

Siemens
exclusive Siemens
feature exclusive
QuickBolt™ feature
QuickBolt eliminates the requirement
to line up mechanical connections- QuickRoll™
instead bolts remain retracted until the QuickRoll eliminates the typical metal
openings lineup - allowing the bolts to brackets for mounting modules to the
protrude through automatically. wall. Instead of metal scraping metal
Springs push the bolts through and QuickRoll allows the module to glide
provide positive pressure to keep bolts down the mounting rail via a durable
in place while wingnuts are attached nylon wheel inside mounting bracket.
and tightened.

s | Power Mod™ with QuickSystem™


7-3
Power Mod Standard Tapboxes
Catalog numbers

Tap box modules: 1-phase, 3-wire WN, 120/240V AC, 100k AICc
Dimensions (inches)a
Line side
Catalog Ampere Service connectionse
number rating feedb Height Width Depth (lugs not included) KO drawing no.

WTB1400CU 400 OH/UG 40.13 12.22 13.19 1 set of 2 studs T-1

WTB1800CU 800 OH/UG 40.13 12.22 13.19


T-2
2 sets of 2 studs
WTB11200CU 1200 OH/UG 47.13 15.22 13.31
T-3

WTB11600CUd 1600 OH/UG 49.09 25.09 13.81 3 sets of 2 studs T-4

Tap box modules: 3-phase, 4-wire SN, 240V AC Max., 100k AICc
Dimensions (inches)a
Line side
Catalog Ampere Service connectionse
number rating feedb Height Width Depth (lugs not included) KO drawing no.

WTB3400CU 400 OH/UG 40.13 12.22 13.19 1 set of 2 studs T-1

WTB3800CU 800 OH/UG 40.13 12.22 13.19 T-2


2 sets of 2 studs
WTB31200CU 1200 OH/UG 47.13 15.22 13.31 T-3

WTB31600CUd 1600 OH/UG 49.09 25.09 13.81 3 sets of 2 studs T-4

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
b Module is invertible- rotate device to point hub openings to appropriate feed direction.
c QuickConnect not included. If used for load side application an additional coupler must be ordered.
d 1200 Amp maximum feed per side- must be used as a center fed main.
e Lugs not included. Refer to page 7-5 for lug size options.

s | Power Mod™ with QuickSystem™


7-4
Power Mod Standard Tapboxes
Lug selector catalog numbers

Tap box lug kits


Wire Size  500 kcmil 600 kcmil 750 kcmil

Amperage # Conductors
400 1 n/a LK11600N2 n/a
2 LK12500N2 n/a n/a
800 2 n/a LK12600N2 LK12750N2
1 Phase
3 LK13500N2 n/a n/a
1200 3 n/a n/a LK13750N2
4 LK14500N2 n/a n/a
1600 5 n/a LK15600N2 LK15750N2

400 1 n/a LK31600N2 n/a


2 LK32500N2 n/a n/a
800 2 n/a LK32600N2 LK32750N2
3 Phase 3 LK33500N2 n/a n/a
1200 3 n/a n/a LK33750N2
4 LK34500N2 n/a n/a
1600 5 n/a LK35600N2 LK35750N2

s | Power Mod™ with QuickSystem™


7-5
Power Mod Standard Tapboxes
Knockout diagrams

T-1 T-2
WTB1400CU WTB1800CU
WTB3400CU WTB3800CU

s | Power Mod™ with QuickSystem™


7-6
Power Mod Standard Tapboxes
Knockout diagrams

T-3 T-4
WTB11200CU WTB11600CU

WTB31200CU WTB31600CU

s | Power Mod™ with QuickSystem™


7-7
Catalog number logic example

W TB 3 4 0 0 C U

Enclosure Incoming feed

W = Outdoor U = 100K AIC rated unit


Amperage

Device 400

TB = Tap Box Phase 800


Incoming feed
1 = Single Phase 1200
C = Top and bottom feed construction
3 = Three Phase 1600
Power Mod™

EUSERC - compliant Tapbox-Pullbox Combination modules


(type WET) offer EUSERC compatibility, a wider range of
lug options, and extra space for pulling in conductors.

Features include:
J QuickSystem™ features
J Standard compression lug capability
J 750 kcmil AL wire options for most models
J 100K AIC standard for all models
J Broad ampacity ratings from 400 to 1200 Amps
J Removable bottom endwall

Tapbox- Pullbox Combination quick reference

J 400-1200A
J 1200 Amp thru-bus rating
J UL Standard #’s UL67
J UL file # E27100
J AIC Rating (100k)
J Voltage
- Single phase 120/240V AC max
- Three phase 240V AC max
J All swing latches and rivets are stainless steel.
J NEMA 3R rated
J G90 galvanized steel
J ANSI 61paint

Tapbox - Pullbox Combinations


www.sea.siemens.com/powermod
Power Mod Tapbox - Pullbox Combinations
Features

Connecting cross bus rated 1200


Amps

Standard compression lug


capability.
750 kcmil aluminum wire options
available.

Removable bottom endwall


The bottom of every enclosure is
blank and removable which allows
the user to cut knockouts after the
device and conduit is installed.
Underground feed only (EUSERC
compliant).

s | Power Mod™ with QuickSystem™


8-2
Power Mod Tapbox - Pullbox Combinations
Features

Ground lugs
3 ground lugs for bonding
additional systems.

Siemens
exclusive
feature
Mounting ear
QuickConnect™ Pivot factory installed mounting ears
QuickConnect reduces bussing to minimum or maximum position
connections from many to to provide additional stability when
one- ensuring a single reliable mounting equipment onto wall.
connection instead of multiple
connections.

QuickTorque™
Eliminates the need for time
consuming torque readings, this
breakaway nut provides the correct
indication of torque of the
QuickConnect. When tightened, the
outer head twists off at the proper
torque for connection, leaving a single
nut for future maintenance.

Siemens
exclusive
Siemens
feature
exclusive
QuickBolt™ feature
QuickBolt eliminates the requirement
to line up mechanical connections- QuickRoll™
instead bolts remain retracted until the QuickRoll eliminates the typical metal
openings lineup - allowing the bolts to brackets for mounting modules to the
protrude through automatically. wall. Instead of metal scraping metal
Springs push the bolts through and QuickRoll allows the module to glide
provide positive pressure to keep bolts down the mounting rail via a durable
in place while wingnuts are attached nylon wheel inside mounting bracket.
and tightened.

s
8-3
Power Mod Tapbox - Pullbox Combinations
Catalog numbers

EUSERC tap box modules: 1-phase, 3-wire SN, incoming, 120/240V ACb
Meets EUSERC requirements, 100k AIC
Dimensions (inches)a Line side
Catalog Ampere Service connectionsc
numberb rating feed Height Width Depth (lugs not included) KO drawing no.

WET1400BU 400 UG 46.19 17.63 8.56 1 set of 2 studs ET-1

WET1800BU 800 UG 50.19 27.13 11.38 2 sets of 2 studs ET-2

WET11200BU 1200 UG 50.19 35.19 11.38 3 sets of 2 studs ET-3

EUSERC tap box modules: 3-phase, 4-wire SN, incoming, 240V AC max.b
Meets EUSERC requirements, 100k AIC
Dimensions (inches)a Line side
Catalog Ampere Service connectionsc
numberb rating feed Height Width Depth (lugs not included) KO drawing no.

WET3400BU 400 UG 46.19 17.63 8.56 1 set of 2 studs ET-1

WET3800BU 800 UG 50.19 27.13 11.38 2 sets of 2 studs ET-2

WET31200BU 1200 UG 50.19 35.19 11.38 3 sets of 2 studs ET-3

a Dimensions shown are representative of outside obx dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
b QuickConnect not included. Service entrance rated only.
c Lugs not included. Refer to page 8-5 for lug size options.

s | Power Mod™ with QuickSystem™


8-4
Power Mod Tapbox - Pullbox Combinations
Lug selector catalog numbers

Tapbox-Pullbox Combination lug kits

Wire Size  500 kcmil 600 kcmil 750 kcmil

Amperage # Conductors
400 1 n/a n/a LK11750N2
2 LK12500N2 n/a n/a
600 2 LK12500N2E n/a LK12750N2
1 Phase
800 2 n/a LK12600N2 LK12750N2
3 LK13500N2 n/a n/a
1200 3 n/a n/a LK13750N2E
4 LK14500N2E n/a n/a

400 1 n/a n/a LK31750N2


2 LK32500N2 n/a n/a
600 2 LK32500N2E n/a LK32750N2
3 Phase 800 2 n/a LK32600N2 LK32750N2
3 LK33500N2 n/a n/a
1200 3 n/a n/a LK33750N2E
4 LK34500N2E n/a n/a

s
8-5
Power Mod Tapbox - Pullbox Combinations
Knockout diagrams

ET-1 ET-2
WET1400BU WET1800BU
WET3400BU WET3800BU

s | Power Mod™ with QuickSystem™


8-6
Power Mod Tapbox - Pullbox Combinations
Knockout diagrams

ET-3
WET11200BU

WET31200BU

s
8-7
Catalog Number Logic Example

W ET 3 4 0 0 B U

Enclosure
Incoming Feed
W = Outdoor
U = 100K AIC rated unit

Device Amperage

ET = EUSERC Tap Phase 400

1 = Single Phase 800

3 = Three Phase 1200


Incoming Feed

B = Bottom feed construction


1PXFS.PEt

Commercial Lever Bypass meter stacks (type WML) are


designed to meet the requirements of those utilities
specifying lever bypass meter sockets for residential
and commercial applications.

Features include:
 QuickSystem™ features
 High-quality, time-proven Landis & Gyr HQ sockets
 A line of 3-phase 100 Amp meter stacks to minimize
tenant main cost
 Removable back knockout plate to facilitate wiring
 225 Amp capability in single and three phase designs
 Up to 4 positions with 225 Amp tenant mains, up to
2 positions with 400 Amp tenant mains
 Ease of wiring – tenant mains require only a
single bend

Lever Bypass quick reference

 100A/225A 1-4 position


 400A 1-2 position
 1200A thru-bus rating
 UL Standard # UL67
 UL file # E27100
 AIC rating (25K, 65K & 100K)
 Voltage
- Single phase 120/240V AC max
- Three in single phase out 208Y/120V AC
- Three Phase 240V AC max
 All swing latches and rivets are stainless steel.
 NEMA 3R rated
 G90 Galvanized Steel
 ANSI 61 Paint

-FWFS#ZQBTT.FUFS4UBDLT
www.sea.siemens.com/powermod
1PXFS.PE-FWFS#ZQBTT
Features

Reduced height for


increased utility acceptance

High quality
Landis & Gyr HQ lever
bypass block

Horizontal breaker mounting


Reduces installation time and
effort for 3-phase installations

Single phase installations feature


the QS breaker which allows 125
or 225 breaker flexibility without
sacrificing cost

Barrel lock capable covers


Accepts common utility
barrel locks to protect
against unauthorized usages

Neutral lugs centrally located

s | Power Mod™ with QuickSystem™



1PXFS.PE-FWFS#ZQBTT
Features

Siemens
exclusive
feature

QuickConnect™
QuickConnect reduces bussing
connections from many to
one- ensuring a single reliable
connection instead of multiple
connections.

Mounting ear
Pivot factory installed mounting ears
QuickTorque™ to minimum or maximum position
Eliminates the need for time to provide additional stability when
consuming torque readings, this mounting equipment onto wall.
breakaway nut provides the correct
indication of torque of the
QuickConnect. When tightened, the
outer head twists off at the proper
torque for connection, leaving a single
nut for future maintenance.

Siemens
exclusive
feature
QuickBolt™
QuickBolt eliminates the requirement
to line up mechanical connections-
instead bolts remain retracted until the
openings lineup - allowing the bolts to
protrude through automatically.
Springs push the bolts through and
provide positive pressure to keep bolts Siemens
in place while wingnuts are attached exclusive
and tightened. feature

QuickRoll™
Tin plated copper bus straps QuickRoll eliminates the typical metal
brackets for mounting modules to the
wall. Instead of metal scraping metal
QuickRoll allows the module to glide
down the mounting rail via a durable
nylon wheel inside mounting bracket.

s | Power Mod™ with QuickSystem™



Power Mod: Lever Bypass
Catalog numbers

Commercial Meter Stacks: Lever Bypass

Max. Stack
Meter tenant Dimensions (inches)a phasing KO
Catalog positions breaker Breaker Maximum phases/ dwg. Schematic
number per stack (Amps) Provisions AICc Height Width Depth socketse no. no.

1-phase, 3-wire SN, incoming and outgoing, ringless type lever bypass, 5-jaw socketsb
WML11225RJ 1 QS, QSH, 100,000 27.75 19.50 9.00 – L-1 S-1
QSHH, HQS,
WML21225RJ 2 HQSH, QP, 100,000 40.75 19.50 9.00 – L-2 S-1
225
WML31225RJ 3 QPH, HQP, 100,000 49.75 19.50 9.00 – L-3 S-1
MP-T, MP-HT,
WML41225RJ 4 MP-MT 100,000 62.75 19.50 9.00 – L-4 S-1

WML11400RJ d
1 JXD62B400 25,000 44.00 16.31 9.69 – L-5 S-2
400
WML21400RJd 2 Factory inst 25,000 70.38 23.00 9.69 – L-6 S-3

3-phase, 4-wire SN, incoming and 1-phase, 3-wire SN outgoing, ringless type lever bypass, 5-jaw socketsb
WML12225RJ 1 100,000 27.75 19.50 9.00 1-AB L-1 S-4

WML22AB225RJ 2 100,000 40.75 19.50 9.00 1-AC, 1-BC L-2 S-5

WML22BC225RJ 2 QS, QSH, 100,000 40.75 19.50 9.00 1-AC, 1-AB L-2 S-6
QSHH, HQS,
WML22CA225RJ 2 100,000 40.75 19.50 9.00 1-AB, 1-BC L-2 S-7
HQSH, QP,
225 1-AB, 1-BC,
WML32225RJ 3 QPH, HQP, 100,000 49.75 19.50 9.00 L-3 S-8
MP-T, MP-HT, 1-CA
MP-MT 2-AB-, 1-BC,
WML42AB225RJ 4 100,000 62.75 19.50 9.00 L-4 S-9
1-CA
1-AB, 2-BC,
WML42BC225RJ 4 100,000 62.75 19.50 9.00 L-4 S-10
1-CA
1-AB, 1-BC,
WML42CA225RJ 4 100,000 62.75 19.50 9.00 L-4 S-11
2-CA
WML12400RJ d
1 JXD62B400 25,000 44.00 16.31 9.69 1-AB L-5 S-12
400
WML22400RJd 2 Factory Inst 25,000 70.38 23.00 9.69 1-AB, 1-BC L-6 S-13

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
b Not for use on 3-phase, 4-wire delta systems
c Max AIC determined by maximum AIC of tenant breakers when used in conjunction with a meter socket. Higher overall ratings may be achieved
through approved series rating combinations.
d Alternate amperage breakers are available. Please see table on right for suffix that needs to be added. Additional lead time may apply. Contact sales
office for details.
e Commerical Stacks are not field phaseable at this time. 1 Meter Position Breaker 2 Meter Positions Breaker
Per Stack Amperage Per Stack Amperage
Add
T1 200A T5 200A/200A
Suffix
 T2 250A T6 200A/250A
T3 300A T7 200/300A
T4 350A T8 200/350A
Alternate amperage breakers Add T9 200/400A
Suffix T10 250A/300A
 T11 250A/350A
T12 250A/400A
T13 300A/300A
T14 300A/350A
T15 300A/400A
T16 350A/350A
T17 350A/400A

s | Power Mod™ with QuickSystem™


9-4
Power Mod: Lever Bypass
Catalog numbers

Commercial Meter Stacks: Lever Bypass

Max.
Meter tenant Dimensions (inches)a KO
Catalog positions breaker Breaker Maximum dwg. Schematic
number per stack (Amps)c provisions AICc Height Width Depth no. no.

3-phase, 4-wire SN, incoming and outgoing, ringless type lever bypass, 7-jaw socketse
WML13100RJb 1 65,000 27.75 23.50 9.00 L-7 S-14
QP, MP-T,
WML23100RJ b
2 QPH, MP-HT, 65,000 40.75 23.50 9.00 L-8 S-14
100
WML33100RJ b
3 HQP, MP-MT 65,000 49.75 23.50 9.00 L-9 S-14

WML43100RJb 4 65,000 62.75 23.50 9.00 L-10 S-14

WML13225RJ 1 100,000 27.75 23.50 9.00 L-11 S-14


QJ2, QJH2,
WML23225RJ 2 QJ2H, HQJ2H, 100,000 40.75 23.50 9.00 L-12 S-14
225
WML33225RJ 3 MQ, MQH, 100,000 49.75 23.50 9.00 L-13 S-14
MQL
WML43225RJ 4 100,000 62.75 23.50 9.00 L-14 S-14

WML13400RJd 1 JXD638400 25,000 44.00 16.31 9.69 L-5 S-15


400
WML23400RJ d
2 Factory Inst 25,000 70.38 23.00 9.69 L-6 S-16

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
b 3-pole breakers only
c Max AIC determined by maximum AIC of tenant breakers when used in conjunction with a meter socket. Higher overall ratings may be achieved
through approved series rating combinations.
d Alternate amperage breakers are available. Please see below table for suffix that needs to be added. Additional lead time may apply. Contact sales
office for details.
e Rated for use with 240/120V Delta systems

Alternate amperage breakers


1 Meter Position Breaker 2 Meter Positions Breaker
Per Stack Amperage Per Stack Amperage
Add
T1 200A T5 200A/200A
Suffix
 T2 250A T6 200A/250A
T3 300A T7 200/300A
T4 350A T8 200/350A
Add T9 200/400A
Suffix T10 250A/300A
 T11 250A/350A
T12 250A/400A
T13 300A/300A
T14 300A/350A
T15 300A/400A
T16 350A/350A
T17 350A/400A

s | Power Mod™ with QuickSystem™


9-5
Power Mod: Lever Bypass
Knockout diagrams

L-1 L-2
WML11225RJ WML12225RJ WML21225RJ WML22BC225RJ
WML22AB225RJ WML22CA225RJ

L-3
WML31225RJ WML32225RJ

s | Power Mod™ with QuickSystem™


9-6
Power Mod: Lever Bypass
Knockout diagrams

L-5
WML11400RJ WML13400RJ
WML12400RJ

L-4
WML41225RJ WML42BC225RJ
WML42AB225RJ WML42CA225RJ

L-6
WML21400RJ WML23400RJ
WML22400RJ

s | Power Mod™ with QuickSystem™


9-7
Power Mod: Lever Bypass
Knockout diagrams

L-7 L-8
WML13100RJ WML23100RJ

L-9 L-10
WML33100RJ  WML43100RJ

s | Power Mod™ with QuickSystem™


9-8
Power Mod: Lever Bypass
Knockout diagrams

L-11 L-12
WML13225RJ WML23225RJ

L-14
L-13
WML43225RJ
WML33225RJ

s | Power Mod™ with QuickSystem™


9-9
Power Mod: Lever Bypass
Schematics

EQUIPMENT GROUND

A B
NEUTRAL
(POTENTIAL JAW)
NEUTRAL
B A (POTENTIAL JAW) NEUTRAL
(POTENTIAL JAW)
A A
N N
B B
NEUTRAL
LUGS

A A
N N
Equip. B B
Grd.
B A

A B A B

S-2
WML11400RJ
WML11400RJ
B A
S-3
A A
N N WML21400RJ
B B WML21400RJ

B A

Equip. B C C A
Grd.
A A A A
N N N N
B B B B
S-1 C C C C

WML41225RJ
WMLX1225RJ

NEUTRAL NEUTRAL
(POTENTIAL JAW) (POTENTIAL JAW)
C A B A

Equip. Equip.
Grd. Grd.

S-5 S-6
NEUTRAL
(POTENTIAL JAW)
WML22AB225RJ
WML22AB225RJ WML22BC225RJ
WML22BC225RJ
B A

A A
N N
B B
C C

Equip.
Grd.

B A
S-4
WML12225RJ

WML12225RJ
C A
C A

B A
B A
B A
A A
A A N N
A A N N
N N B B
B B C C
B B C C
C C

NEUTRAL NEUTRAL
NEUTRAL (POTENTIAL JAW)
(POTENTIAL JAW)
(POTENTIAL JAW) B C
B C
B C

Equip. Equip. Equip.


Grd. Grd. Grd.

S-7 S-8 S-9


WML22CA225RJ
WML22CA225RJ WML32225RJ WML42AB225RJ
WML42AB225RJ
WML32225RJ
s | Power Mod™ with QuickSystem™
9-10
Power Mod: Lever Bypass
Schematics

NEUTRAL
(POTENTIAL JAW)

A A
N N
B C C A
B B
C C

Equip.
Grd.

C A C A A B

S-12
WML12400RJ
WML12400RJ

B A B A

A A A A
N N N N
B B B B
C C C C

NEUTRAL
NEUTRAL NEUTRAL (POTENTIAL JAW)
(POTENTIAL JAW) (POTENTIAL JAW)
B C B C

Equip. Equip.
Grd. Grd. A A
N N
B B
C C
S-10 S-11
WML42BC225RJ
WML42BC225RJ WML42CA225RJ
WML42CA225RJ
Equip.
Grd.

A B C HIGH LEG FOR 3Ø,


4 WIRE DELTA SYSTEM

S-15
WML13400RJ
WML13400RJ
HIGH LEG FOR 3Ø,
4 WIRE DELTA SYSTEM
(ALL BRANCH POSITIONS)

EQUIPMENT GROUND A
B
C NEUTRAL
(POTENTIAL JAW)
C B

NEUTRAL
(POTENTIAL JAW) A
B
C HIGH LEG FOR 3Ø, EQUIPMENT GROUND
4 WIRE DELTA SYSTEM
(ALL BRANCH POSITIONS)
NEUTRAL
LUGS NEUTRAL
(POTENTIAL JAW)
A B C
A A
N N HIGH LEG FOR 3Ø,
B B 4 WIRE DELTA SYSTEM
C C
A
B
C
A C
A A
N N
B B
C C
NEUTRAL
LUGS

A A
N N
B B
S-13 C C

WML22400RJ A
WML22400RJ B A B C
C
HIGH LEG FOR 3Ø,
4 WIRE DELTA SYSTEM

Equip.
Grd.

S-14 S-16
WML43100RJ WML23400RJ
WMLX3100RJ WMLX3225RJ WML23400RJ

s | Power Mod™ with QuickSystem™


9-11
Catalog Number Logic Example

W M L 1 3 100 R J

WML Positions Amperage


Cover
WML = NEMA 3R Lever 1 = One position 100
bypass stack R = Ringless
2 = Two positions 225 a

3 = Three positions 400

4 = Four positions 5th Jaw

J = 5th Jaw install (7 jaws for 3 phase in/out)

Phase

1 = Single phase

2 = 3 phase in/single out a

3 = 3 phase

a 2 postion and 4 postion 225A stacks have AB, BC, or CA configurations


1PXFS.PEt

Commercial K-Base Meter Stacks (type WMK) are designed


to meet the requirements of those utilities specifying
bolt-in meter sockets for 400 and 600 Amp residential and
commercial applications.

Features include:
 QuickSystem™ features
 Exclusive Landis & Gyr K4, K5, & K7 meter sockets
 1 position K4, K5, K7 modules with 400 & 600 Amp
tenant mains
 2 position K7 module with 400 Amp tenant main
 Space saving design

K-Base quick reference

 400A & 600A 1-2 positions


 1200A Thru bus-rating
 UL Standard # UL67
 UL file # E27100
 AIC Rating (25k)
 Voltage
- Single Phase 120/240V AC Max
- Three In Single Phase Out 208Y/120V AC
- Three Phase 240V AC Max
 All swing latches and rivets are stainless steel
 NEMA 3R rated
 G90 Galvanized Steel
 ANSI 61 Paint

,#BTF.FUFS4UBDLT
www.sea.siemens.com/powermod
1PXFS.PE,#BTF
Features


High quality
Landis & Gyr bolt
on meter base

Connecting cross bus rated


1200 Amps

External main
service disconnect
Provides safety with quick
convenient access to disconnect
made externally. Eliminates taking
time to remove cover to disconnect

s | Power Mod™ with Quick System™



Power Mod: K-Base
Features

Siemens
exclusive
feature

QuickConnect™
QuickConnect reduces bussing
connections from many to
one- ensuring a single reliable
connection instead of multiple
connections.

Mounting ear
Pivot factory installed mounting ears
to minimum or maximum position
QuickTorque™
to provide additional stability when
Eliminates the need for time
mounting equipment onto wall.
consuming torque readings,
this breakaway nut provides the
correct indication of torque of the
QuickConnect. When tightened, the
outer head twists off at the proper
torque for connection, leaving a
single nut for future maintenance.

Siemens
exclusive
feature

QuickBolt™
QuickBolt eliminates the requirement
to line up mechanical connections-
instead bolts remain retracted until the
openings lineup - allowing the bolts to
protrude through automatically.
Springs push the bolts through and
provide positive pressure to keep bolts Siemens
in place while wingnuts are attached exclusive
and tightened. feature

QuickRoll™
QuickRoll eliminates the typical metal
brackets for mounting modules to the
wall. Instead of metal scraping metal
QuickRoll allows the module to glide
down the mounting rail via a durable
nylon wheel inside mounting bracket.

s | Power Mod™ with Quick System™


10-3
Power Mod: K-Base
Catalog numbers

Commercial meter stacks: K-Base bolt-in, 25k AICc f


Meter Max. Dimensions (inches)a KO
Catalog positions tenant breaker Breaker dwg. Schematics
number per stack (Amps) provisiond Height Width Depth Phase no. no.

1-phase, 3-wire SN, incoming and outgoing, K4 K-Base bolt-in


JXD62B400
WMK11400Rd 1 400
Factory Inst.
54.00 19.25 10.00 — KB-1 S-1
LXD62B600
WMK11600R 1 600 54.00 19.25 10.00 — KB-1 S-1
Factory Inst.
3-phase, 4-wire SN, incoming and 1-phase, 3-wire SN outgoing, K5 K-Base bolt-in bf

JXD62B400
WMK12400RJd 1 400
Factory Inst.
54.00 19.25 10.00 AB KB-2 S-2

3-phase, 4-wire SN, incoming and outgoing, K7 K-Base bolt-ine


WMK13400RJd 1 54.00 19.25 10.00 — KB-2 S-3
JXD63B400
400
Factory Inst.
WMK23400RJd 2 72.88 27.00 11.00 — KB-3 S-4
LXD63B600
WMK13600RJ 1 600 54.00 19.25 10.00 — KB-2 S-3
Factory Inst.
a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
b Not for use on 3-Phase 4-wire delta systems
c Max AIC determined by maximum AIC of tenant breakers when used in conjunction with a meter socket. Higher overall ratings may be achieved
through approved series rating combinations
d Alternate amperage breakers are available. Please see table below for suffix that needs to be added for ordering. Extended leadtime may apply. Contact
sales office for more details.
e Rated for use with 240/120V Delta systems
f Commerical Stacks are not field phaseable

Alternate amperage breakers


1 Meter Position Breaker 2 Meter Positions Breaker
Per Stack Amperage Per Stack Amperage
Add
T1 200A T5 200A/200A
Suffix
 T2 250A T6 200A/250A
T3 300A T7 200/300A
T4 350A T8 200/350A
Add T9 200/400A
Suffix T10 250A/300A
 T11 250A/350A
T12 250A/400A
T13 300A/300A
T14 300A/350A
T15 300A/400A
T16 350A/350A
T17 350A/400A

s | Power Mod™ with Quick System™


10-4
Power Mod: K-Base
Knockout diagrams

KB-2
WMK12400RJ WMK13600RJ
WMK13400RJ

KB-1
WMK11400R
WMK11600R Schematics NEUTRAL
(POTENTIAL JAW)

A A
N N
B B
C C

A A
Equip.
N N Grd.
B B
A B

S-2
Equip.
Grd. WMK12400RJ
WMK12400RJ
A B

S-1

WMK11400R WMK11600R
WMK11400R HIGH LEG FOR 3Ø,
4 WIRE DELTA SYSTEM
EQUIPMENT GROUND

WMK11600R
(ALL BRANCH POSITIONS)
NEUTRAL
(POTENTIAL JAW)
A B C

NEUTRAL
(POTENTIAL JAW)

NEUTRAL
LUGS

A A A A
N N N N
B B
B B C C
C C

A B C

HIGH LEG FOR 3Ø,


Equip. 4 WIRE DELTA SYSTEM
Grd.

A B C HIGH LEG FOR 3Ø,


4 WIRE DELTA SYSTEM
KB-3
WMK23400RJ S-3 S-4
WMK23400RJ
WMK13400RJ WMK13600RJ WMK23400RJ
WMK13400RJ
s
WMK13600RJ | Power Mod™ with Quick System™
10-5
Catalog Number Logic Example

W M K 1 1 400 R J

Positions

WMK 1 Amperage 5th jaw

WMK = NEMA 3R K-Base 2 400


J = 5th jaw installed (7 jaws for 3-phase in/out)
600

BLANK = No 5th jaw

Phase
Cover
1 = Single phase
R = Ringless
2 = 3-phase in/single out
BLANK = Ring Type
3 = 3-phase
1PXFS.PEt

Commercial Test Block Bypass Meter Stacks (type WMT)


are designed to meet the requirements of those utilities
specifying test block bypass meter sockets for commercial
applications in areas subscribing to the EUSERC standards.

Features include:
 QuickSystem™ features
 High-quality, time-proven Siemens SMM switchboard
meter socket
 Removable back knockout plate to facilitate wiring
 225 Amp capability in single and three phase designs
 Up to 3 positions with 225 Amp tenant mains
 Wiring flexibility - tenant mains require only a single
bend
 Three phase input, single phase output modules
 In line wiring: side knockouts allow wiring for adjacent
units to pass through

Test Block Bypass quick reference

 225A 1-3 positions


 1200A thru-bus rating
 UL Standard #’s UL67
 UL file # E27100
 AIC Rating (100k)
 Voltage
- Single phase 120/240V AC max
- 3 phase in single phase out 120Y/208V AC max
- Three phase 240V AC max
 All swing latches and rivets are stainless steel
 NEMA 3R rated
 G90 galvanized steel
 ANSI 61 paint
 EUSERC drawing numbers 304 and 305

5FTU#MPDL#ZQBTT.FUFS4UBDLT
www.sea.siemens.com/powermod
1PXFS.PE5FTU#MPDL#ZQBTT
Features

EUSERC compliant Test Block


Bypass Meter Socket

Breakers require only a single


bend to wire
Single phase installations feature
the QS breaker which allows 125
or 225 breaker flexibility without
sacrificing cost. Three phase
installations feature a horizontally
mounted breaker which minimizes
height and allows for a single bend
to wire.

Neutral lugs centrally located

Removable back KO plate


Keeping the contractor in
mind, simplifies and speeds up
pulling wire. Entire plate can be
removed to allow ample space
for wire. Knockouts in the plate
can be removed before or after
stack installation

Side knockouts for pass


through conductors

s | Power Mod™ with Quick System™



1PXFS.PE5FTU#MPDL#ZQBTT
Features

Siemens
exclusive
feature

QuickConnect™
QuickConnect reduces bussing
connections from many to
one- ensuring a single reliable
connection instead of multiple
connections.

Mounting ear
Pivot factory installed mounting ears
to minimum or maximum position
QuickTorque™ to provide additional stability when
Eliminates the need for time mounting equipment onto wall.
consuming torque readings, this
breakaway nut provides the correct
indication of torque of the Quick-
Connect. When tightened, the outer
head twists off at the proper torque
for connection, leaving a single nut
for future maintenance.

Siemens
exclusive
feature
QuickBolt™
QuickBolt eliminates the requirement
to line up mechanical connections-
instead bolts remain retracted until the
openings lineup - allowing the bolts to
protrude through automatically.
Springs push the bolts through and
provide positive pressure to keep bolts Siemens
in place while wingnuts are attached exclusive
and tightened. feature

QuickRoll™
QuickRoll eliminates the typical metal
brackets for mounting modules to the
wall. Instead of metal scraping metal
QuickRoll allows the module to glide
down the mounting rail via a durable
nylon wheel inside mounting bracket.

s | Power Mod™ with Quick System™



Power Mod: Test Block Bypass
Catalog numbers

Commercial Meter Stacks: Test Block Bypass,100k AICc


Max. Dimensions (inches)a
Meter tenant KO
Catalog positions breaker Breaker dwg. Schematics
number per stack (Amps) provisions Height Width Depth Phase no. no.

1-phase, 3-wire SN, incoming and outgoing, test block bpass, 4-jaw socketsb
WMT11225 1 225 QS, QSH, QSHH, 40.50 21.50 9.00 — TB-1 S-1
HQS, HQSH, QP,
WMT21225 2 225 46.00 21.50 9.00 — TB-2 S-2
QPH, HQP, MP-T,
WMT31225 3 225 MP-HT, MP-MT 65.50 21.50 9.00 — TB-3 S-3

3-phase, 4-wire SN, incoming and 1-phase, 3-wire SN outgoing, test block bypass, 5-jaw socketsb e
WMT12225J 1 225 40.50 21.50 9.00 AB TB-1 S-4

WMT22AB225J 2 225 QS, QSH, QSHH, 46.00 21.50 9.00 1-BC, 1-CA TB-2 S-5
HQS, HQSH, QP,
WMT22BC225J 2 225 46.00 21.50 9.00 1-AB, 1-CA TB-2 S-6
QPH, HQP, MP-T,
WMT22CA225J 2 225 MP-HT, MP-MT 46.00 21.50 9.00 1-AB, 1-BC TB-2 S-7
1-AB, 1-BC,
WMT32225J 3 225 65.50 21.50 9.00 TB-3 S-8
1-CA
3-phase, 4-wire SN, incoming and outgoing, test block bypass, 7-jaw socketsd
WMT13225J 1 225 40.50 25.50 9.00 — TB-4 S-9
QJ2, QJH2,
WMT23225J 2 225 QJ2H, HQJ2H, 46.00 25.50 9.00 — TB-5 S-10
MQ, MQH, MQL
WMT33225J 3 225 65.50 25.50 9.00 — TB-6 S-11
a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
b Not for use on 3-phase,4-wire delta systems.
c Max AIC determined by maximum AIC of tenant breakers when used in conjunction with a meter socket.
d Rated for use with 240/120V Delta systems.
e Commercial Stacks are not field phaseable.

s | Power Mod™ with Quick System™


11-4
Power Mod: Test Block Bypass
Knockout diagrams

TB-1 TB-2
WMT12225J WMT22AB225J WMT22CA225J
WMT22BC225J

TB-3 TB-4
WMT31225J WMT32225J WMT13225J

s | Power Mod™ with Quick System™


11-5
Power Mod: Test Block Bypass
Knockout diagrams

TB-5 TB-6
WMT23225J WMT33225J

Schematics
L L L L
I O I O
N A N A
E D E D

B A

L L L L L L L L
I O I O I O I O
N A N A N A N A
E D E D E D E D

B A B A

A A A A A A
N N N N N N
B B B B B B

Equip. Equip. Equip.


Grd. Grd. Grd.
L L L L L L L L L L L L
I O I O I O I O I O I O
N A N A N A N A N A N A
E D E D E D E D E D E D

B A B A B A

S-1 S-2 S-3


WMT11225 WMT21225 WMT31225
WMT11225 WMT21225 WMT31225

s | Power Mod™ with Quick System™


11-6
Power Mod: Test Block Bypass
Schematics
NEUTRAL
(POTENTIAL JAW)
A A
N N NEUTRAL NEUTRAL
B B (POTENTIAL JAW) (POTENTIAL JAW)
C C L L L L L L L L
I O I O I O I O
N A N A N A N A
E D E D E D E D

Equip.
B C C A
Grd.
L L L L
I O I O
N A N A
E D E D A A A A
N N N N
B B B B
C C C C
B A

S-4 Equip.
Grd.
Equip.
Grd.
WMT12225J L
I
L
O
L
I
L
O
L
I
L
O
L
I
L
O

WMT12225J N
E
A
D
N
E
A
D
N
E
A
D
N
E
A
D

C A B A

S-5 S-6
WMT22AB225J WMT22BC225J
WMT22AB225J WMT22BC225J

NEUTRAL
(POTENTIAL JAW) NEUTRAL (POTENTIAL JAW)

L L L L A A
I O I O N N
N A N A
E D E D B B
C C

B A

HIGH LEG FOR 3Ø,


4 WIRE DELTA SYSTEM
A A
N N L L L L L L
B B Equip. I O I O I O
NEUTRAL Grd. N A N A N A
C C
(POTENTIAL JAW) E D E D E D

L L L L
I O I O
N A N A A
E D E D
B
C
Equip.
Grd.
L L L L
C A
I O I O
N
E
A
D
N
E
A
D S-9
WMT13225J
WMT13225J
B C

L L L L
S-7 I
N
O
A
I
N
O
A

WMT22CA225J E D E D

WMT22CA225J
B A

NEUTRAL (POTENTIAL JAW)


A A
N N HIGH LEG FOR 3Ø,
B B 4 WIRE DELTA SYSTEM
C C (ALL BRANCH POSITIONS) L L L L L L
I O I O I O
N A N A N A
E D E D E D

Equip. A
Grd. B
L L L L C
I O I O
N A N A
E D E D

B C
NEUTRAL (POTENTIAL JAW)

HIGH LEG FOR 3Ø,


4 WIRE DELTA SYSTEM
(ALL BRANCH POSITIONS) L L L L L L S-8 L L L L L L

WMT32225J
I O I O I O I O I O I O
N A N A N A N A N A N A
E D E D E D E D E D E D
WMT32225J
A A
B B
C C
A A A A
N N N N
B B B B
C C C C

HIGH LEG FOR 3Ø, HIGH LEG FOR 3Ø,


4 WIRE DELTA SYSTEM 4 WIRE DELTA SYSTEM

Equip. Equip. L L L L L L
L L L L L L
Grd. I O I O I O Grd. I O I O I O
N A N A N A N A N A N A
E D E D E D E D E D E D

A A
B B
C C

S-10 S-11
WMT23225J WMT33225J
WMT23225J WMT33225J

s | Power Mod™ with Quick System™


11-7
Catalog Number Logic Example

W M T 1 2 225 J

Positions
Amperage
WMT 1 5th jaw
225
WMT = N3R Test Block Bypass Stack 2a
J = 5th jaw installed (7 jaws for 3-phase in/out)
3

BLANK = No 5th jaw

Phase

1 = Single phase

2 = 3-phase in/single out

3 = 3-phase

a 2 position 225A stacks have AB, BC, or CA configurations.


1PXFS.PEt

Siemens offers a wide range of accessories to help


customize the product to fit your application. Eliminate the
need for special orders with replacement part kits available
for your convenience. All kits come with appropriate
hardware and instruction sheets for safe installation.

Accessory quick reference

For lugs:
 UL486A/B
 750 kcmil maximum wire size (may vary by catalog
number)
 Tin plated aluminum extrusions

For QS Breaker:
 UL489
 100-225 Amps
 300 kcmil maximum wire size

"DDFTTPSJFT
www.sea.siemens.com/powermod
Power Mod lug kits
Lug selector catalog numbers

Lug kits are available to meet the growing demand for multiple
wiring configurations using aluminum and copper conductors in
today’s market. PowerModTM offers a variety of lug configurations
for every breaker, switch, and tap box module. Standard circuit
breaker mains (type WB) include lugs for 1200 Amp and below
models. All other modules come with factory studs and require
lugs to be field installed. The chart below will help you in
identifying the proper lug kit based on your conductor size.

For example, if you have (1) 1200 single phase tapbox, and are
running (3) 750 kcmil wires per phase, you would order (1)
LK13750N2

Type WTB Type WB


How to use the Power Mod lug selector:

1. Select enclosure from top


2. Choose applicable wire size
Standard Standard
3. Select number of conductors being run
tapbox breaker
beside appropriate amperage and phase to
find correct lug kit part number

Wire size 500 600 750 500 600 750

Amperage # Conductors
400 1 n/a LK11600N2 n/a n/a n/a LK11750*
2 LK12500N2 n/a n/a LK12500*^ n/a n/a
600 2 n/a n/a n/a LK12500*^ n/a n/a
800 2 n/a LK12600N2 LK12750N2 n/a n/a n/a
1 Phase
3 LK13500N2 n/a n/a LK13500*^ n/a LK13750*
1200 3 n/a n/a LK13750N2 n/a n/a LK13750*
4 LK14500N2 n/a n/a LK14500*^ n/a n/a
1600 5 n/a LK15600N2 LK15750N2 n/a LK15600N2 LK15750N2
2000 6 n/a n/a n/a n/a n/a LK16750N2

400 1 n/a LK31600N2 n/a n/a n/a LK31750*


2 LK32500N2 n/a n/a LK32500*^ n/a n/a
600 2 n/a n/a n/a LK32500*^ n/a n/a
800 2 n/a LK32600N2 LK32750N2 n/a n/a n/a
3 Phase 3 LK33500N2 n/a n/a LK33500*^ n/a LK33750*
1200 3 n/a n/a LK33750N2 n/a n/a LK33750*
4 LK34500N2 n/a n/a LK34500*^ n/a n/a
1600 5 n/a LK35600N2 LK35750N2 n/a LK35600N2 LK35750N2
2000 6 n/a n/a n/a n/a n/a LK36750N2

* Lug kits -Sentron breaker lugs

s | Power Mod™ with QuickSystem™


12-2
Power Mod lug kits
Lug selector catalog numbers

Type WB Type WS Types WET, WES, WEB

Standard Standard Pullbox


breaker lug landing pad fusible switch combination units

350 500 600 750 500 600 750 500 600 750

n/a n/a LK11600N2 n/a n/a LK11600N2 LK11750N2 n/a n/a LK11750N2
LK12350N2 n/a n/a n/a LK12500N2 n/a n/a LK12500N2 n/a n/a
LK12350N2 n/a n/a n/a LK12500N2 n/a n/a LK12500N2E n/a LK12750N2
n/a n/a LK12600N2 LK12750N2 n/a LK12600N2 LK12750N2 n/a LK12600N2 LK12750N2
n/a LK13500N2 n/a n/a LK13500N2 n/a n/a LK13500N2 n/a n/a
n/a n/a n/a LK13750N2 n/a n/a n/a n/a n/a LK13750N2E
n/a LK14500N2 n/a n/a LK14500*^ n/a n/a LK14500N2E n/a n/a
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a

n/a n/a LK31600N2 n/a n/a LK31600N2 LK31750N2 n/a n/a LK31750N2
LK32350N2 n/a n/a n/a LK32500N2 n/a n/a LK32500N2 n/a n/a
LK32350N2 n/a n/a n/a LK32500N2 n/a n/a LK32500N2E n/a LK32750N2
n/a n/a LK32600N2 LK32750N2 n/a LK32600N2 LK32750N2 n/a LK32600N2 LK32750N2
n/a LK33500N2 n/a n/a LK33500N2 n/a n/a LK33500N2 n/a n/a
n/a n/a n/a LK33750N2 n/a n/a n/a n/a n/a LK33750N2E
n/a LK34500N2 n/a n/a LK34500*^ n/a n/a LK34500N2E n/a n/a
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a

* Lug kits - Sentron breaker lugs

| Power Mod™ with Quick System™

12-3
Accessories and replacement parts
Catalog numbers

Accessory Catalog number Description

QC1 QuickConnect™ 1-phase, 3-wire, 1200 Amp maximum

QC4 QuickConnect™ 3-phase, 4-wire, 1200 Amp maximum

LLP600 Lug Landing Pad for 400-600 Amp standard Breaker modules (new only)

LLP1200 Lug Landing Pad for 800-1200 Amp standard breaker modules (new only)

Bussed Elbow and Bussed Extensions/Spacers

Dimensions (inches) a
Catalog number Description
Height Length Width

Indoor Bussed Elbow,


1-phase, 3-wire,
BE1 1200 Amp maximum 15.06 15.06 4.87

Indoor Bussed Elbow,


3-phase, 4-wire,
BE4 1200 Amp maximum 15.06 15.06 4.87
Bussed
Elbows
Indoor Bussed Elbow,12”,
1-phase, 3-wire,
BE112 1200 Amp maximum 12.00 12.00 4.87
BE1
BE4

Indoor Bussed Elbow, 12”,


3-phase, 4-wire,
BE412 1200 Amp maximum 12.00 12.00 4.87

Outdoor Bussed Extension,


1-phase, 3-wire,
Bussed WMEX1U 1200 Amp maximum 12.00 7.25 6.25
Extensions/
Spacers
Outdoor Bussed Extension,
WMEX1U 3-phase, 4-wire,
WMEX4U WMEX4U 1200 Amp maximum 12.00 7.25 6.25

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.

s | Power Mod™ with QuickSystem™


12-4
Accessories and replacement parts
Catalog numbers

Catalog number Description

ECMFH Horn bypass kit for new Residential Meter Stacks (1 position)

ECMF5 5th jaw replacement for Residential Meter Stacks

ECMFS Meter Socket replacement for Residential Meter Stacks

ECMFBM1 Breaker mounting replacement for 125 Amp Power Mod Residential Meter Stacks

ECMFBM2 Breaker Mounting replacement for 225 Amp Power Mod Residential Meter Stacks

ECMFMC Meter cover replacement for ring type Power Mod Residential Meter stacks

ECMFMCR Meter cover replacement for Power Mod Ringless Residential Meter stacks

ECMFPK Loose parts replacement kit (parts shipped loose include labels and hardware, QuickConnect™ not included)

ECMFCS Cover screw replacement (quantity 10) for Power Mod Meter Stacks

ECMFC Bottom pull cover replacement for Power Mod Residential Meter Stacks

ECMFPS Quick phase "Z" strap replacement

ECBC Breaker cover replacement for Power Mod Residential Stacks

| Power Mod™ with Quick System™

12-5
Accessories and replacement parts
Catalog numbers

Catalog number Description

ECMFTAB Mounting tabs or "ears" for top of Power Mod devices

Ground/neutral Bar kit for 125 Amp Residential Stacks, ground only for 225 Amp
ECMFGN125
Residential Stacks

ECMFN225 Neutral bar kit for 225 Amp Residential stacks

ECMFWLCLIP Rail/clip located on back of unit with wheels

ECMMRLCK Power Mod ring to ringless cover conversion kit

ECMMBCM Power Mod plastic breaker cover for main breaker units

Power Mod knock-out plate without knock-outs for Residential Stacks


ECMMNKOP

Power Mod knock-out plate with knock-outs for Residential Stacks


ECMMKOP

MMRAIL Standard wall mounting rail

MMCLIP Rail/clip that comes on back of unit (no wheels)

MMZR60 60" long mounting "Z" rail for wall mounting

s | Power Mod™ with QuickSystem™


12-6
Accessories and replacement parts
Catalog numbers

Catalog number Description

WMMBKa Pass thru-bushing - for use with underground pull box

WMEP b
End closure plate

EC56854 c
2" HD type hub

EC56855c 2-1/2" HD type hub

EC56856 3" HD type hub

EC56857 3-1/2" HD type hub

EC56858 4" HD type hub

EC56933S Closure plate for HD hub opening

SRSS Sealing ring - snap-on , stainless steel

SRSW Sealing ring - screw-type , stainless steel

SRSTD Sealing ring - snap-on, aluminum

ECPP Plastic cover plate - for ring style socket

ECCP3 Plastic cover plate - for ringless style socket

ECJSd Meter by-pass jumper 4 and 5 jaw


a One pass thru-bushing supplied with each WMMB device.
b When adding modular metering modules to old installation, replace metal end closure plate with plastic end closure plate.
c Item is a kit consisting of adapter plate and RX type hub.
d (2) Required per 1-phase meter socket. Residential type ring and ringless - 200 Amp max.
Meter cannot be installed while in use. For use with ECPP cover plate.

| Power Mod™ with Quick System™

12-7
Accessories
Catalog numbers

EUSERC compliant pullbox modules: 1-phase, 3-wire SN, incoming , 120/240V AC max.
Dimensions (inches)a KO
Catalog Ampere Withstand Service Line terminal lugs no. drawing
number rating ratingb feed and size per line and netural Height Width Depth no.

WMMB1400 400 65,000 UG 1 set of 2 studs 37.50 16.69 9.34 P-1

WMMB1800 800 65,000 UG 1 set of 2 studs 45.50 19.44 12.72 P-2

WMMB11200 1200 65,000 UG 3 sets of 2 studs 47.50 25.94 12.72 P-3

EUSERC compliant pullbox modules: 3-phase, 4-wire SN, incoming, 240V AC max.
Dimensions (inches)a KO
Catalog Ampere Withstand Service Line terminal lugs no. drawing
number rating ratingb feed and size per line and netural Height Width Depth no.

WMMB3400 400 65,000 UG 1 set of 2 studs 37.50 16.69 9.34 P-1

WMMB3800 800 65,000 UG 2 set of 2 studs 45.50 25.94 12.72 P-2

WMMB31200 1200 65,000 UG 3 sets of 2 studs 47.50 33.83 12.72 P-3

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
b Devices rated for 22,000. 65,000 rating requires cables to be tied together. Please see instructions with pullbox for details.

W W

P-1 P-2 P-3


WMMB1400 Width Width
WMMB3400 WMMB1800 19.44 WMMB11200 25.94
WMMB3800 25.94 WMMB31200 33.83

s | Power Mod™ with QuickSystem™


12-8
Bus Duct
Catalog numbers
Busway application
Siemens offers a direct busway to modular metering connection.
When six or less disconnects are present a connection can be made
directly to the meter module. If a main is needed Siemens offers
breaker options up to 1200 Amps and switch options up to 800
Amps.

All breaker and switch modules are available with up to 100,000


AIC ratings, are UL listed, and carry a NEMA 1 (indoor) rating.
Common service entrance modules are listed below. Lead time may
apply. See diagrams to the right for spacing considerations.

QuickConnect (QC)

Tap Stacksa
Tap stacks save space by connecting Siemens Sentron Busway
directly to specially designed Siemens circuit breaker, switch or
tapbox modules. Common modules are listed above. Tap stacks
require end-user to purchase additional QuickConnect coupler and
are for indoor use on end-feed applications only.

a Tap stacks are produced with the busway. Contact sales office for more
information.

Common Bus Duct Units: 3-phase, 4-wire SN, incoming, 240V AC max.be
Dimensions (Inches)a
Ampere Mechanism
Catalog number ratingd Height Width Depth type AIC ratingc KO Diagram

MC44BD 400 33.00 15.00 10.44 JXD2 breaker 65,000 BD-1


MC64BD 600 33.00 15.00 10.44 LX06 breaker 65,000 BD-2
MC84BD 800 43.00 20.00 10.44 JX06 breaker 65,000 BD-3
MC104BD 1000 47.00 20.00 10.44 NX06 breaker 65,000 BD-4
MC124BD 1200 47.00 20.00 10.44 NX06 breaker 65,000 BD-5
MS44UBD 400 33.00 15.00 14.94 BD-6
MS64UBD 600 33.00 15.00 14.94 Class T fuse 100,000 BD-7
MS84UBD 800 33.00 15.00 14.94 BD-8

a Dimensions shown are representative of outside box dimensions and do not include allowances for mounting bumps, hubs, or hardware protrusions.
b All devices are build to order. Tap stack and QuickConnect sold separately.
c 100K AIC breaker units available - contact sales office for more information.
d Alternate amperages for breaker modules available. Contact sales office for more information.
e Single phase bus duct devices are available. Contact sales office for more information.

| Power Mod™ with Quick System™

12-9
Bus Duct
Knockout diagrams

BD-1 BD-2
MC44BD MC64BD

BD-3 BD-4
MC84BD MC104BD

s | Power Mod™ with QuickSystem™


12-10
Bus Duct
Knockout diagrams

BD-6
MS44UBD

BD-5 BD-7
MC124BD MS64UBD

BD-8
MS84UBD

| Power Mod™ with Quick System™

12-11
$JSDVJU#SFBLFST
Catalog numbers

10K AIC 22K AIC 42K AIC 65K AIC 100K AIC

Amperage Siemens Murray Siemens Murray Siemens Murray Siemens Murray Siemens Murray

Type QP Type MP-T Type QPH Type MP-HT - - Type HQP Type MP-MT - -

For use in 125 Amp and 225 Amp single phase output WMM, WML, WMT meter stacks

60 Q260 MP260 Q260H MP260KH use HQP use MP-MT Q260HH MP260KM use HQSH/ use HQSH/

70 Q270 MP270 Q270H MP270KH use HQP use MP-MT Q270HH MP270KM use HQSH/ use HQSH/

80 Q280 MP280 Q280H MP280KH use HQP use MP-MT Q280HH MP280KM use HQSH/ use HQSH/

90 Q290 MP290 Q290H MP290KH use HQP use MP-MT Q290HH MP290KM use HQSH/ use HQSH/

100 Q2100 MP2100 Q2100H MP2100KH use HQP use MP-MT Q2100HH MP2100KM use HQSH /
use HQSH/

110 Q2110 MP2110 Q2110H MP2110KH use HQP use MP-MT Q2110HH MP2110KM use HQSH /
use HQSH/

125 Q2125 MP2125 Q2125H MP2125KH use HQP use MP-MT Q2125HH MP2125KM use HQSH /
use HQSH/

For use in 100 Amp, 3- phase output WML meter stacks only

60 Q360 MP360 Q360H MP360KH use HQP use MP-MT Q360HH MP360KM use HQJ2H0 use HQJ2H0

70 Q370 MP370 Q370H MP370KH use HQP use MP-MT Q370HH MP370KM use HQJ2H0 use HQJ2H0

80 Q380 MP380 Q380H MP380KH use HQP use MP-MT Q380HH MP380KM use HQJ2H0 use HQJ2H0

90 Q390 MP390 Q390H MP390KH use HQP use MP-MT Q390HH MP390KM use HQJ2H0 use HQJ2H0

100 Q3100 MP3100 Q3100H MP3100KH use HQP use MP-MT Q3100HH MP3100KM use HQJ2H 0
use HQJ2H0

For use in 225 Amp single phase output WMM, WML, WMT meter stacks

Type QS1 - Type QSH1 - Type QHS1 - Type HQS1 - Type HQSH1 -

100 QS2100 use QS QS2100H use QSH QSH2100 use QHS QS2100HH use HQS HQS2100H use HQSH

125 QS2125 use QS QS2125H use QSH QSH2125 use QHS QS2125HH use HQS HQS2125H use HQSH

150 QS2150 use QS QS2150H use QSH QSH2150 use QHS QS2150HH use HQS HQS2150H use HQSH

200 QS2200 use QS QS2200H use QSH QSH2200 use QHS QS2200HH use HQS HQS2200H use HQSH

225 QS2225 use QS QS2225H use QSH QSH2225 use QHS QS2225HH use HQS HQS2225H use HQSH

For use in 225 Amp 3-phase output WML & WMT meter stacks only

Type QJ2 Type MQ Type QJH2 Type MQH Type QJ2H Type MQL - - Type HQJ2H -

60 QJ23B060 MQJ360 QJH23B060 MQJ360KH QJ23B060H MQJ360KL - - - -

70 QJ23B070 MQJ370 QJH23B070 MQJ370KH QJ23B070H MQJ370KL - - - -

80 QJ23B080 MQJ380 QJH23B080 MQJ380KH QJ23B080H MQJ380KL - - - -

90 QJ23B090 MQJ390 QJH23B090 MQJ390KH QJ23B090H MQJ390KL - - - -

100 QJ23B100 MQJ3100 QJH23B100 MQJ3100KH QJ23B100H MQJ3100KL use HQJ2H use HQJ2H HQJ23B100H use HQJ2H

110 QJ23B110 MQJ3110 QJH23B110 MQJ3110KH QJ23B110H MQJ3110KL use HQJ2H use HQJ2H HQJ23B110H use HQJ2H

125 QJ23B125 MQJ3125 QJH23B125 MQJ3125KH QJ23B125H MQJ3125KL use HQJ2H use HQJ2H HQJ23B125H use HQJ2H

150 QJ23B150 MQJ3150 QJH23B150 MQJ3150KH QJ23B150H MQJ3150KL use HQJ2H use HQJ2H HQJ23B150H use HQJ2H

175 QJ23B175 MQJ3175 QJH23B175 MQJ3175KH QJ23B175H MQJ3175KL use HQJ2H use HQJ2H HQJ23B175H use HQJ2H

200 QJ23B200 MQJ3200 QJH23B200 MQJ3200KH QJ23B200H MQJ3200KL use HQJ2H use HQJ2H HQJ23B200H use HQJ2H

225 QJ23B225 MQJ3225 QJH23B225 MQJ3225KH QJ23B225H MQJ3225KL use HQJ2H use HQJ2H HQJ23B225H use HQJ2H

/ HQSH breakers require the use of 225 Amp WMM meter stacks.
0 HQJ2H breakers require the use of 225 Amp 3-phase WML meter stacks.
1 QS series rates with Murray circuit breakers.

s | Power Mod™ with QuickSystem™



Notes:
Notes:
Murray Load Center Riser Load Center Generator Ready UltimateTM
Load Center

(FUUIFIJHIFTUTUBOEBSE
Siemens is proud to offer one of the highest quality and broadest and most flexible load

center lines in the industry. From single family to multi-family applications, Siemens can

offer a high quality, labor saving load center for your application.

Murray Load Center Generator Ready Load Center


N For those that prefer a high quality N Automatic transfer switch ready
outboard neutral design N Power only critical circuits to minimize
N Exclusive labor saving features generator size
N Indoor/outdoor/main lug/main
Riser Load Center breaker versions
N 125 and 200 Amp models for high
rise applications Siemens Ultimate
N High quality interior – CU bus and metal N Exclusive labor saving features
hook rails N Most flexible load center in the industry
N Available in 16, 24, 30 space versions
Selection and application guide

The information provided in this brochure contains merely


general descriptions or characteristics of performance
Siemens Energy & Automation, Inc. Subject to change without prior notice
Industry Sector
3333 Old Milton Parkway
Alpharetta, GA 30005
Order No.: RPSA-POMOD-0409
Printed in USA
© 2009 Siemens Energy & Automation, Inc.
which in case of actual use do not always apply as described
or which may change as a result of further development
of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the
Power Mod™ with QuickSystem™
1-800-964-4114 terms of contract.

info.sea@siemens.com All product designations may be trademarks or product

www.sea.siemens.com/powermod
names of Siemens AG or supplier companies whose use by Answers for industry.
third parties for their own purposes could violate the rights
of the owners.