An Estimation of Dynamic Properties of Soils from


Block Vibration Tests
V. D. Miglani
Regional Engineering College, India

Follow this and additional works at: http://scholarsmine.mst.edu/icrageesd


Part of the Geotechnical Engineering Commons

Recommended Citation
Miglani, V. D., "An Estimation of Dynamic Properties of Soils from Block Vibration Tests" (1991). International Conferences on Recent
Advances in Geotechnical Earthquake Engineering and Soil Dynamics. 3.
http://scholarsmine.mst.edu/icrageesd/02icrageesd/session01/3

This Article - Conference proceedings is brought to you for free and open access by Scholars' Mine. It has been accepted for inclusion in International
Conferences on Recent Advances in Geotechnical Earthquake Engineering and Soil Dynamics by an authorized administrator of Scholars' Mine. This
work is protected by U. S. Copyright Law. Unauthorized use including reproduction for redistribution requires the permission of the copyright holder.
For more information, please contact scholarsmine@mst.edu.
Proceedings: Second International Conference on Recent Advances in Geotechnical Earthquake Engineering and Soil Dynamics,
March 11-15, 1991, St. Louis, Missouri, Paper No. 1.62

An Estimation of Dynamic Properties of Soils from Block Vibration


Tests
V.D. Miglani
Professor of Civil Engineering, Regional Engineering College,
Kurukshetra, Haryana, India

SYNOPSIS: The paper presents departures that have to be made in the conduct of block vibration
tests from the standard method and in the analysis of test data under unusual conditions. Disturbed
soil condition under an edge of the block leads to occurrence of double peaks in amplitude versus
frequency curves from vertical vibration test. Two methods have been devised to analyse such double
peaks. The first method assumes a correlation between dynamic coefficients. The dynamic properties
can be predicted from non-dimensional curves of correction factor versus ratio of effective
base area. The second method assumes linear variation of coefficient of elastic uniform compression
and its maximum value is estimated from non-dimensional curves of correction factor versus ratio of
frequencies at first and second peaks. Comparison of results of a repeat test under near-ideal
conditions with corrected values of soil parameters confirms the adequacy of the presented methods.

INTRODUCTION These tests are conducted by mounting a mechani-


cal oscillator on top of the block. The oscill-
Several methods of test are available for in- ator is positioned to produce vertical
situ determination of dynamic properties or horizontal excitation. The oscillator
of soils required for analysis and design is driven by a D.C. shunt motor, the speed
of machine foundations. They lead to a of which is varied with a speed control
wide range of variation of values as the strain unit. The vibrations of the block are
levels associated with these tests are widely picked up by a vibration pick-up (velometer
different (Ishihara 1971). Since a properly or accelerometer), signal of which is processed
designed machine foundation introduces a strain and indicated at vibration meter. The line
level of the order of 10- 3 (Silver & Seed,1971), diagram in Fig.1 shows the test arrangement.
Prakash (1975) has strongly advocated the The equipment shown in dotted blocks is
use of block vibration tests as the strain in addition to the equipment required as per IS:
levels introduced and nature of loading Code and has been discussed later.
are similar. Designers depend mainly on
the values of dynamic properties of soils
determined by these tests. : --;H-~~--~--•--- ----,
\ : 1

1 METER ~ ........ ..,


The Indian Standard Code (IS:5249-1977) ~----------~ '
prescribes size of block (1.5 m x 0.75 mx 0.70m
high), s1ze of pit (4.5 m x 2.75 m in plan,
depth =depth of foundation), method of conduct-
ing and method of analysing results of block I
vibration tests. The author has had opportunity '
'
of carrying out block vibration tests for L---

determination of dynamic soil properties


required for design of foundations of a r--- !____ ,
number of turbo-generators/gas turbines of some ' '
1

important power projects of the country and 1 AMMETER c---+--;


discusses in this paper some problems encounter- L.. _ _ _ _ _ _ _ _ _ -l

ed in the conduct of such tests, such as very


high water table submerging the block,disturbance Fig.1 -Line Diagram of Test Equipment
of soil under one edge, failure of the equipment
to cover the resonance, etc. Remedies of such
situations have been suggested.
VERTICAL VIBRATION TEST
BLOCK VIBRATION TEST The mechanical oscillator is mounted centrally
on the block such that it generates vertical
The following vibration tests are conducted harmonic exciting force and the line of action
on the model block foundation: of the excitation passes through the centre
1. Vertical vibration test of gravity of the block. The vibration
pick-up is fixed on top of the block with
2. Horizontal vibration test

183
its sensing axis in the vertical direction.
Amplitudes of vibration are observed on
vibration meter and recorded for different . . . ( 2)
frequencies and at different angles of eccentri-
city of the oscillator. Amplitude versus
frequency curves at different eccentricities
are plotted. A typical and normally obtained where cu and cu correspond to base areas A &
1 2 1
curve is shown in Fig.2. A2 respectively. Such a relationship is valid
120
for small areas upto about 10 sq m. For base area
ECCENTRICITY OF OSCILLATOR ~f~~!~r c~~~~a~~ C~a~ka~h~ 9 ~~~~e of Cu remains
_,....,..... 104°
110

100 /:\ TABLE-1


Resonant Frequencies and Values of

l/ i:
\
Cu from Vertical Vibration Test
90 1\
I

eo
I
I

I
\ \
ANGLE OF
ECCENTRICITY
OF
RESONANT
FREQUENCY
lnz
DYNAMIC
FORCE
(kg)
Cu
(kg/cm 3)
Cu
(kg/ cm 11

I A 21.125ml A :10 mz
I
~
OSCILLATOR (Cps)
I
70

I
1 2 3
I 4 5
I
60 I 68° 36·7 160 9-10 3.05

I
I
I 104° 35·8 215
UJ
I 8-66 2-90
> sa
140° 34.9
,_ I 244 8·23 2-76
< I
__,
UJ
a:
a I I

I
I
I
I
a
/ I
I
I

v
a / HORIZONTAL VIBRATION TEST
I RESONANT FREQ.UENCY

a I !/ 40 epa
The oscillator is positioned and mounted on top
32 34 36 3e 40 42 46 of the block such that it produces horizontal
harmonic excitation parallel to longitudinal
FREQUENCY (cps)
axis of the block. The vibration pick-up
is mounted with its axis horizontal and parallel
Fig. 2- A Typical Amplitude v/s Frequencyfrom to the excitation. Horizontal amplitudes
Vertical Vibration Test of vibration are recorded for different
frequencies and at different settings of
co-efficient of elastic uniform compression eccentricity of oscillator. Amplitude versus
is obtained by using the following frequency curves from horizontal vibration test
for different eccentricities are plotted,
expression:
The horizontal excitation at top of the block
causes the block to vibrate in coupled trans-
lation along the longitudinal axis and rocking
••• ( 1) motion about transverse axis of the block.
A The system has two degrees of freedom and
hence two natural frequencies.
where
m Mass of the block plus that of the motor, A method using three acceleration pick-ups
oscillator and other mountings to determine whether the resonant frequency
obtained corresponds to first or second
A Base area of the block mode of vibration is given in the code (IS:5249-
150 X 75 Sq Cm 1977). Another way to do this using one
Resonant frequency in the vertical mode pick-up is to observe amplitudes carefully
fnz for different frequencies of the oscillator
of vibration.
varying from zero till first resonance is
A typical set of calc:nlations for Cu are shown in observed. This may be called method of
Table-1. The values of Cu so calculated corres- 'frequency scanning'. It is experience
of the author that only first mode peak
pond to the base area of the model block. without exception is obtained. After determin-
The values of C corresponding to actual ing the mode of vibration, the co-efficient
foundation area uare calculated from the of elastic uniform shear (Ct) is calculated
relationship: using the expression:

184
PROBLEMS OF BLOCK VIBRATION TESTS
. . . ( 3) In most cases, conduct of block vibration tests
or analysis of test results does not pose
any problem. However, on account of some
unusual field conditions, conduct of the
where test as per the standard method may become
y Mm/Mmo difficult if not impossible. In some situations,
Resonant frequency obtained from the test observations especially of the vertical
fnx vibration test may show no clear resonant
horizontal vibration test Both these
peak or may show two peaks.
A A/m situations being abnormal are discussed.
0

M
m
Mass moment of inertia (m m i)ofblock CLEAR RESONANT PEAK NOT AVAILABLE IN VERT !CAL
with mountings about the horizontal VIBRATION TEST-
axis passing through centre of gravity
of the block and perpendicular to the Such a condition arises when the equipment
direction of vibrations for generation of harmonic excitation is
M m m i of block and mountings about the unable to cope up with the power requirements
mo horizontal axis passing through centre of the test especially near resonance.
of base area of the block and perpend- D.C. supply and speed control unit is always
icular to the direction of vibration equipped with tripping arrangement at limiting
currents for safety reasons. High resonant
I Second moment of area of base of the frequencies of the soil-block system, low
block about the horizontal axis pass- damping factor associated with the system,
ing through the centre of gravity of low voltage etc. individually or severally
the area and perpendicular to the may cause limiting current tripping before
direction of vibration. crossing the resonant peak. A typical amplitude
versus frequency curve from vertical vibration
Use the +ve sign for second mode of vibration test under such a condition is shown in Fig.3.
and -ve sign for the first mode.
For the size of the standard block used ECCENTRICITY OF OSCILLATOR
in the test and first resonant frequency eo•
equation (3) reduces to:
70

f
2 I 125 ••• ( 4) 1fT~-
nx I
60
/ I
The values of Ct from equation ( 4) correspond

I
I
to base area of the block. The values of I
I
Ct corresponding to actual foundation area
up to 10 Sq m may be obtained using the 50
l
I
relation ship:
If I
I
:
40

I
I
••• ( 5) I
I

v
I
0
I
where ct and ct correspond to areas A1 and A2 I
1 2
respectively. A typical amplitude versus I
frequency curve from horizontal vibration test I
0
and table of calculations of Ct being similar in

/
I
nature to those of vertical mode of vibration I
have not been shown in this paper. I
I
0
/ RESONANT 1
FREQUENCY~~ 56-7 cps
COFFICIENTS OF ELASTIC NON-UNIFORM COMPRESSION (EXTRA POLATEOJ 1;
(C~) AND ELASTIC NON-UNIFORM SHEAR (C~ )
415 48 so 52 54 56 58
In the absence of direct field tests as
OBSERVED FREQUENCY IN cps
at present, the IS:Code prescribes the following
relationship for determination of these
coefficients: Fig. 3 - A Partial Peak Amplitude v/s Frequency
Curve from Vertical Vibration Test
••• ( 6 ) (Ref.: Miglani 1987)
••• ( 7)

185
The curve can be extrapolated to obtain when angle of phase " 76°. Using the G!- r curve
the resonant peak by using curve fitting for ~ = 0. 12, at G! = 7 6 ° , r' = 0. 9 7. Therefore
technique. However, the result may suffer from resonant frequency 46/0.97 47.4cps.
errors to an extent of 10-20%. Two better Similarly resonant frequency may be obtained
methods have been tried and are suggested below. assuming other possible values of~ (between
0.08 & 0.16). Thus resonant frequency works
(i) By Measuring Phase Difference between out to be between 47.9 and 46.9 cps. It
Force and Displacement Components: This can be can be clearly inferred that using G! -r curve
done by fixing a force transducer to the f o r " = 0.12 gives a fairly accurate (error
mechanical oscillator. The transducer can work as being less than 1%) value of resonant frequency.
techogenerator as well and using a phase meterto The illustration is an extreme case and
read angle of phase between force and displace- in other cases, the errors associated in
ment vectors (See Fig. 1). The output from the extrapolating resonance are much smaller.
force transducer may have to be attenuated
to match with that of the vibration pick-up. (ii) By Measuring Input Power: This can
It is well known that at resonance, phase angle be done by using an A.C. ammeter or watt-meter
(G!) between force and displacement of a as shown in Fig.l. This method is not as
sing! e degree of freedom system is 90°. good as the first method but can be used
Plot of phase angle (G!) versus frequency ratio with advantage in the absence of a force
1
r 1 (ratio of oscillator frequency to natural transducer. The concept can be understood
frequency of the system) can be seen in from the following derivation:
any standard test book on theory of vibrations,
e.g., by Thomson(1958).
Work done by exciting force
Damping factor 1 ~ 1 associated with block-soil per cycle ="'P X sinG! (Grover 1972)
system has been observed 0 0
to 1i e between
0.08 and 0.16. For these values of J it may be
observed that when frequency ratio 1 r 1 varies where P Exciting force amplitude
0
from zero to 0.9, phase angle 1
01 varies X Amplitude of vibration
zero to 37°( '1;=0.08), 43°()=0.10), 49°( 'S =0.12) 0
Phase angle between P & X
and 57°() =0.16). Experience of using phase 0 0
meter has shown that the electrical system Therefore,
very rarely trips for phase angles below
80°. An enlarged picture of plots of phase
angle 1
G!' versus frequency ratio 1
r 1
greater work done per sec;ond (W) = 7t f P X sin G!
0 0
than 0.96 & upto 1.00 for ) =0.08, 0.10,
0. 12. 0.14 & 0.16 are shown in Fig.4. where f = Oscillator frequency in cps.

90 The expression can be reduced to:

88 constant
w ••• ( 8 )
lll
IJ.J
IJ.J 86
0::
t!l where r = frequency ratio
IJ.J
0
84 f/fnz
z
~ P 1 o t s of 1 W1 versus 1 r 1 for different va 1 u e s
IJ.J 82 of ~ are shown in Fig. 5, which explains that
...J
t!l power requirement for running the test near
z resonance is relatively much higher. In
<t
80 view of the earlier statement in respect
IJ.J
lll of phase angle at the time of tripping and
<t discussion , resonant frequency can be estimated
I
a. 78 to be within 7 percent higher than the frequency
at which the electrical system trips. The
purpose of using ammeter is to ensure that
there has been general steep rise in power
0·9 7 0 98 0 99 1.oo requirement and that the system has not
tripped on account of some other reason.
FREQUENCY RATIO ( rl
The values of
thus Cu
determined
Fig.4 - Phase Angle versus Frequency ratio 1 could be verified from values of Ct as mentioned
r 1
later.
Plots near Resonance.

A fairly good estimate of resonant frequency


can be made by assuming ~ =0.12 and reading
1
r 1 against phase angle 1 G! 1 when the system
trips. For example, take an extreme case
of systemtripping at oscillator frequency= 46 cps

186
1

18 Though rare, two peaks (in place of normal! y


r=.075 one peak) have been seen sometimes in amplitude
'\
versus frequency plots from vertical vibration
16 \ tests. Such dual peaks have been observed
I \ at three sites for turbogenerators of different
I \ I
stages of a prest igeous
the country and also at
power
a
project
site for heavy
of
14

,_
i
I .--,\\
t=-10\
machinery on desert
is shown in Fig.6 •
soil. A typical plot

z
LU
12
,, On account of high water table submerging

~\
I I
:l: even the block, loose soil etc., a departure
LU
0:: from standard pit had to be made. For example,
::J
10 I' at the three sites mentioned above, the
0 \;,
vibration tests were conducted on standard
LU
0:: Jf '!j
I \ blocks in wells of internal diameter 3.5 m and at
8 depths of the order of 4.5 m for retaining

,f
0::

\~
LU I the soil. To keep the water table low,
3: two additional wells of 2 m internal dia
0
D.. \\ I'.. adjacent to the main well were provided

! \'~
LU
2:
,_
~
I" . . . . .
....... ::-- and water from them pumped out.
is shown in Fig.7.
The arrangement

-----
...J 4
LU ........ MAIN WELL
0::

2.
j. SIDE WELL SIDE WELL

-;~~
0
0·6
~
Q.7 0·6 0·9 1·0 1·1 1·2 1.3 ~
FREQUENCY RAT 10
Fig.5 -Power Requirement versus Frequency Ratio
Curves
f I fnz ( r l
~
SHADED AREA ASSUMED ESTIMATED DIRECTION
AS EFFECTIVE BASE AREA OF SUBSOIL WATER FLOW
TWO RESONANT PEAKS OBSERVED IN VERTICAL
VIBRATION TEST -
Fig.7 -Plan of Test Arrangement

ECCENTRICITY CF One such case history has been reported


OSCILLATOR-140°
by the author (Miglani 1988a) wherein pumping
eo out of water from side wells was not enough
and pumping from within the main well also
had to be resorted to to lower the water
70 level to at least below the top surface
of the block. The point chosen for this
purpose was on the longer axis of the block
LU
60 near the well boundary and as far as possible
0
,_
::J
{:\ near the
with a
surface of water.
view to cause least
This was done
distrubance of

/v
/I'). soil. Later at a different site for a turbo-
...J 50
I-t
\ \ -
I
D..
I I
generator, pumping from within the main
:l: I well was not resorted however, subsurface
~ I
I I
40
I flow of water was capable enough to cause

I \ (
LU I I distrubance of soil near one edge (Miglani 1988b).
> I I
,_ I I Deviation from non-uniform reaction causes
I I
~ the block, subjected to central vertical
30
...J I
~ I excitation, to vibrate in two modes ( &

Iv
LU I I
0:: I
I
I
hence two resonant peaks);
I
I
20 (i) rocking about a horizontal axispassing
I I through the centre of the base area, &
I I
I I
I I (ii) vertical
10 I

I
I RESONANT I
It can be easily worked out that the first
rnz, : FRECUE NCY !fnzzl36. 0 :cps
resonant peak corresponds to the rocking mode and
""-: --.........I
the second corresponds to the vertical mode
16 20 24 28 32 36 40 44 of vibration. Therefore, to estimate the
FREQUENCY IN cps correct value of Cu, only the second resonant
frequency is considered. The values of
Fig. 6 - A Double Peak Amplitude v/s Frequency Cu obtained by using equation (1) need corrections.
Curve from Horizontal Vibration Test

187
It has been observed and may be noted that
the effect of disturbance of soil near one
short edge of block on resonant frequency
in horizontal vibration test is highly
pronounced. The values of Ct by using equation
(3) or (4) drop more steeply as compared
to the values of Cu.
Two methods have been devised by the author
to estimate correction fact or s applied to
the values of soi 1 parameters obtained in
the tests.

First Method
a:
This method assumes a correlation between 0
1-
the dynamic coefficients Cu and Ct. u
Values <
u.
of Ct of a particular soil may be found z
to lie between half to two third values !:!
1-
of Cu, more commonly being close to half u
LIJ
of Cu. The method also assumes that Cu a:
a:
0
and Ct are u
constant over a certain base
area away from the di strubed edge • Ratio
of effective base area to actual base area PER CENT BASE ARE A
(p) may be obtained by drawing curves between Fig.8 - Ratio of Frequencies (fnz /fnxl
2 and
1
P 1 and ratio fnz /fnx observed from vertical Correction Factor v/s Effective
2 Base
vibration test and horizontal vibration Area Curves
test as follows:
(a) From amplitude versus frequency curves
Equations (1) & (3) give ratio of fnz 2 & of vertical and horizontal vibration
fnx which can be expressed as tests, determine the ratio: fnz /fnx'
2
(b) Use curve fnz 2 /fnx versus
2A Y determine the val'ue 1 p 1 against
0
.. • ( 9) value obtained in step (a) •
Ct (D-E)
(c) Use correction factor versus 1
p 1 and
determine the correction factor against
where D 1
p 1 obtained in step (b l.
(d) Determine Cu from equation (1) using
- 4A
0
fnz 2 • Multiply this with the correction
For the standard block, equation (9) reduces to factor obtained in step (c). This
is the corrected value of Cu.
(e) Ct is determined by multiplying Cu with 0.5 •

.. • ( 10)
Illustration and adequacy of the method
have already been reported (Miglani 19 8 8a l
where d 121.1 + 223.9 p 2
Second Method
This method assumes linear variation of
Cu and uses the first and second resonant
Using equation (10), ratio fnz /fnx versus 1
P1 peaks of the amplitude versus frequency
2
curve has been drawn in Fig.8, using Cu/Ct = 2. curves of the vertical vibration test.
However, full base area is assumed to participate.
From the two resonant frequencies, with
Correction factor versus effective base these assumptions, the values of Cu across
area parameter 1 p 1 curve in Fig. 8 has been
derived using equation (2). Thus, the the length of the base can be computed:
procedure to predict the correct values
of Cu and Ct for base area of the block
4n2 f 2 m
can be summerised as follows: nz2
±------- . . . (11)
A 1

188
The negative sign is of no consequence for TABLE-2
maximum value of C • The correction fact or Comparison of Uncorrected, Corrected values
is to be with n\'spect to the first part of Dynamic Coefficients and Values from
of the expression for Cu in this equation. Repeat Test
Therefore,

M Af 2 PREDICTED VALUES
nz1 mo DYNAMIC UNCORRECTED 1
VALUES FROM
kg/ cm
Correction factor=-- ' - - - - + 1 ... ( 12) COEFFICIENT VALUES
REPEAT TEST
f 2 m I METHOD 1 METHOD 2 kg I em'
nz2
I
For the standard block, correction fact or
Cu 5.96-6-49 8.95-9.83 11·32-12-32
I a.1s- a. 75
versus ratio of frequencies fn 22 /fnz 1 curve Ct 1-15-1.31 1..47- 4.92 5·66- 6-16 4-95- 6 .so
is shown in Fig.9.
2- 4

It can be seen that the second method gives


2-2
upper bound values of Cu on account of extreme

2-0
1\\ assumption and the first method gives fairly
good values of the coefficient.
values of ct lie between those
The actual
determined

1-8
~ by the two methods. Importance of the two
methods can be easily gauged from the comparison
~
cz:
,_
0 of the corrected and un-corrected values
of dynamic coefficients, especially Ct.
~
u
<{
u. 1-6
z
2,_ """ ~ r---...
u
w
1.4 --... CONCLUSIONS
cz:
cz: t--- 1--- 1. Certain field conditions such as high
0
u 1-2
t--- water table, loose soil etc. necessitate
departure from the standard method.

1-0 2. Introduction of phase meter between force


1-2 1-4 H 1·8 2 ·0 2-2 2-4 2-8 and vibration transducers or A.C. ammeter
can greatly facilitate extrapolating
RATIO OF FREQUENCIES fnz2f fnz 1 resonant peaks, should the electric system
be unable to cope up with power requirement
near resonance in vertical vibration
Fig.9 - Correction Factor v/s Ratio of test.
Frequencies fn 22 /fn 21 Curve
3. The two methods devised to analyse the
double peaks in amplitude-frequency curves
To use this method: from vertical vibration test have been
found quite effective. It is suggested
(a) From vertical vibration test amplitude that, should such double peaks occur
versus frequency curves obtain fn 21 • in the amplitude frequency curves,
fnz and their ratio fn 22 /fnz 1 • values of Cu and Ct be determined by
2
(1 ) both the methods and judicious values
(b) Calculate Cu from equation
be adopted.
using f nz 2 •
(c) Read correction factor from curve
in Fig.9 against ratio fn 22 /fnz 1 REFERENCES:
obtained in step(a) and apply
it to value of Cu obtained in Barkan, D.D. (1962), "Dynamics of Bases
step(b). and Foundations", McGraw-Hi 11 Book
Co. Inc., New York.
As already mentioned, adequacy of the first
method has been tested through a repeat Grover, G.K. (1972), "Mechanical Vibrations",
test under near-ideal conditions. A comparison Nem Chand & Bros., Roorkee (U.P.).
of values of Cu determined by the two methods
IS: 5249-1977, "Indian Standard Method of
and by the repeat test is shown in Tabl e-2. Test for Determination of Dynamic Properties
of Soil (First Revision)", Indian Standards
Institution, New Delhi.

189
Ishihara, K.(1971), "Factors Affecting Dynamic
Properties of Soils", Proceedings:
Fourth Asian Regional Conference on
Soil Mechanics and Foundation Engineering,
Bangkok, Vol.2, August.

Miglani, V.D. (1987), "Report on Dynamic


Tests of Soil Conducted at Thermal
Power Station, Jalkheri" No.C/VDM/ 2,
Regional Engineering College, Kurukshetra.

Miglani, V.D. (1988a), "In-situ Determination


of Dynamic Properties of Soil for Foundation
of a Turbogenerator", Proceedings:
Second International Conference on
Case Histories in Geotechnical Engineering,
St.Louis, MO., June, Paper No.4.36.

Miglani, V.D. (1988b), "Report on Dynamic


Tests of Soil at Sites of Turbogenerators,
Stage 3 at RTP, Ropar., "No.VDM/8,
Regional Engineering Coli ege ,Kurukshet ra.

Prakash, Shamsher (1975), "Analysis and


Design of Vibrating footings", SOIL
MECHANICS Recent developments,
Proceedings of the General Session
of the Symposi urn, University of New
South Wales, Sydney.

Silver, M.L. and H.B.Seed (1971), "Deformation


Characteristics of soils under Cyclic
Loading", Journal of Soi 1 Mechanics
and Foundation Division, ASCE Vol.97,
SMS August, 1971.

Thomson, W. T., (1958), "Mechanical Vibrations"


Prentice Hall Inc., Englewood Cliffs,
N• J •

190