Вы находитесь на странице: 1из 14

Technical Application Papers

C.4 Filters L-C functioning as capacitors one decreases as the harmonic order rises and besides,
Take into consideration a branch of a passive series filter for higher frequencies, the compensation bank presents
Annex C

L-C resonant at an established frequency and represent itself to the network on the whole as an inductance, thus
graphically, as shown below, the capacitive and inductive eliminating the possibility of parallel resonance with the
reactance as a function of the frequency. network inductance.
Application example
X XI
Assume that a totally controlled three-phase Graetz
Xc
static rectifier has to be supplied by a network at 50 Hz
with a short-circuit power sufficiently high to make it
possible to disregard the distortion of the set of three
voltages caused by the distorted current injected into
the network by the rectifier.
fr
Figura C.2

Id
IL1
f L1
IL2

LOAD
As shown in the graph, it is possible to observe that below L2 Vd
IL3
1 L3
the resonance frequency4 f r = the capacitive
2⋅ π ⋅ L ⋅ C
reactance prevails and consequently also the generated
reactive power prevails over the drawn one, that is:

1
Q = Q L - QC = w ⋅ L ⋅ I 2 − ⋅ I2 < 0 [C.19]
w⋅C
The current in each phase of the line (assuming a high
Therefore, by using passive filters for harmonic filtering
inductance value on the d.c. side) has a rectangular
at resonance frequencies, power factor correction at
lower frequencies is obtained and this effect shall be waveform with the fundamental harmonic frequency
taken into consideration for the dimensioning of the ca- equal to that of the sinusoidal voltage. The development
pacitor banks of the filters themselves. In other words, in Fourier series of such waveform gives only harmonics6
when dimensioning filters L-C it is possible to choose of order k = 6n ± 1 (n = 0,1,2…), whose theoretical
simultaneously such inductance and capacitance values, amplitude is inversely proportional to the harmonic of
so that the sum of the reactive power generated at the order k7, that is:
fundamental harmonic by all the filters installed corre- I
Ik = 1 [C.20]
sponds to the reactive power required to make the total k
displacement factor seen from the upstream network where I1 is the amplitude of the fundamental harmonic
reach the value of 0.9. (in the case under examination equal to 50 Hz). As, by
initial hypothesis, the voltage waveform is not subject
At frequencies higher than the resonance one, the induc- to distortion, its development in series is reduced to the
tive effect prevails, but the amplitude of the harmonics fundamental harmonic only and consequently the active
present in the distorted current waveform, in common
5
This means that, as shown in the figure, the silicon valves are all tyristors, which can be
plant engineering applications, decreases as the fre- operated with a delay (phase control angle α); in this way it is possible to change the value
quency rises; consequently, the reactive power drawn by of the rectified voltage Vd and the power values P according to the following relations:

the filter at a frequency value higher than the resonance Vd = Vdo · cosa P = Pdo · cosa
where Vdo and Pdo are respectively the average value of the rectified voltage and the power
on the d.c. side with no phase control (a = 0).

4
The resonance frequency is that defined frequency value for which the inductive and The effect of the phase control angle α on the a.c. side is causing a phase displacement ϕ
capacitive reactances coincide (see Chapter 8). In a formula: between voltage and current, which implies absorption of reactive power Q. In particular,
1 1 the relation a = j is valid.
XL = Xc 2⋅ π ⋅ f ⋅ L = 4 ⋅ π 2⋅ f 2 ⋅ L ⋅ C =1 f =
2 ⋅ π ⋅ f⋅ C 2 ⋅ π ⋅ L⋅C 6
This depends on the typology of the bridge rectifier (single-phase, three-phase,
If the inductance and the capacitance are in series, the total impedance shall tend to zero hexa-phase, etc.) and on the type of control (non-control, semi-control or hybrid, total
and consequently a short-circuit shall occur for the current harmonic having the same control).
frequency as the resonance frequency. Analogously, if the inductance and the capacitance
are in parallel, the total impedance shall theoretically tend to infinity with a consequent 7
In fact, non-instantaneous switching and a phase control angle different from 0° reduce
overvoltage at the ends. the amplitude of the harmonics with respect to the theoretical value.

48 Power factor correction and harmonic filtering in electrical plants


and reactive powers absorbed by the rectifier (assumed By developing in Fourier series the distorted waveform
without losses), calculated in compliance with [C.10], of the current on the a.c. side, according to [C.20], the

Annex C
are equal to8: following values for the harmonic amplitudes are obtained
∞ [C.21] (the harmonics up to the 25th have been considered):
P = 3⋅∑Vk ⋅ I k ⋅ cosϕ k = 3 ⋅V1 ⋅ I1 ⋅ cosϕ1 =P1 = Vdo⋅ I d ⋅ cosα = Pd
k=1
Table C.1

[C.22]
Q = 3⋅∑Vk ⋅ I k ⋅ sinϕ k = 3 ⋅V1 ⋅ I1 ⋅ sinϕ1 = 3 ⋅V1 ⋅ I1 ⋅ sinα = Q1 k Ik [A] Ik/I1 %
k=1
1 202 100
where: 5 40 20
Vdo is the voltage value on the d.c. side;
7 29 14
Id is the current value on the d.c. side.
11 18 9
The apparent power which corresponds to these powers is:
13 15 8
2 2
A= P1 + Q1 = A 1 [C.23]
17 12 6

19 11 5
Since the total apparent power seen from the supply
network is: 23 9 4

∞ 25 8 4
S = 3⋅ V ⋅ I = 3 ⋅ V1 ⋅ ∑ I k2
2
[C.24]
k=1

a distortion power due to the distorted current waveform Therefore, in the upstream network, in case of absence
is present: of harmonic filters, a current would flow with a total
r.m.s. value equal to the square root of the sum of the
D = S 2 - A 12 [C.25]
squares of the r.m.s. values of the harmonics given in
the previous Table:
Assuming that the bridge rectifier has a rated power Pdo, 25

delivered on the d.c. side, equal to 140 kW, when it is I= ∑I 2


k = 210 A
supplied by a network with non-distorted rated voltage k=1

and assuming that the switching is instantaneous and


the phase control angle α is such that cosj = cosa = 0.8,
the following values for the powers on the a.c. side are with a total apparent power:
obtained:
S = 3 ⋅ U n ⋅ I = 3 ⋅ 400 ⋅ 210 =146 kVA
P = Pd = Pdo⋅ cos α = 140 ⋅ 0.8 = 112 kW

from which a first harmonic current: and a total harmonic distortion equal to:

P 112⋅10 3 25
I1 = = = 202 A
3⋅ U n ⋅cosϕ 3 ⋅ 400 ⋅ 0.8 ∑I 2
k
k= 5
THD = = 29%
I1
and consequently a reactive and apparent power : 9

Q = 3 ⋅ U n ⋅ I1 ⋅ sinϕ = 3 ⋅ 400 ⋅ 202 ⋅ 0.6 = 84 kvar As a consequence, there would be a distortion factor
A
A = P 2 + Q2 = 140 kVA cosy= = 0.96 and, seen from the upstream network,
S
a phase displacement factor cosf = cosj · cosy =
= 0.8 · 0.96 = 0.77.
8
Since there are no harmonics of higher order in the voltage, all the addends in the sum
are equal to zero for k>1. Moreover, as the displacement angle ϕ and the phase control The target is obtaining a total phase displacement factor
angle α (in the instant when the tyristors are required to operate) coincide, it can be
noticed how the absorption of reactive power from the rectifier rises by increasing the
equal to cosf'= 0.9 and to this purpose it is assumed to
phase control angle. size and insert in parallel some filters L-C for the 5th-7th-
9
cosj = 0.8 j = 36.9° sinj = 0.6

Power factor correction and harmonic filtering in electrical plants 49


Technical Application Papers

11th and 13th harmonic as shown in the following figure. which is about 12% lower than the initial value of I1, to
which the current values of the non-filtered harmonics
Annex C

Figura C.3 correspond:


Id
II I
LOAD Table C.3
I13 I11 I7 I5
k Ik [A] Ik/I’1 %
17 10 6

L13 L11 L7 L5 19 9 5

C13 C11 C7 C5 23 8 4
25 7 4

Therefore the final value of cosf' shall exceed 0.9. As it can be noticed when comparing the absolute values of
Assuming to set this value at 0.91, the obtained reactive the r.m.s. values in the Tables C.1 and C.3, the power factor
power compensation is€equal to: correction at 50 Hz determines a reduction in the r.m.s. value
of the first harmonic of current, which affects the reduction
Qc=P⋅(tgϕ - tgϕ')=112⋅ (tg(cos- 1(0.8)- tg (cos- 1(0.91)))= 33 kvar I'
of the non-filtered harmonics (since I k '= 1 ).
from which the final reactive power Q' after power factor k
This also involves a further reduction in the total current
correction: seen from the upstream network becoming equal to
Q'=Q -Q c = 84 €- 33 = 51 kvar I' = 178 A (16% lower than the total initial current I) with
a total apparent power S':
Proceeding by attempts and setting some inductance

values for the harmonics to be filtered, the following S' = 3 ⋅ U n ⋅ I'= 3 ⋅ 400 ⋅178 = 124 kVA
capacitance values causing series resonance are ob- €
tained: The distortion factor passes from 0.96 to:
1
Ck =
(2πf ) 2 ⋅ L k A' 123
cosy'= = = 0.99
Table C.2 S' 124
k f [Hz] Lk [mH] Ck [μF]
and the total displacement factor results:
5 250 1 406
7 350 2 103 cosf'= cosϕ'⋅ cosy' = 0.91⋅ 0.99 = 0.906
11 550 1 84
13 650 1 6 Thus the appointed goal has been reached; otherwise,
the set value of cosj should have been increased and the
The reactive power at 50 Hz supplied, for example, by
previous procedure should have been repeated.
the filter L-C resonant at the 5th harmonic is calculated
The total harmonic distortion ratio decreases to THD’= 9.9%
as follows:
Un (lower than the wished 10%).
I1,5 =
1
3 ⋅ 2π50⋅ L5 - To conclude, thanks to this example, it has been possible
2π50⋅ C5
to notice how in distorted steady-state, if the inductances
1 and the capacitances of the passive filters are suitably
Q1,5 = 3⋅ - 2π50⋅ L5 ⋅ I1,5
2
sized, it is possible to obtain two further effects in addition
2π 50 ⋅C5
to harmonic filtering for which the filters are used:
Analogously, the contributions of the other harmonics
• common power factor correction at 50 Hz since at the
are calculated. The sum of the compensation reactive
fundamental frequency the capacitive effect prevails
powers at 50 Hz is very close to the predefined one (with
over the inductive effect and consequently the gener-
the inductance and capacitance values given in Table
ated reactive power over the absorbed one;
C.2); considering the value of apparent power A' (at the
same value of absorbed active power P): • by reducing, through the power factor correction, the
r.m.s. value of the fundamental harmonic of the current,
A'= P 2 + Q' 2 =123 kVA € consequently also the r.m.s. values of the non-filtered
the r.m.s. value of the first harmonic current becomes harmonics diminish; therefore a further reduction of
equal to: the total current flowing through the network and of
A' 123⋅103 the total THD is obtained, which means a reduction in
I1 '= = =177 A
3 ⋅ Un 3 ⋅ 400 the distortion of the waveform of the current itself.

50 Power factor correction and harmonic filtering in electrical plants


Annex D
Voltages and currents upon switching and from the first equation of those in [D.5] the capacitor
voltage in steady-state is obtained:
discharging of capacitors

Annex D
1 2⋅ I

t
vc '= ⋅ i'dt = - ⋅ cos(wt +y + ϕ) [D.7]
D.1 Switching of capacitor banks C 0
w⋅C
Taking into consideration the series single-phase equiva-
For the voltage vcıı it results2:
lent circuit of a capacitance and the resistance of the t

wiring as shown in the following diagram: vc'' =Vc'' ⋅ e τ [D.8]

Figure D.1
i imposing as initial conditions null voltage on the capaci-
tor for t=0:

2⋅ I
V Vc vc0 = vc 0 '+vc0 ''= - ⋅ cos(y + ϕ) + Vc ''= 0 [D.9]
w⋅C
C
from which:
2⋅ I
R Vc ''= ⋅ cos( y + ϕ) [D.10]
w⋅C
with: and therefore:
t
v = 2 ⋅ V fn ⋅ sen (wt +y) [D.1] 2⋅ I -
vc = ⋅ cos(y + ϕ) ⋅ e τ - cos(wt +y + ϕ) [D.11]
w⋅C
the following equation is valid:
Analogously, for the current too, we have the sum of the
1
∫ 0 idt = 2 ⋅ V fn ⋅ sen(wt +y)
t
R⋅ i + ⋅ [D.2] steady-state and transient components:
C
i = i'+ i'' [D.12]

With the capacitor voltage Vc as unknown quantity and


The steady-state component is given by [D.6], whereas
dv
with i = i c = C ⋅ c it results: the transient component results by deriving [D.8] with
dt respect to time, that is:
dvc [D.13]
R⋅ C ⋅ + vc = 2 ⋅ V fn ⋅ sen(wt +y) [D.3] t
dt dv '' 2⋅I - 1
i''= C ⋅ c = C ⋅ ⋅ cos(y + ϕ) ⋅ e τ ⋅ - =
dt w⋅C R⋅ C
t
The solution of the first order linear differential equation 2⋅ I -
- ⋅ cos( y + ϕ) ⋅ e τ
is the sum of two components: the steady-state solution w ⋅ R⋅ C
vcı (particular integral) and a unidirectional component [D.14]
from which:
with damped exponential function vcıı (general integral), t
1 -
that is: i = 2⋅ I ⋅ - ⋅ cos(y + ϕ) ⋅ e τ + sen(wt +y + ϕ)
w ⋅ R⋅ C
vc = v'c + v''c [D.4]
The unidirectional component becomes equal to 0 when:
from which:
[D.5] cos(y + ϕ) = 0 y = 90°- ϕ
dv' dv'' that is when the insertion angle of the voltage is
R⋅ C ⋅ c + v'c = 2 ⋅ V fn ⋅ sen (wt +y) R⋅ C ⋅ c + vc'' = 0
dt dt complementary to the phase displacement angle
between voltage and current under steady-state
conditions. In this case there are not current peaks and
Since in steady-state the current flowing through the
switching overvoltages. On the contrary, if:
circuit is the following1:
i'= 2 ⋅ I ⋅ sen (w t +y + ϕ) [D.6] cos(y + ϕ) = 1 y=-ϕ

there shall be the maximum value of the unidirectional


1
component with the maximum peak of current and the
I=
V fn highest overvoltage.
2
1
R2 +
wC 2
It is defined τ the time constant of the system under consideration equal to τ = RC

Power factor correction and harmonic filtering in electrical plants 51


Technical Application Papers

Example D.2 Discharge of capacitors


Let us suppose we want to switch a 50 kvar three-phase Take into consideration a charged capacitor bank having
Annex D

bank of star-connected capacitors supplied by a network an initial voltage Vc0 and connected to a discharge resistor
with infinite power at 400 V @ 50 Hz and by a three-pole R as shown in the following diagram:
PVC cable, 10 m long. The capacitance per phase results Figure D.2 i
equal to:
2
Un Qc 50 ⋅10 3
Qc = 3⋅ w ⋅ C ⋅ C= = =1 mF Vc
3 w ⋅ U n2 314 ⋅ 400 2 C

The r.m.s. value of the rated current absorbed in steady-


R
state is:
In the absence of an applied voltage, it is possible to
Qc 5 ⋅103
In = = = 72 A write, as a function of the capacitor voltage:
3 ⋅ Un 3 ⋅ 400
dv
R⋅ C ⋅ c + vc = 0 [D.15]
dt
With such a rated current, a 16 mm2 cable installed on a the solution of which gives:
t
tray and having a total resistance per phase equal to 15 mΩ -
vc = Vc0 ⋅ e τ [D.16]
is chosen. As a consequence, the time constant τ of the
circuit RC is 15 μs, whereas the phase displacement angle which, in the worst case, becomes:
t
between current and voltage results: vc = 2 ⋅ Vn ⋅ e τ
-
[D.17]

1 1 dv
ϕ = tg- 1 = tg- 1 = 89.73° Moreover, knowing that i = i c = C c , the current results
w ⋅ R⋅ C 314⋅15⋅10- 3 ⋅10- 3 to be: dt
(in advance) t
Vc0 - τ [D.18]
i =- ⋅e
Replacing I (negligible error) in [D.13] with the values of R
resistance, capacitance and In, it results that the maxi-
Inserting in [D.17], in compliance with the prescriptions
mum peak of the inrush current (assuming y = -j) is about of the Standard IEC 60831-1, t=180 s and vc=75 V and
22 kA, that is 300 times the rated current of the bank, solving it with respect to R, the maximum value of the
as shown in the following diagram. In plant engineer- discharge resistance is determined as indicated in the
ing practice, the impedance of the upstream network formula [9.12] of Chapter 9.
contributes to limit this peak. However, should it be too
Example
high for the present electrical equipment, further limiting Let us suppose we want to dimension the discharge
inductances should be put as suggested in Chapter 9. resistors for the capacitor bank of the previous example.
Starting from [D.17] and replacing the values under con-
sideration it results (with the coefficient k = 1):
3⋅ 60
- 180
75≥ 2 ⋅ 230⋅e R ⋅10 -3 R≤ = 123 kΩ
Maximum peak of the inrush current of the capacitor bank 2 ⋅ 230
25 10- 3 ⋅ ln
i(t) 75
[kA]

20 By choosing a resistor with the same value as that in-


dicated, since in 3 min the resistor dissipates into heat
15 the electrostatic energy stored by each capacitor, the
maximum developed power results to be:
10 2

V2 2 ⋅ 230
5 P = c0 = = 0.86 W
R 123 ⋅103
0 As it can be noticed, in spite of the resistance value of the
-0.005 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
order of hundreds kΩ, the maximum power dissipated
-5
into heat is lower than 1W, because the maximum value
[ms]
of the discharge current is about:
Vc0 2 ⋅ 230
I= = = 2.6 mA
R 123 ⋅10 3
The consequence is a small cross section of the connec-
tion cables and limited thermal phenomena.

52 Power factor correction and harmonic filtering in electrical plants


Annex E
Power factor correction in photovoltaic plants If there is not a photovoltaic plant (PPV = 0):

Annex E
A photovoltaic plant usually supplies only active power, 0
tgϕ 2 = 0.5⋅ 1- = 0.5 cosϕ 2 = 0.9 [E.5]
therefore it is however necessary to draw from the net- P
work the reactive power required for the loads of the
user plant. that is why the power factor controller is set at 0.9 as
If a photovoltaic plant is added to an already existing usually prescribed.
electrical installation, the reactive power drawn by the
network remains the same, whereas the active power In the presence of a photovoltaic plant, active power is
decreases by the quantity supplied by the photovoltaic generated and the power factor regulator shall be set
generator as shown in the following figure: at a value higher than 0.9. In fact, for example, if the
Figure E.1
generated power is half the power drawn by the loads
(PPV = 0.5 · P ), it results:
PPV PN , QN

PV NETWORK 0.5⋅ P
tgϕ 2 = 0.5⋅ 1- = 0.25 cosϕ 2 = 0.97 [E.6]
P

Qc P = PPV + PN In the limit case, when the photovoltaic plant supplies all
Q = Qc + QN the active power required by the loads (PPV=P), the power
factor controller shall be set at a value equal to:

P, Q P
tgϕ 2 = 0.5⋅ 1- =0 cosϕ 2 = 1 [E.7]
P

LOADS
and consequently the capacitor bank shall deliver all the
reactive power required by the loads.
From the point of view of the network, the electrical
installation as a whole (photovoltaic generator and user
plant) shall have, not to incur penalties, an average power
factor equal to 0.9 from which it results:
QN
cos ϕ N ≥ 0.9 tgϕ N ≤ 0.5 ≤ 0.5 [E.1]
PN

Taking into account the indications given in the figure,


the previous formula can be rewritten as:
Q - Qc
≤ 0.5 [E.2]
P - PPV

from which:
[E.3]
P
Q C ≥ Q - 0.5⋅ ( P - PPV ) = P ⋅ tgϕ1 - 0.5⋅ 1- PV =
P
P ⋅ ( tgϕ1 - tgϕ 2 )

where:
PPV
tgϕ 2 = 0.5⋅ 1- [E.4]
P

Power factor correction and harmonic filtering in electrical plants 53


Technical Application Papers

Annex F
Harmonics in three-phase systems with Take into consideration the presence in the three-phase
neutral currents of the 3rd harmonic only, in addition to the
Annex F

fundamental one, with a value given by the Standard


F.1 Introduction IEC 60947-2 Annex F option b):
In three-phase systems with neutral it is possible to have
• I3 = 0.6 · I1
installation applications implying in the neutral conductor
the circulation of a current with an r.m.s. value higher than The r.m.s. value of the phase current as a function of the
the value of the phase currents. 1st harmonic results to be:
[F.1]
Hence the necessity to size the neutral with a cross I L1 = I L 2 = I L 3 = I L = I12 + I 32 = I12 ⋅ (1+ 0.62 ) =1.17⋅ I1
section larger than that of the phases and to have a
In the neutral conductor a current flows which is equal
different setting for the overcurrent protection of the
to the algebraic sum of the r.m.s. values of the three 3rd
phases and of the neutral in four-pole circuit-breakers.
harmonic components in phase between them:
As a consequence, the use of the harmonic filters and I N = 3 ⋅ I 3 = 3⋅ 0.6⋅ I1 =1.8⋅ I1 [F.2]
of the power correction techniques previously described
contribute also towards a reduction in the amount of the from which, expressing the neutral current as a function
neutral current, whose ratio with the phase current shall of the phase current, it results:
be analyzed under the different conditions of harmonic IL
I N =1.8⋅ I1 =1.8⋅ =1.54⋅ I L ≈ 160%I L [F.3]
pollution in the following cases. 1.17

Whereas, assuming as 3rd harmonic value that given in


the Standard IEC 60947-2 Annex F option a):
F.2 Symmetrical three-phase supply system and
three single-phase loads balanced but not linear
• I3 = 0.88 · I1
Figure F.1
E1
IL1 the previous relationships become:
[F.4]

E2 I L1 = I L 2 = I L 3 = I L = I12 + I 32 = I12 ⋅ (1+ 0.882 ) =1.33 ⋅ I1


IL2

I N = 3 ⋅ I 3 = 3⋅ 0.88 ⋅ I1 =2.64 ⋅ I1 [F.5]


E3 IL3

IL
I N =2.64 ⋅ I1 =2.64 ⋅ =1.98⋅ I L ≈ 200%I L [F.6]
IN 1.33
LOAD LOAD LOAD
As it can be noticed, in the neutral, a current which is
even twice the phase current may flow with the conse-
quent repercussion in the size of the cross section of the
conductor and in the settings of the overload protec-
tions. The ratio between the current in the neutral and in
the phase would increase if also harmonics multiple of
the 3rd one were present. Instead, the assumption that
other harmonics not multiple of the 3rd one are absent
represents a pejorative situation: their presence would
reduce the ratio previously given since such harmonics
would not flow through the neutral being balanced sym-
metrical sets.

54 Power factor correction and harmonic filtering in electrical plants


F.3 Symmetrical three-phase supply system and If also the 5th and the 7th harmonics are present, with
two single-phase loads balanced but not linear the following values given by the Standard IEC 60947-2

Annex F
Figure F.2
Annex F:
• I5 = 0.55 · I1
E1
IL1 • I7 = 0.07 · I1

E2 IL2
the ratio between the neutral current and the phase cur-
rent becomes:
E3 IL3 = 0
I N = I1⋅ 1+ (2 ⋅ 0.88)2 + 0.55 2 + 0.07 2 = 2.1⋅ I1 [F.11]

IN [F.12]

LOAD LOAD I L1 = I L 2 = I L = I1 ⋅ 1+ 0.88 2 + 0.55 2 + 0.07 2 =1.44⋅ I1

2.1
IN = ⋅ I L =1.46⋅ I L [F.13]
1.44

At first, take into consideration the presence of the 3rd As it can be noticed comparing the formula [F.13] with
harmonic only in addition to the fundamental one. Com- [F.10], also in this case the presence of harmonics not
pared with the previous case, now the current flowing in multiple of the 3rd reduces the ratio between the neutral
the neutral is the square root of the sum of the square of current and the phase current.
the fundamental component plus the square of the sum
of the two 3rd harmonics, that is:

IN = I12 + (2⋅ I 3 ) 2 [F.7]

In this particular case, the fundamental component of the


neutral current is the vectorial sum of the fundamental
components of the phase currents; since the latter are
equal in module and phase-displaced by 120°, the sum
gives, as resulting r.m.s value, the same value of the
phase fundamental component.

Assuming by hypothesis I3 = 0.88 · I1 (which can be veri-


fied in the single-phase rectifiers), it results:

[F.8]

I N = I12 + (2⋅ 0.88⋅ I1) 2 = I1⋅ 1+ (2⋅ 0.88) 2 = 2.02⋅ I1

[F.9]
I L1 = I L 2 = I L = I12 + I 32 = I12 ⋅ (1+ 0.88 2 ) =1.33 ⋅ I1

2.02
IN = ⋅ I L =1.52⋅ I L [F.10]
1.33

Power factor correction and harmonic filtering in electrical plants 55


Technical Application Papers

Glossary
I r.m.s. value of the total current
Glossary

Ir current component in phase with the voltage


Iq current component in quadrature with the voltage
I1 r.m.s. value of the first current harmonic
Ik r.m.s. value of the k-th current harmonic
U r.m.s. value of the line-to-line voltage
V r.m.s. value of the total phase voltage
V1 r.m.s. value of the first voltage harmonic
Vk r.m.s. value of the k-th voltage harmonic
P active power absorbed by the load
Q reactive power absorbed by the load
Q1 total reactive power before power factor correction
Q2 total reactive power after power factor correction
A apparent power absorbed by the load
D distortion power
N non-active power
S total apparent power
S1 total apparent power before power factor correction
S2 total apparent power after power factor correction
Qc reactive power of the capacitor bank
Icn rated current of the capacitor
Icmax maximum current drawn by the capacitor
cosϕ power factor
cosψ distortion factor
cosφ phase displacement factor
cosϕ1 power factor before reactive power compensation
cosϕ2 power factor after reactive power
THD total harmonic distortion factor
fr resonance frequency
PPV active power supplied by a photovoltaic generator
PN active power supplied by the network
QN reactive power supplied by the network

56 Power factor correction and harmonic filtering in electrical plants


Technical Application Papers
QT4
ABB circuit-breakers inside LV switchboards

QT5
ABB circuit-breakers for direct current
applications

QT1 QT6
Low voltage selectivity with ABB circuit-breakers Arc-proof low voltage switchgear and controlgear
assemblies

QT2 QT7
MV/LV trasformer substations: theory and exam- Three-phase asynchronous motors
ples of short-circuit calculation Generalities and ABB proposals for the coordina-
tion of protective devices

QT3 QT8
Distribution systems and protection against indi- Power factor correction and harmonic filtering in
rect contact and earth fault electrical plants
8

1SDC007107G0201 September ’08


Printed in Italy
6.000 - CAL

Due to possible developments of standards as well as of


materials, the characteristics and dimensions specified in this
document may only be considered binding after confirmation
by ABB SACE.

ABB SACE
A division of ABB S.p.A.

L.V. Breakers
Via Baioni, 35
24123 Bergamo - Italy
Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433

http://www.abb.com

Вам также может понравиться