Вы находитесь на странице: 1из 52

Caddyt

Arc 251i

Service manual

0740 800 188 080903 Valid for serial no. 810--xxx--xxxx


READ THIS FIRST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Component description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Arc 251i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DESCRIPTION OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1 MMC unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2AP1 EMC board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2AP2 Power supply board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2AP2:1 Primary circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2AP2:2 Secondary circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2AP2 Component positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
15AP1 Power module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
15AP1:1 Switching circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
15AP1:2 Gate driver stages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
15AP1:3 Secondary power circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
15AP1:4 Temperature monitoring circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
15AP1:5 Thyristor firing circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
15AP1 Component positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
17AP1 PFC board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
17AP1:1 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
17AP1:2 Power factor corrector (PFC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
17AP1:3 Thyristor firing circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
17AP1:4 Temperature monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
17AP1 Component positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
20AP1 Control board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
20AP1:1 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
20AP1:2 Control panel interface circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
20AP1:3 Remote control input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
20AP1:4 Pulse width modulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
20AP1:5 Temperature monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
20AP1:6 Shunt and current control amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
20AP1:7 Arc voltage feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
20AP1:8 TIG functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
20AP1:9 Welding process control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
20AP1:10 Power--up starting sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
20AP1:11 Fan On/Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
20AP1 Component positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
20AP1 VRD strapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
FAULT CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SERVICE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
What is ESD? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Service aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Special tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Checking power board 15AP1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Checking PFC board 17AP1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Soft starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Checking the gate pulses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Mounting components on the heat sink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
IN--SERVICE INSPECTION AND TESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
General requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Periodic inspection and test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
After repair, inspection and test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Visual inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Electrical test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Functional test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Test report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Rights reserved to alter specifications without notice.

TOCe -- 2 -- S0740 800 188/E080903/P52


INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Mains power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Connections and control devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Overheating protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Power source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
FAULT--TRACING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
SPARE PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Rights reserved to alter specifications without notice.

TOCe -- 3 -- S0740 800 188/E080903/P52


READ THIS FIRST
Maintenance and repair work should be performed by an experienced person, and
electrical work only by a trained electrician. Use only recommended replacement parts.
This service manual is intended for use by technicians with electrical/electronic training for
help in connection with fault--tracing and repair.
Use the wiring diagram as a form of index for the description of operation. The circuit
boards are divided into numbered blocks, which are described individually in more detail in
the description of operation. Component names in the wiring diagram are listed in the
component description.
Use the spare parts list as a guide to where the components are located in the equipment.
The spare parts list is published as a separate document, see page 51.
This manual contains details of design changes that have been made up to and including
August 2008.
The manual is valid for: Arc 251i with serial number 810--xxx--xxxx.

The Arc 251i is designed and tested in accordance with international and European
standards IEC/EN 60974.
On completion of service or repair work, it is the responsibility of the person(s)
performing the work to ensure that the product still complies with the requirements of
the above standard.

WARNING!
Many parts of the power source are at mains voltage.

CAUTION!
Read and understand the instruction manual before
installing or operating.

INTRODUCTION
Caddy Arc 251i is a welding power source intended for MMA and TIG welding, where all
settings are made from the control panel.

Design structure of the power source


Caddy Arc 251i is a microprocessor controlled power source based on the inverter principle.
It consists of a number of function modules, as shown in the schematic diagram below.
Each module has a module number, which is always included as the first part of the
name/identification of components in the module.

ch34_00 -- 4 -- S0740 800 188/E080903/P52


Principle block diagram of the Arc 251i

The modules have the following main functions:


2AP1 EMC module
The EMC module suppresses interference to the mains.
17AP1 PFC
The PFC module handles the power factor correction for the power source. The 3 phase
voltage is rectified and feeds a switching circuit that forms a controlled high voltage DC
supply to the power board, 15AP1.
15AP1 Power board
This module is a forward inverter, operating at a switching frequency of 45 kHz. IGBT
transistors are used as the switching elements. All power semiconductors are built into
modules.
2AP2 Power supply unit
The power supply unit (PSU) is supplied by the PFC module. It generates supply voltages
to the fan, the control board and the switching circuit of the PFC module.
20AP1 Control board
The control board, 20AP1, checks the status of the control elements of the control panel
and controls the function of the power board, 15AP1.

TECHNICAL DATA
Arc 251i
Mains voltage 400 V ±15%, 3∼ 50/60 Hz
Mains supply Ssc min 3.3 MVA
Primary current
Imax MMA 14 A
Imax TIG 10 A
No--load power demand when in the
energy--saving mode, 6.5 min. after welding 30 W
Setting range
MMA 4 -- 250 A
TIG 3 -- 250 A
Permissible load at MMA
30 % duty cycle 250 A / 30 V
60 % duty cycle 190 A / 27.6 V
100% duty cycle 150 A / 26 V

ch34_00 -- 5 -- S0740 800 188/E080903/P52


Arc 251i
Permissible load at TIG
30 % duty cycle 250 A / 20 V
60 % duty cycle 190 A / 17.6 V
100% duty cycle 150 A / 16 V
Power factor at maximum current
MMA 0.94
TIG 0.93
Efficiency at maximum current
MMA 83 %
TIG 79 %
Open--circuit voltage
without VRD 62 V
with VRD <35 V
Operating temperature --10 to +40˚C
Transportation temperature --20 to +55˚C
Constant sound pressure when idling <70 db (A)
Dimensions lxwxh 418 x 188 x 208 mm
Weight 10.5 kg
Insulation class transformer H
Enclosure class IP 23
Application class

Mains supply, Ssc min


Minimum short circuit power on the network in accordance with IEC 61000--3--12

Duty cycle
The duty cycle refers to the time as a percentage of a ten--minute period that you can weld at a cer-
tain load without overloading. The duty cycle is valid for 40˚C.

Enclosure class
The IP code indicates the enclosure class, i. e. the degree of protection against penetration by solid
objects or water. Equipment marked IP23 is designed for indoor and outdoor use.

Application class
The symbol indicates that the power source is designed for use in areas with increased
electrical hazard.

WIRING DIAGRAM
The power source consists of a number of function modules, which are described in the
component descriptions on the following pages. Wire numbers and component names in
the wiring diagram show to which module each component belongs.
Wires/cables within modules are marked 100 -- 6999.
Wires/cables between modules are marked 7000 -- 7999.
Components outside modules -- e.g. capacitors -- are named such as C1 -- C99,
connectors XS1 -- XS99 (S = socket), XT1 -- XT99 (T = terminal).
Circuit boards within each module have names such as 20AP1 -- 20AP99.

ch34_00 -- 6 -- S0740 800 188/E080903/P52


20 = module association, 1--69
AP = circuit board
1 = individual identification number, 0--99

Transistors within particular modules have identification numbers such as 15Q1 --


15Q99.
15 = module association, 1--69
Q = transistor
1 = individual identification number, 0--99

Component description
Component Description
1 MMC module. This module is described in a separate manuals for the
control panels.
2 Mains module. Wire numbers 200 -- 299.
2AP1 EMC board, see page 11.
2AP2 Power supply board, see page 12.
2QF1 Main switch.
2L1 -- 2L5 Ferrite ring cores.
15AP1 Power board, see page 16.
15AP2 LC--filter board, see page 17
15TM1 Main transformer
15L2 Inductor, welding circuit.
15ST1 Thermal switch in the winding of 15L2.
15D1 -- 15D3 Diode modules Each module consists of two diodes.
Two diodes are rectifier diodes, one from 15D1 and one from 15D2.
Three diodes are frewheel diodes, one from each module.
One diode from 15D3 is a filterdiode.
See page 41 for assembly instructions.
15EV1 Fan.
15RS1 Shunt. 119 ±1 mV at 250 A
17AP1 PFC board, see page 20.
17L1 PFC inductor
20AP1 Control board, see page 23.

CAUTION !
STATIC ELECTRICITY can damage circuit
boards and electronic components.
S Observe precautions for handling electrostatic--
sensitive devices.
ESD S Use proper static--proof bags and boxes.

ch34_00 -- 7 -- S0740 800 188/E080903/P52


Arc 251i

Placement of the circuit boards

ch34_00 -- 8 -- S0740 800 188/E080903/P52


ch34_00 -- 9 -- S0740 800 188/E080903/P52
DESCRIPTION OF OPERATION
This description of operation describes the function of circuit boards and other components
in the equipment. It is divided into sections, numbered to correspond to the circuit board
numbers and divisions into function blocks.

1 MMC unit
The MMC unit consists of a operator’s control panel and a display board. The MMC is used
for setting and displaying welding data. The welding data are stored by the control board,
20AP1.
The control panel consists of pushbuttons, control knob, LEDs and a 3--digit display.
The control panels are described in separate instruction and service manuals.
The control panels are:

S A32 intended for MMA-- and DC TIG--welding


S A34 intended for MMA-- and DC TIG--welding.

ch34_01 -- 10 -- S0740 800 188/E080903/P52


2AP1 EMC board
The combination of coils and capacitors prevents interference from the inside of the
machine to reach the electric mains network.

Circuit diagram

WARNING!,
Dangerous voltage - mains voltage.

Component positions

ch34_02_1 -- 11 -- S0740 800 188/E080903/P52


2AP2 Power supply board
The power supply board receives rectified mains voltage, about 565 V DC, from the PFC
board. From this it generates supply voltages for the power source.

2AP2:1 Primary circuit


WARNING! Dangerous voltage - mains voltage.

The primary circuit is supplied at 565 V DC from the PFC board, 17AP1.
Transistors Q1 and Q2 are the switching elements in a switched voltage
supply. The sensing circuit uses the secondary voltage +24V that is connected
to IC5. Through optocoupler IC2, IC5 controls switch regulator IC3, which
generates gate pulses to Q1 and Q2, via TR1.
+15VA and 0VA
Internal power supply for the 2AP2 and for circuits on the 17AP1 and 15AP1.
It is regulated to 15±0.75 V by VR3. It is part of the primary side as it shares
the 0VA with the 565 V supply voltage.

ch34_02_2 -- 12 -- S0740 800 188/E080903/P52


2AP2:2 Secondary circuit

The output voltages can be tested by the SST 3, see soft--starting on page 38.
+13VB and 0VB
Unregulated voltage at 13±1.5 V with galvanic isolation, used for remote
control.
+5V and 0V
The voltage is regulated by VR1 to 5±0.25 V.
+24V and 0V
This voltage is regulated to 24±0.75 V by IC3 on the primary side togheter
with IC5 on the secondary side.
--15V and 0V
This voltage is regulated to --15±0.75 V by VR4.
Fan On/Off
The fan, 15EV1, is supplied at +24V. It is controlled by 20AP1 with the signal
Fan On/Off. See also “20AP1:11 Fan On/Off” on page 29.
Early warning power shut down
If the voltage goes low, the output CN1:8 generates a warning signal to the
processor on the control board 20AP1. The control board AP201 then shuts
down in a controlled manner.

ch34_02_2 -- 13 -- S0740 800 188/E080903/P52


2AP2 Component positions

WARNING!
Dangerous voltage - mains voltage. The shaded area is at mains voltage
potential.

ch34_02_2 -- 14 -- S0740 800 188/E080903/P52


emptypage -- 15 -- S0740 800 188/E080903/P52
15AP1 Power module

Power module main circuits


WARNING!
Dangerous voltage - mains voltage. Never make any measurements on this board
when the machine is connected to the mains supply.
The power module is a single forward converter, operating at a switching frequency of
45 kHz with IGBT transistors as the switching elements.
The power board carries the gate circuit and the switching circuit. The switching transistors
are integrated in a semiconductor module, PM1, which is part of the power board.
See page 40 for screen traces of waveforms and measurement instructions.
On page 34 there are instructions on how to check the power board.
If the power board has failed, a replacement board must be mounted in accordance with the
instructions on page 41.

15AP1:1 Switching circuit


The switching transistors are integrated in the semiconductor module, PM1.
They are connected in parallel four and four.

15AP1:2 Gate driver stages


Transformer TR1 is a gate driver transformer for galvanic isolation of the drive
circuits from circuit board 20AP1. The gate pulses are measured on circuit
board 20AP1, see instructions on page 40.

ch34_15 -- 16 -- S0740 800 188/E080903/P52


15AP1:3 Secondary power circuits

The secondary power circuits are: transformer 15TM1, diode modules


15D1,15D2,15D3, inductor 15L2 and LC filter 15AP2.
Diode modules
Each diode module consists of two diodes.
Two diodes are rectifier diodes, one from 15D1 and one from 15D2.
Three diodes are frewheel diodes, one from each module.
One diode from 15D3 is a filterdiode.
During the time interval between two voltage pulses from transformer 15TM1,
the freewheel diodes maintain the welding current from inductor 15L2.
If a diode module has failed, a replacement module must be fitted in
accordance with the instructions on page 41.

15AP2 Filter board


Inductor L1 forms an LC circuit
with C1//C2 and D2 to reduce
the risk of arc extinction at low
welding currents.
When rectifier diodes
15D1//15D2 conducts, the LC
circuit charges up.
The circuit is capable of
temporarily maintaining a high 15AP2, circuit diagram and component positions
arc voltage at low current.
Diode D2 prevents capacitor C1//C2 from going negative.

ch34_15 -- 17 -- S0740 800 188/E080903/P52


15AP1:4 Temperature monitoring circuits

WARNING!
Dangerous voltage - mains voltage. +15VA, +14VA, +5V1A and 0VA are at
mains voltage potential.
The control board, 20AP1, uses a digital input to monitor the temperatures of
the power source. The temperature feedback from the NTC resistors on the
PFC and power boards is analogue. The monitoring circuits on the power
board handles the threshold levels and hysteresis of the temperature
measument.
See also “20AP1:5 Temperature monitoring” on page 25.

15AP1:5 Thyristor firing circuit


See “17AP1:3 Thyristor firing circuit” on page 21.

ch34_15 -- 18 -- S0740 800 188/E080903/P52


15AP1 Component positions

ch34_15 -- 19 -- S0740 800 188/E080903/P52


17AP1 PFC board

The PFC board consists of the main rectifier, the thyristor firing circuit, the temperature
circuit and the PFC control circuit.
If the PFC board has failed, a replacement board must be mounted in accordance with the
instructions on page 42.
On page 36 there are instructions on how to check the PFC board.
WARNING!
Dangerous voltage - mains voltage. All parts of this circuit board are at mains
voltage potential.

17AP1 main circuits

17AP1:1 Power supply


The three--phase mains voltage is rectified by semiconductor module PM1.
When the power source is in idle mode, the rectified voltage (565 V) is
supplied through the charging resistors, R78 and R79. In welding mode the
thyristor in PM1 by--passes the resistors. If the thyristor did not conduct,
resistors R78 and R79 would burn out when the unit is in welding mode.
The 565 V supplies the PFC circuit that boosts the voltage to 710 V.

17AP1:2 Power factor corrector (PFC)


The aim with the power factor corrector is to keep the mains current sinusoidial
and in phase with the mains voltage. The PFC circuit holds the intermediate
voltage (+DCbus) at 710 V. If the PFC circuit does not work the intermediate
voltage is 565 V or less.
When the PFC is working properly, the voltage across the DCbus is 710 V.

ch34_17 -- 20 -- S0740 800 188/E080903/P52


17AP1:3 Thyristor firing circuit

When the mains power supply is turned on and during idle mode the thyristor
in PM1 is off.
When the switching circuit on power board 15AP1 receives gatepulses from
the control board, the firing circuit turns on the thyristor in PM1 so that it
by--passes the charging resistors.

17AP1:4 Temperature monitoring

The PM1 module havs a built--in NTC--resistor that monitors the internal
temperature. It is connected to the temperature circuits on the power board.
See “15AP1:4 Temperature monitoring” on page 18 and
“20AP1:5 Temperature monitoring” on page 25.

ch34_17 -- 21 -- S0740 800 188/E080903/P52


17AP1 Component positions

ch34_17 -- 22 -- S0740 800 188/E080903/P52


20AP1 Control board
The processor on the control board monitors and controls the various functions of the power
source. It obtains information on welding data from the control panel.
If the circuit board is faulty, it must be replaced. After replacing the circuit board, soft--start
the machine. See the instructions on page 38.
Note! There are jumpers on the board that must be moved to the replacement board, see
page 30.

20AP1:1 Power supply


+5 V and +2.5 V

IC6 monitors the 24 V voltage supply to the 5 V regulator on circuit board


2AP2. IC16 monitors the 5 and 2.5 V supplies. Regulator VR4 supplies the
processor with +2.5 V.
The voltage on terminal PF6 is normally about 24 V, when this drops below
20 V, pin 14 of IC6 goes low, providing the processor with a low power supply
voltage signal. The processor then stores current data and generates fault
code E4. When the 5 and 2.5 V voltages are passing below their treshold
values, the processor receives a reset signal from IC16.
Fault code E4 is not displayed at normal power off

+15 V and +20 V

Voltage regulator VR2 produces an output voltage of +20 ±1.0 V, which


supplies the pulse width modulator output stage.
Voltage divider R70/R75 supplies 2.6 V to the processor. This provides a signal
that the power supply is available.
Voltage regulator VR1 produces an output voltage of +15 V, and this, together
with the --15 V supply, powers the analogue circuits.

ch34_20 -- 23 -- S0740 800 188/E080903/P52


--15 V

The --15 V power supply is monitored by the processor.

+10 VB

Voltage regulator VR3 produces a stabilised +10 V supply, which is used to


supply the remote control unit. This supply is referred to as +10 VB, and its
neutral point, 0 VB, is separated from the electronic neutral (0 V).
Potentiometer R56 is used to adjust the voltage.

20AP1:2 Control panel interface circuits


See the service manual for the A32/A34 control panels.

20AP1:3 Remote control input

If the remote control input is activated, but there is no reference signal, resistor
R54 holds the reference input low. This results in a welding current of 3 A for
TIG welding and 4 A for MMA welding.

ch34_20 -- 24 -- S0740 800 188/E080903/P52


20AP1:4 Pulse width modulator

The pulse width modulator determines the frequency and pulse time of the
switching transistors’ control pulses. IC3 controls the pulse frequency, the
pulse time and inhibition of pulses.
The pulse frequency is 45 kHz +/-- 1kHz, with a maximum pulse width of 43 --
44 % of the cycle width. See page 40 for screen traces of waveforms and
measurement instructions.
Transistor Q5 controls the primary winding of the pulse transformer on circuit
board 15AP1.

20AP1:5 Temperature monitoring

Principle diagram of the temperature monitoring circuits

The temperature monitoring circuit operates when the temperature exceeds


one of the threshold temperatures as decribed below.
If the monitoring circuit operates, the power source is stopped. The power
source cannot be restarted until it has cooled sufficiently.
15NTC_PM1 is fitted inside semiconductor module PM1 of the power board,
15AP1. The treshold temperature is 95_C and it resets at 62_C.
17NTC_PM1 is fitted inside semiconductor module PM1 of the PFC board,
17AP1. The treshold temperature is 88_C and it resets at 60_C.
Thermal overload switch 15ST1 is fitted in the winding of inductor 15L2. It
opens at 140_C.

ch34_20 -- 25 -- S0740 800 188/E080903/P52


20AP1:6 Shunt and current control amplifier

The shunt produces 119 mV at a welding current of 250 A. The shunt response
is linear to the welding current.
If the shunt is not connected to the circuit board, resistor R2 supplies about
1.4 to 1.9 V to the shunt input. This blocks the current control amplifier, i.e. the
machine does not deliver any welding current.

20AP1:7 Arc voltage feedback

This circuit measures and scales the arc voltage to a suitable level for the
processor. 64 V arc voltage produces a voltage signal of 5.0 V at the cathode
of diode D13.
Open--circuit voltage control
The open--circuit voltage control holds the voltage at 50 -- 64 V.
When the VRD (Voltage Reduction Device) function is active, the open--circuit
voltage is < 35 V (19 -- 30 V). The VRD function can only be activated or
deactivated by changing the strapping of the control board, see the circuit
diagram below and the component positions diagram
on page 30.
Note! Spare part boards are delivered with VRD
inactive.

VRD strapping

ch34_20 -- 26 -- S0740 800 188/E080903/P52


MMA
S The machine generates the actual open--circuit voltage, see: “Open--circuit
voltage control” above.
S Touch the electrode on to the workpiece. When the open--circuit voltage
goes below 45 V (16 V when VRD is active), the open--circuit voltage
control is disabled.
S When the current exceeds 8 A the hot start current is activated.
S When the arc voltage exceeds 52 V, welding stops and the open--circuit
voltage control is activated.
When the welding arc extinguishes the open circuit voltage is about 120 V,
peak voltage. Within 0.3 seconds the open--circuit voltage control reduces the
voltage to about 60 V, peak voltage, (30 V when VRD is active).
TIG
See: “20AP1:8 TIG functions” below.

20AP1:8 TIG functions


Live TIG start
S The machine generates the actual open--circuit voltage, see: “Open--circuit
voltage control” above.
S Touch the electrode on to the workpiece. The machine produces a current
of about 24 A.
S Lift the electrode from the workpiece. The arc strikes, the open--circuit
voltage control is deactivated and the current increases to 30 A.
S When the arc voltage exceeds 8 V, the current increases / decreases to
the set current.
S If the arc voltage is above 45 V for more than 100 milliseconds the
open--circuit voltage control is activated.
When the welding arc extinguishes the open circuit voltage is about 120 V,
peak voltage. Within 0.3 seconds the open--circuit voltage control reduces the
voltage to about 60 V, peak voltage, (30 V when VRD is active).

Terminal TIG

Terminal TIG, shown above, is not used in this application.


Terminals TIG1 and TIG5 are used for power supply during soft--starting, see page 38.

ch34_20 -- 27 -- S0740 800 188/E080903/P52


20AP1:9 Welding process control
The processor inputs are the set values of welding data and the arc voltage.
The processor also calculates a set value signal for welding current, and
supplies this to the current control amplifier.

The process regulator control principle

Hot start MMA


Current

Peak current

Adjustable starting current

Set current

Time
1 2
Starting current, MMA welding mode
1. Phase 1, fixed starting current depending on the set current.
2. Phase 2, hot start = adjustable starting current.

MMA normal welding mode


In the MMA normal welding mode, the welding current is briefly increased at
the start of welding. The peak current, phase 1 in the diagram above, is
engaged for 150 milliseconds.
The peak current is twice the normal welding current up to 150 A (i.e. twice the
set value), subject to a maximum of 350 A.
The hot start current, phase 2 above, is engaged for 1.5 seconds. It is set in
per cent of the set current, but does never exceed the peak current.
MMA drop welding mode
In the MMA drop welding mode, the peak current is three times the set value,
but the duration is shorter at only 50 ms.
The hot start current, phase 2 above, is engaged for 240 milliseconds. It is set
in per cent of the set current, but does never exceed the peak current.

ch34_20 -- 28 -- S0740 800 188/E080903/P52


20AP1:10 Power-- up starting sequence
On power--up, the board’s CAN controller reads in the bus speed from the
micro processor: 400 kbit/s.
The circuit board displays the starting
sequence from power--up.
LED1 lights red. Then LED1, LED2 and
LED3 lights green.
When the board has been initiated, and the
power source is in the application program,
LED1 flashes continously with a green light.
LEDs on circuit board 20AP1

20AP1:11 Fan On/Off

The fan is controlled by the control signal Fan On/Off. The signal is connected
to a power transistor on 2AP2 that switches the power to the fan on or off.
See also “Fan On/Off” on page 13.
The fan starts when the mains switch is turned on and runs for seven seconds.
It starts when welding starts and continues to run six and a half minutes after
welding is finished.

ch34_20 -- 29 -- S0740 800 188/E080903/P52


20AP1 Component positions

Note! There must be a jumper between pin 5 and 6 on terminal RS.

20AP1 VRD strapping


Strap terminal A1 and A2 to activate the VRD function.
Strap terminal A2 and A3 to deactivate the VRD function.
See also item 20AP1:7 Arc voltage feedback on page 26.

ch34_20 -- 30 -- S0740 800 188/E080903/P52


FAULT CODES
Code Description
E04 5 V power supply too low
The unregulated power supply voltage (+24 V) is too low: the smoothing capacitors cannot
keep the voltage up enough for the processor to continue to operate. The processor stops all
normal activities, expecting to be shut down.
Action: Turn off the mains power supply to reset the unit. If the fault persists, check the
power supply to circuit board 20AP1.

E06 High temperature


The temperature monitoring circuit has operated. The power source is stopped, and cannot
be restarted until the circuit has reset. See also page 25.
Possible causes: Overloading, fan not working properly, cooling air inlets or outlets blocked
or obstructed or dirt on the heat exchanger.
E11 Current servo fault
Automatic reset when the fault has cleared. May also be reset by pressing any pushbutton.
E16 High no--load voltage, VRD error
The open circuit voltage is too high.
Action: Turn off the mains power supply to reset the unit. Check the arc voltage monitoring
circuits, see diagram on page 26. If the fault persists replace circuit board 20AP1.

E19 Error in persistent memory


Action: Restart the machine. If the fault persists, replace circuit board 20AP1.

ch34f1 -- 31 -- S0740 800 188/E080903/P52


SERVICE INSTRUCTIONS

CAUTION !
STATIC ELECTRICITY can damage circuit
boards and electronic components.
S Observe precautions for handling electrostatic--
sensitive devices.
ESD S Use proper static--proof bags and boxes.

What is ESD?
A sudden transfer or discharge of static electricity from one object to another. ESD stands for
Electrostatic Discharge.

How does ESD damage occur?


ESD can cause damage to sensitive electrical components, but is not dangerous to people.
ESD damage occurs when an ungrounded person or object with a static charge comes into
contact with a component or assembly that is grounded. A rapid discharge can occur,
causing damage. This damage can take the form of immediate failure, but it is more likely
that system performance will be affected and the component will fail prematurely.

How do we prevent ESD damage?


ESD damage can be prevented by awareness. If static electricity is prevented from building
up on you or on anything at your work station, then there cannot be any static discharges.
Nonconductive materials (e.g. fabrics), or insulators (e.g. plastics) generate and hold static
charge, so you should not bring unnecessary nonconductive items into the work area.
It is obviously difficult to avoid all such items, so various means are used to drain off any
static discharge from persons to prevent the risk of ESD damage. This is done by simple
devices: wrist straps, connected to ground, and conductive shoes.
Work surfaces, carts and containers must be conductive and grounded. Use only antistatic
packaging materials. Overall, handling of ESD--sensitive devices should be minimized to
prevent damage.

ch34f2 -- 32 -- S0740 800 188/E080903/P52


Service aid
We can offer a number of service tools that will simplify the service.

Antistatic service kit


Ordering no. 0740 511 001
The kit makes it easier to protect sensitve
components from electrostatic discharge.
Contents:
S A conductive mat (size 610 x 610 mm)
S A 1.5 metre long ground cable with a
crocodile clip
S An adjustable wrist strap and cable with
an inbuilt protective resistor
Antistatic service kit

Special tools
Soft--starting tool SST 3
The soft--starting tool SST 3 is made for ESAB’s single phase inverters and for 3--phase
inverters with 250 A output current. Ordering no. 0459 534 881
The tool includes:
Soft starting rectifier, cable set, voltage test board, gate pulse load and shunt voltage
resistor for single phase inverters with analogue control board (Arc 151i A31, Arc 152i A31
and OrigoArc).
For the 3--phase machines there are: soft--starting--voltage adapter with current limit and
temperature--switch jumper.

Test box TB 1
To be used for in--service inspection and testing.
Ordering no. 0460 868 880

ch34f2 -- 33 -- S0740 800 188/E080903/P52


Checking power board 15AP1

1. Disconnect the welding power source from the mains supply.


2. Dismantle the cover.
3. Measure the forward voltage drop of the freewheel diodes in the PM1 module.
a. Connect the positive pole of the multimeter to CN4 and the negatve pole to CN5.
The voltage drop must be 0.35 to 0.6 V.
b. Connect the positive pole of the multimeter to CN6 and the negatve pole to CN3.
The voltage drop must be 0.35 to 0.6 V.
4. Measure the resistance across gate and source of the transistors in the PM1 module.
a. Connect the negative pole of the ohmmeter to CN5 and the positive to PM1:9,
PM1:10, PM1:12 and PM1:13 respectively.
The resistance must be higher than 100 kohm.
b. Connect the negative pole of the ohmmeter to CN4 and the positive to PM1:18,
PM1:19, PM1:21 and PM1:22 respectively.
The resistance must be higher than 100 kohm.
5. Measure the resistance of the NTC--resistor in PM1.
Measure between PM1:23 and PM1:24.
The resistance must be 1.5 to 2.0 kohm at an ambient temperature of about 20°C.

ch34f_15ap1 -- 34 -- S0740 800 188/E080903/P52


Measuring points for 15AP1

ch34f_15ap1 -- 35 -- S0740 800 188/E080903/P52


Checking PFC board 17AP1

1. Disconnect the welding power source from the mains supply.


2. Dismantle the cover.
3. Measure the forward voltage drop of the diodes of the rectifier bridge.
The voltage drop must be 0.4 to 0.6 V.
a. Connect the negative pole of the multimeter to R78 and the positive pole to CN1,
CN4 and CN6 respectively.
b. Connect the positve pole of the multimeter to CN3 and the negative pole to CN1,
CN4 and CN6 respectively.
4. Unscrew and remove the two screws that are connecting 17L1 to the circuit board.
Insulate the terminals of 17L1 from the circuit board by fitting the tip of a plastic cable
tie, or similar, between the connection terminals of 17L1 and the circuit board.
a. Measure the forward voltage drop of diode PM1:D1.
Connect the positve pole of the multimeter to R79 and the negative pole to CN2.
The voltage drop must be 0.4 to 0.6 V.
b. Measure the forward voltage drop of diode PM1:D2.
Connect the positve pole of the multimeter to 17L1 and the negative pole to CN2.
The voltage drop must be 0.7 to 0.9 V.
5. Connect 17L1 to the circuit board, tighten the connection screws to a torque of 4.5 Nm.
6. Measure the resistance across the charge resistors R78 and R79.
The resistance must be about 24 ohm.
7. Measure the resistance of the NTC--resistor in PM1.
a. Measure between PM1:5 and PM1:6.
The resistance must be 1 to 2 kohm at an ambient temperature of about 20°C.
b. Disconnect the ribbon cable from terminal CN5.
c. Measure between PM1:5 and PM1:6.
The resistance must be 5.5 to 6.5 kohm at an ambient temperature of about 20°C.
d. Reconnect the ribbon cable to terminal CN5.
8. Connect the power source to the mains and switch it on.
9. Measure the rectified mains voltage.
Measure between R79 and CN3. The voltage must be 565 V DC (15%).
10. Measure the output voltage from the PFC board.
Measure between CN2 and CN3. The voltage must be 710 V DC (5%).
11. Checking the thyristor firing circuit.
a. Connect a voltmeter across R78 and R79.
The voltage at no load must be about 1.2 V DC.
b. Connect the output of the power source to a resistive load of
200 ohm 100 W (test box TB 1 can be used).
c. Set a welding current of 25 A.
The voltage across R78 and R79 must be about 0.8 V DC.
12. Checking voltage 5V1. Measure between TP1 and CN3.
The voltage must be 5.1 V DC (2%).
13. Disconnect the power source from the mains.
14. Reassemble the cover.

ch34f_17ap1 -- 36 -- S0740 800 188/E080903/P52


Measuring points for 17AP1
The circuit diagram of 17AP1 is on page 20.

ch34f_17ap1 -- 37 -- S0740 800 188/E080903/P52


Soft starting
We recommend soft starting of the machine after replacing circuit board 20AP1, power
supply board 2AP2 and circuit boards or components in the power module.
Soft starting supplies the power board with a low voltage in order to avoid injury to persons
or damage to components.
It is a good idea to use soft starting when fault tracing.

Special equipment
To soft--start the machine you need the
soft--starting tool SST 3, this is described on
page 33.

WARNING!
Dangerous voltage - The PFC board,
17AP1, is at mains voltage during the
soft- starting procedure.

Placement of the circuit boards

Instructions
1. Disconnect the welding power source from the mains supply.
2. Dismantle the cover.
3. Remove the two copper bars between
the PFC board, 17AP1 and
the power board, 15AP1.
(Connections 17AP1:CN2 to 15AP1:CN5
and 17AP1:CN3 to 15AP1:CN6.)

4. Disconnect the ribbon cable from terminal CN1 of the


power supply board, 2AP2.
5. Connect the cable “Voltage test” from SST 3 to terminal
CN1 of 2AP2.
6. Connect the power source to the mains supply.
7. Turn the mains switch to ON.
WARNING!
8. Verify the output voltages from 2AP1, all LEDs on the Terminal
SST 3 must light. CN2 is at
mains volt-
9. Check the +15VA voltage from 2AP2. age
Measure between terminals CN2:4 and CN2:5 on 2AP2.
The voltage must be 15 V 0.75 V.
10. Turn the mains switch to OFF.
11. Reassemble the ribbon cable between the power supply board and the control board.
12. Disconnect the power source from the mains supply.

ch34f3soft -- 38 -- S0740 800 188/E080903/P52


13. Connect SST 3 for soft starting of 15AP1.
a. Connect cable 20AP1 TIG to terminal TIG of the control board.

Connection of the SST 3 to


the control board

b. Connect cable 15AP1 CN5 to terminal CN5 of the power board.


c. Connect cable 15AP1 CN6 to terminal CN6 of the power board.

Connection of the SST 3 to


the power board

14. Connect the power source to the mains supply.


15. Turn the mains switch to ON.
16. Set the power source to MMA mode.
17. Measure the supply voltage to 15AP1.
Measure between CN5 (+) and CN6 (--).
The voltage must be 22 to 25 V DC.
18. Measure the voltage across the welding outlets.
The voltage must be about 4 V DC.

Circuit connections and measuring points for soft starting

19. Turn the mains switch of the welding power source to OFF.
20. Disconnect the power source from the mains supply.
21. Disconnect SST 3.
22. Reassamble the two copper bars between the PFC board and the power board.
(Connections 17AP1:CN2 to 15AP1:CN5 and 17AP1:CN3 to 15AP1:CN6.)
23. Reassemble the cover.

ch34f3soft -- 39 -- S0740 800 188/E080903/P52


Checking the gate pulses
When checking the gate pulses, the machine can either be in soft--starting mode or in
normal operation mode.

Special equipment
To measure the gate pulses, you need a gate pulse load. This is included in soft--starting
tool SST3, which is described on page 33.

Instructions
1. Disconnect the machine from the mains.
2. Disconnect connector 20XS5 from terminal G on control board 20AP1.
3. Connect the gate pulse test cable of the SST 3 to terminal G on control board 20AP1.

Measuring connection for the gate pulses


4. Connect the temperature--switch jumper to terminal T on control board 20AP1.
5. Switch on the machine.
6. Connect an oscilloscope to the SST 3, with the probe to terminal G2 and the screen to
terminal G1 of SST 3.
7. Set the machine to MMA welding mode.
8. Measure the pulse frequency. It must be 45 kHz +/-- 1kHz.
9. Measure the duration of the negative pulse. It must be 41 -- 43 % of the cycle time,
measured at a voltage level of --10 V.
10. The waveform of the pulses must be as shown below.

Gate pulses from circuit board 20AP1

ch34f3gate -- 40 -- S0740 800 188/E080903/P52


Mounting components on the heat sink
Thermal paste
Apply thermal conducting paste to the components before fitting them to the heat sink.
Start by cleaning the heat sink, and then apply a very thin, even layer of thermal paste to
the contact surfaces of the components. The purpose of the paste is to fill out any hollows
in the surfaces of the components and the heat sink. Those parts of the component and the
heat sink that are in true metallic contact may already have good thermal contact.
Mount the components as described below.
See the spare parts list for the order number for thermal paste, roller and roller handle. Use
only the paste recommended by us.

Fitting instructions

15AP1 Power board with semiconductor module


1. Clean the heat sink and apply thermal conducting paste to the
semiconductor module as described above.
2. Fit the board and tighten the screws to a torque of 2.5 Nm, and then further
tighten them to 4.5 Nm.
3. Tighten the screws that connect transformer 15TM1 and copper bars to
circuit board 15AP1 to a torque of 4.5 Nm.
CAUTION!
Incorrectly fitted components can cause failure. Do not tighten the screws to
more than 4.5 Nm.
Note! If transformer 15TM1 has to be replaced, the power board must be
removed and then refitted as described above.

15D1, Diode modules


15D2,
1. Clean the heat sink and apply thermal conducting paste to the diode
15D3
module as described above.
2. Fit the module and tighten the screws to a torque of 2.5 Nm, and then
further tighten them to 4.5 Nm.
3. Tighten all connections to the copper bars and circuit board 15AP1 to
4.5 Nm.
CAUTION!
Incorrectly fitted components can cause failure. Do not tighten the screws to
more than 4.5 Nm.

ch34f3heat -- 41 -- S0740 800 188/E080903/P52


17AP1 PFC board with semiconductor module

1. Clean the heat sink and apply thermal conducting paste to the
semiconductor module as described above.
2. Fit the board and tighten the screws to a torque of 2.5 Nm, and then further
tighten them to 4.5 Nm.
3. Tighten the screws that connect 17L1 and the copper bars to circuit board
15AP1 to a torque of 4.5 Nm.
CAUTION!
Incorrectly fitted components can cause failure. Do not tighten the screws to
more than 4.5 Nm.

ch34f3heat -- 42 -- S0740 800 188/E080903/P52


IN--SERVICE INSPECTION AND TESTING
in accordance with IEC 60974--4.

General requirements
Qualification of test personnel
Tests of welding power sources can be hazardous and shall be carried out by an expert in
the field of electrical repair, preferably also familiar with welding, cutting and allied
processes.
Test conditions
Tests shall be carried out at an ambient air temperature between 10 °C and 40 °C on a dry
and cleaned welding power source.
Measuring instruments
The accuracy of measuring instruments shall be class 2.5 as a minimum, except for the
measurement of insulation resistance, where the accuracy of the instruments is not
specified but shall be taken into account for the measurement.
The voltmeter shall have an internal resistance of at least 1MÙ and indicate mean value.

Periodic inspection and test


Periodic inspection and test shall be carried out in accordance with manufacturers
instructions and local regulations. The periodic inspection and test consists of:

S Visual inspection, (see Visual inspection, page 44)


S Electrical test (see Electrical test, page 45)
The inspection and test shall be documented in a test report, (see Test report, page 48).

A signed and dated label shall be attached to the equipment after an approved test.

After repair, inspection and test


After repair, inspection and test shall be carried out according to manufacturers instructions
and local regulations. The after repair, inspection and test consists of:

S Visual inspection, (see Visual inspection, page 44)


S Electrical test (see Electrical test, page 45)
S Functional test (see Functional test, page 47)
The inspection and test shall be documented in a test report, (see Test report, page 48).

A signed and dated label shall be attached to the equipment after an approved test.

cz01_general -- 43 -- S0740 800 188/E080903/P52


Visual inspection

Disconnect the welding power source from the mains supply.


During visual inspection, each safety related function judged as relevant by the test
personnel, shall be checked for correct operation.
During visual inspection, the following listed items shall be checked:
1. Torch/electrode holder, welding current return clamp.
S missing or defective insulation
S defective connections
S defective, damaged switches
S other damage
2. Mains supply
S defective, damaged cable
S deformed, faulty plug
S broken or thermally damaged plug pins
S ineffective cable anchorage
S cables and plugs unsuitable for the intended use and performance
3. Welding circuit
S defective damaged cable
S deformed, faulty or thermally damaged coupler/sockets
S ineffective cable anchorage
S cables and coupler unsuitable for the intended use and performance
4. Enclosure
S missing or damaged parts
S unauthorised modifications
S cooling openings blocked or missing air filters
S signs of overload and improper use
S missing or defective protective covers
S missing or defective lifting means, holder etc
S conductive objects placed in the enclosure
5. Controls and indicators
S defective switches, meters and lamps
6. General condition
S poor legibility of markings and labelling
S other damage or signs of improper use

ch34_test -- 44 -- S0740 800 188/E080903/P52


Electrical test

1. Disconnect the welding power source from the mains supply.

2. Check continuity of the protective circuit.


Measure the resistance of the protective circuit from the screw (1) to
the protective earth connection in the the mains plug (2).
During the measurement the cable shall be bent, flexed and twisted
along the whole length in order to detect interuptions in the
protective conductor.
S Required value for cables up to 5 m, max 0.3 Ù.

3. Check the insulation resistance with an insulation tester with


the measurement voltage set to 500 VDC.
a. Turn the mains switch of the the welding power source to ON.
b. Measure from the supply pins in the mains plug (2) to the
welding outlets (3,4).
S Required value not less than 5 MÙ.
c. Measure from the welding outlets (3,4) to the protective earth connection in the
mains plug (2).
S Required value not less than 2.5 MÙ.
d. Measure from the supply pins in the mains plug (2) to the protective earth
connection in the mains plug (2).
S Required value not less than 2.5 MÙ.
e. Turn the mains switch of the the welding power source to OFF.

4. Check the no--load voltage.


Use the ESAB test box TB 1. If the welding power source has an activated VRD
function then proceed to step 5.
a. Connect the positive (3) and negative (4) welding outlets to the positive and
negative terminals (DCIN) of the TB 1.
b. Connect a voltmeter to VPEAK of the TB 1.
c. Connect the welding power source to the mains supply.
d. Turn the control knob of the TB 1 anti--clockwise to 0.2.
e. Turn the mains switch of the the welding power source to ON.
f. Set the welding current control on the welding power souce to maximum.
g. Slowly turn the control knob of the TB 1 clockwise from 0.2 to 5.2 while checking
the voltmeter for the highest value.
S Measured value shall not exceed the allowable value 113 VPEAK
h. Turn the mains switch of the the welding power source to OFF.
i. Disconnect the welding power source from the mains supply.

5. Check of no--load voltage with the VRD activated.


Use the ESAB test box TB 1. This test is only conducted when the VRD function is
activated.

ch34_test -- 45 -- S0740 800 188/E080903/P52


a. Connect the positive (3) and negative (4) welding outlets to the positive and
negative terminals (DCIN) of the TB 1.
b. Connect a voltmeter to VPEAK of the TB 1.
c. Connect the welding power source to the mains supply.
d. Turn the control knob of the TB 1 anti--clockwise to 0.2.
e. Turn the mains switch of the the welding power source to ON.
f. Set the welding current control on the welding power souce to maximum.
g. Check the voltage with the voltmeter.
S Measured value shall not exceed 35 V.
h. Check that the LED indicates active VRD function by a steady green light.
i. Turn the mains switch of the the welding power source to OFF.
j. Disconnect the welding power source from the mains supply.

Test box TB 1

Circuit diagram of the TB 1

ch34_test -- 46 -- S0740 800 188/E080903/P52


Functional test

1. Each safety related function judged as relevant by the test personnel shall be
checked for correct operation.
Conformity shall be checked by operating the device and by checking whether the
welding power source operates correctly.
2. Check the supply circuits on/off switching device

a. Disconnect the welding power source from the mains supply.


b. Remove the cover
c. Turn the mains switch of the the welding power source to OFF.
d. Measure from the supply pins of the mains plug to the EMC
board, 2AP1.
S Measure L1--CN2:3. Required value, open circuit
S Measure L2--CN2:1. Required value, open circuit
S Measure L3--CN2:5. Required value, open circuit
e. Turn the mains switch of the the welding power source to ON.
f. Measure from the supply pins in the mains plug to the EMC
board 2AP1.
S Measure L1--CN2:3. Required value, less than 0.5 Ù
S Measure L2--CN2:1. Required value, less than 0.5 Ù
S Measure L3--CN2:5. Required value, less than 0.5 Ù
g. Reassemble the cover.
3. Check signal and control lamps
Check the function of the display indicators by turning on the unit and visually check the
front panel.
The LED test starts with all LEDs dark, then the diodes are turned on and off, one at a
time, until all diodes have been tested. If the test detects a fault, no fault code will be
logged.
Then the display test is made in the same way as the LED test but for each segment of
the digits in the display. If the test detects a fault, no fault code will be logged.
Finally the software version of the welding data unit is displayed.
4. Check the function of the welding power source by welding.
5. Disconnect the welding power source from the mains supply.
6. Write the test report.
See Test report, page 48).
7. If the unit passes all the tests, attach appropriate label with signature and date of
the test.

ch34_test -- 47 -- S0740 800 188/E080903/P52


Test report

Company: Location:

Equipment: Arc welding power source Serial number:


Manufacturer: ESAB Type:
Testing equipment:

VISUAL INSPECTION PASSED


ELECTRICAL TEST Limit Measured values
Protective conductor resistance ≤ 0.3 Ω

Insulation resistance
Input circuit/ ≥ 5 MΩ
Welding circuit (500 VDC)
Welding circuit/ ≥ 2.5 MΩ
Protective circuit (500 VDC)
Input circuit/ ≥ 2.5 MΩ
Protective circuit (500 VDC)
No--load voltage
without VRD Vpeak
≤113 VDC

with VRD activated Vpeak


≤35 VDC

Electrical test PASSED


FUNCTIONAL TEST PASSED
Remarks

Date

Tested by Signature

Testing company

cz01_testreport -- 48 -- S0740 800 188/E080903/P52


INSTRUCTIONS
This chapter is an extract from the instruction manual for the Arc 251i.

SAFETY

CAUTION!
Read and understand the instruction manual before
installing or operating.

INSTALLATION

Location
Place the power source so that its cooling air inlets and outlets are not obstructed.

Mains power supply

Note!
Mains supply requirements
High power equipment may, due to the primary current drawn from the mains supply, influence the
power quality of the grid. Therefore connection restrictions or requirements regarding the
maximum permissible mains impedance or the required minimum supply capacity at the interface
point to the public grid may apply for some types of equipment (see technical data). In this case it
is the responsibility of the installer or user of the equipment to ensure, by consultation with the
distrubution network operator if necessary, that the equipment may be connected.

Make sure that the welding power source is connected to the correct supply voltage and
that it is protected by the correct fuse rating. A protective earth connection must be made in
accordance with regulations.

Recommended fuse sizes and minimum cable area

Mains voltage 400V


Mains cable area mm2 4 G 1.5
Phase current I1eff 8A
Fuse
anti--surge 10 A
type C MCB
10 A

NOTE!
The cable area and fuse rating above comply with Swedish regulations. Use the welding
power source in accordance with the relevant national regulations.

ch34i1 -- 49 -- S0740 800 188/E080903/P52


OPERATION

Connections and control devices

1 Mains voltage switch 4 Connection for remote control unit


2 Connection (+) 5 Control panel,
MMA: welding cable or return cable see separate instruction manual
TIG: return cable
3 Connection (--)
MMA: return cable or welding cable
TIG: torch

Overheating protection
The welding power source has overheating protection that operates if the temperature
becomes too high. When this occurs the welding current is interrupted and a fault code is
displayed on the control panel.
The overheating protection resets automatically when the temperature has fallen.

MAINTENANCE
Regular maintenance is important for safe, reliable operation.
Only those persons who have appropriate electrical knowledge (authorized personnel) may
remove the safety plates.

CAUTION!
All guarantee undertakings from the supplier cease to apply if the customer himself
attempts any work in the product during the guarantee period in order to rectify any faults.

ch34i1 -- 50 -- S0740 800 188/E080903/P52


Power source
Check regularly that the welding power source is not clogged with dirt.
How often and which cleaning methods apply depend on:

S the welding process


S arc times
S placement
S the surrounding environment.
It is normally sufficient to blow down the power source with dry compressed air (reduced
pressure) once a year.
Clogged or blocked air inlets and outlets otherwise result in overheating.

FAULT--TRACING
Try these recommended checks and inspections before sending for an authorized service
technician.

Type of fault Corrective action


No arc. S Check that the mains power supply switch is turned on.
S Check that the welding current supply and return cables are
correctly connected.
S Check that the correct current value is set.
S Check the mains power supply fuses.
The welding current is S Check whether the thermal cut--outs have tripped (a fault
interrupted during welding. code is displayed on the control panel).
S Check the mains power supply fuses.
The thermal cut--out trips S Make sure that you are not exceeding the rated data for the
frequently. welding power source (i.e. that the unit is not being
overloaded).
S Check that the welding power source is not clogged with dirt.
Poor welding performance. S Check that the welding current supply and return cables are
correctly connected.
S Check that the correct current value is set.
S Check that the correct electrodes are being used.

SPARE PARTS
The spare parts list is published in a separate document that can be downloaded from the
internet: www.esab.com
Product Filename
Arc 251i 0459 839 021

ch34i1 -- 51 -- S0740 800 188/E080903/P52


ESAB subsidiaries and representative offices

Europe NORWAY Asia/Pacific Representative offices


AUSTRIA AS ESAB BULGARIA
CHINA
ESAB Ges.m.b.H Larvik ESAB Representative Office
Tel: +47 33 12 10 00 Shanghai ESAB A/P
Vienna--Liesing Shanghai Sofia
Tel: +43 1 888 25 11 Fax: +47 33 11 52 03 Tel/Fax: +359 2 974 42 88
Tel: +86 21 5308 9922
Fax: +43 1 888 25 11 85 Fax: +86 21 6566 6622
POLAND EGYPT
BELGIUM ESAB Sp.zo.o. INDIA ESAB Egypt
S.A. ESAB N.V. Katowice ESAB India Ltd Dokki--Cairo
Brussels Tel: +48 32 351 11 00 Calcutta Tel: +20 2 390 96 69
Tel: +32 2 745 11 00 Fax: +48 32 351 11 20 Tel: +91 33 478 45 17 Fax: +20 2 393 32 13
Fax: +32 2 745 11 28 Fax: +91 33 468 18 80
PORTUGAL ROMANIA
THE CZECH REPUBLIC ESAB Lda INDONESIA ESAB Representative Office
ESAB VAMBERK s.r.o. Lisbon P.T. ESABindo Pratama Bucharest
Vamberk Tel: +351 8 310 960 Jakarta Tel/Fax: +40 1 322 36 74
Tel: +420 2 819 40 885 Fax: +351 1 859 1277 Tel: +62 21 460 0188
Fax: +420 2 819 40 120 Fax: +62 21 461 2929 RUSSIA
SLOVAKIA LLC ESAB
DENMARK ESAB Slovakia s.r.o. JAPAN Moscow
Aktieselskabet ESAB Bratislava ESAB Japan Tel: +7 095 543 9281
Herlev Tel: +421 7 44 88 24 26 Tokyo Fax: +7 095 543 9280
Tel: +45 36 30 01 11 Fax: +421 7 44 88 87 41 Tel: +81 3 5296 7371
Fax: +45 36 30 40 03 Fax: +81 3 5296 8080 LLC ESAB
SPAIN St Petersburg
FINLAND ESAB Ibérica S.A. MALAYSIA Tel: +7 812 336 7080
ESAB Oy Alcalá de Henares (MADRID) ESAB (Malaysia) Snd Bhd Fax: +7 812 336 7060
Helsinki Tel: +34 91 878 3600 Selangor
Tel: +358 9 547 761 Fax: +34 91 802 3461 Tel: +60 3 8027 9869
Fax: +358 9 547 77 71 Fax: +60 3 8027 4754 Distributors
SWEDEN For addresses and phone
FRANCE ESAB Sverige AB SINGAPORE numbers to our distributors in
ESAB France S.A. Gothenburg ESAB Asia/Pacific Pte Ltd other countries, please visit our
Cergy Pontoise Tel: +46 31 50 95 00 Singapore home page
Tel: +33 1 30 75 55 00 Fax: +46 31 50 92 22 Tel: +65 6861 43 22
www.esab.com
Fax: +33 1 30 75 55 24 ESAB international AB Fax: +65 6861 31 95
Gothenburg
GERMANY Tel: +46 31 50 90 00 SOUTH KOREA
ESAB GmbH Fax: +46 31 50 93 60 ESAB SeAH Corporation
Solingen Kyungnam
Tel: +49 212 298 0 SWITZERLAND Tel: +82 55 269 8170
Fax: +49 212 298 218 ESAB AG Fax: +82 55 289 8864
Dietikon
GREAT BRITAIN Tel: +41 1 741 25 25 UNITED ARAB EMIRATES
ESAB Group (UK) Ltd Fax: +41 1 740 30 55 ESAB Middle East FZE
Waltham Cross Dubai
Tel: +44 1992 76 85 15 North and South America Tel: +971 4 887 21 11
Fax: +44 1992 71 58 03 Fax: +971 4 887 22 63
ARGENTINA
ESAB Automation Ltd CONARCO
Andover Buenos Aires
Tel: +44 1264 33 22 33 Tel: +54 11 4 753 4039
Fax: +44 1264 33 20 74 Fax: +54 11 4 753 6313
BRAZIL
HUNGARY
ESAB S.A.
ESAB Kft
Contagem--MG
Budapest
Tel: +55 31 2191 4333
Tel: +36 1 20 44 182
Fax: +55 31 2191 4440
Fax: +36 1 20 44 186
CANADA
ITALY ESAB Group Canada Inc.
ESAB Saldatura S.p.A. Missisauga, Ontario
Mesero (Mi) Tel: +1 905 670 02 20
Tel: +39 02 97 96 81 Fax: +1 905 670 48 79
Fax: +39 02 97 28 91 81
MEXICO
THE NETHERLANDS ESAB Mexico S.A.
ESAB Nederland B.V. Monterrey
Amersfoort Tel: +52 8 350 5959
Tel: +31 33 422 35 55 Fax: +52 8 350 7554
Fax: +31 33 422 35 44
USA
ESAB Welding & Cutting Products
Florence, SC
Tel: +1 843 669 44 11
Fax: +1 843 664 57 48

ESAB AB
SE-- 695 81 LAXÅ
SWEDEN
Phone +46 584 81 000

www.esab.com

070514

Вам также может понравиться