Академический Документы
Профессиональный Документы
Культура Документы
Battery banks for switchgear and control applications are made up of many cells.
These cells are typically wired in series to achieve a desired voltage and may also be
wired in parallel to achieve additional ampere capacity. Sizing of these battery banks,
therefore, includes selecting the number and type of cells to be used.
The terminal voltage per cell varies with the battery's chemical composition. The
required number of series wired cells to achieve the more common DC control
voltages for switchgear control is shown in Table 1. Selection of the type of cell is
based on the required peak ampere output and total Ampere-hour (Ah) output
capacity for the load and duration.
Load type
The duty cycle imposed on switchgear batteries usually consists of momentary high
ampere loading during charging of the respective tripping or closing springs, in
addition to the small continuous load of powering protective relays and lights.
While both motors for charging the tripping and closing springs can be DC, the more
common switchgear design uses an AC closing motor and a DC tripping motor. Such
a design reduces the total DC load because tripping is of the utmost importance —
particularly when a fault occurs. However, this only allows one full operational cycle
following a power failure because there is no AC to charge the closing spring.
Sizing battery banks for switchgear and control applications is commonly performed
using software designed specifically for that purpose. Just input the required load
profile, and the program selects the optimum battery configuration. Although this is
quite simple, an engineer should be capable of performing a straightforward hand
calculation — either to confirm the results of a software-generated solution or to
serve as an accurate design for a simple battery system.
Do you know how to perform these calculations by hand? If not, then read on. This
article will help you understand the basic premise of sizing switchgear battery
systems and provide an example calculation for clarification of the concept. IEEE
Standard 485-1997, “Recommended Practice for Sizing Lead-Acid Batteries for
Stationary Applications,” also provides detailed guidelines for battery sizing.
Number of cells
Battery banks for switchgear and control applications are made up of many cells.
These cells are typically wired in series to achieve a desired voltage and may also be
wired in parallel to achieve additional ampere capacity. Sizing of these battery banks,
therefore, includes selecting the number and type of cells to be used.
The terminal voltage per cell varies with the battery's chemical composition. The
required number of series wired cells to achieve the more common DC control
voltages for switchgear control is shown in Table 1. Selection of the type of cell is
based on the required peak ampere output and total Ampere-hour (Ah) output
capacity for the load and duration.
Load type
The duty cycle imposed on switchgear batteries usually consists of momentary high
ampere loading during charging of the respective tripping or closing springs, in
addition to the small continuous load of powering protective relays and lights.
While both motors for charging the tripping and closing springs can be DC, the more
common switchgear design uses an AC closing motor and a DC tripping motor. Such
a design reduces the total DC load because tripping is of the utmost importance —
particularly when a fault occurs. However, this only allows one full operational cycle
following a power failure because there is no AC to charge the closing spring.
Sizing guidelines
Since the momentary load on a switchgear battery bank is much higher than the
continuous load, the required 1-minute (peak) ampere rate typically determines the
battery cell type. However the Ampere-hour rate should also be checked. The battery
cell type that meets the worst-case condition between the two should be selected.
These rates are tabulated in the manufacturer's standard literature at several final
voltages. Use the rates published at a final voltage of 1.75 volts-per-cell for lead acid
cells or 1.14 volts-per-cell for nickel cadmium cells. As an example, the data in Table
2 on page 43 is excerpted from a manufacturer's Web site. (The model designations
are fictitious.)
To calculate the required 1-minute ampere rate, assume the peak rate to be equal to
the sum of the loads (i.e. in-rush current for all breaker charging motors, load
currents for all relays and other loads, and ignore pilot lights).
Although momentary loads usually exist for much less than a minute — perhaps only
a fraction of a second — it is common practice to use the full ampere value for an
entire minute. Assign a required 1-minute rate equal to this peak rate divided by the
ambient temperature derating factor, the battery aging factor, and a design margin as
listed in Table 3 on page 43.
To calculate the required Ampere-hour rate, compute the average continuous load
and divide by the ambient temperature-derating factor and battery-aging factor, as
listed in Table 3. Use the manufacturer's data to select the battery cell type that
meets both the ampere and Ampere-hour requirements.
Sample calculation
To use a hypothetical real-world example, calculate the battery size for the 69kV
substation loads listed in Table 4. The battery type shall be lead acid, operate the
given loads for 8 hours at 125VDC, and be housed in a climate-controlled building.
As can be seen in Table 4, the peak discharge rate is 96.2A. Divide this number by an
ambient temperature factor of one for a 77°F room, by a 0.8 battery-aging factor, and
by 0.85 for the design margin.
As can be seen in Table 5, the total Ampere-hour rate is 27.1 Ah. Divide by an
ambient temperature factor of one for a 77°F room, and by a 0.8 battery-aging factor.
Back to basics
So whether you're one of those people that refuses to trust a computer farther than
you can throw it — or you simply feel more comfortable double checking calculations
by hand — possessing the knowledge to size battery banks for switchgear the old-
fashioned way is a good skill for any engineer to master. Not only will you impress
your peers, but you'll also feel more confident about recommending a rock solid
switchgear solution.
Load Definition
Loads are classified as:
Typical Loads
Note: commonly momentary loads are assumed to last for 1 minute during battery sizing calculations.
The standard recommends a duty cycle be drawn showing the anticipated loads (in [[Ampere]] or
power) for the required duration of battery backup time.
IEEE 485 Std. Recommended Practice for Sizing Lead Acid Batteries for Stationary Applications -
Typical Duty Cycle
Considerations
loads and times where known should be shown
random loads should be shown at the most critical times
The minimum battery voltage is the minimum system voltage (including voltage drops across
cables). Given the minimum cell voltage the minimum cell voltage is given by:
Temperature Correction - at temperature decreases the capacity of a cell decreases (and vise verse
as the temperature increases). Manufacturers quote cell capacity at a given temperature and
appropriate correction factors should be used for other temperatures.
Aging Factor - battery performance is relatively stable through out its life, dropping of rapidly towards
the end. To ensure the battery can meet the design requirements throughout its life the standard
suggestions the initial capacity should be 125% of the design capacity.
Design Margin - to cater for unexpected circumstances (increased loads, poor maintenance, recent
discharge, etc.) it is common to allow a design margin of 10% to 15%.
Where S can be any integer from 1 to N depending on the section being calculated and FS is
expressed in watt-hours or ampere-hours depending on which Ct is used.
The required uncorrected cell size F, is then given by:
where:
Term Rt
The term Rt is the number of amperes each plate can supply for t minutes, at 25oC to a defined
minimum cell voltage.
giving:
Term Kt
The term Kt is the ratio of ampere-hour capacity, at a standard time rate, at 25oC and to a defined
minimum voltage which can be delivered for t minutes.
giving: