Вы находитесь на странице: 1из 9

398 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 37, NO.

2, MARCH/APRIL 2001

The Effects of Very-High-Resistance Grounding


on the Selectivity of Ground-Fault Relaying in
High-Voltage Longwall Power Systems
Thomas Novak, Senior Member, IEEE

Abstract—With the advent of high-voltage (greater than 1 kV) Paragraph 18.47 (d) (3) of Title 30, Code of Federal Regu-
utilization circuits on longwall mining equipment in the late 1980s, lations, permits alternating-current machines to have nameplate
the Mine Safety and Health Administration (MSHA) initially ratings up to 4160 V if all high-voltage switchgear are remotely
required maximum ground-fault current limits of 3.75 A for
4160-V systems and 6.5 A for 2400-V systems. (It should be noted located and operated by remote control. However, the use of
that the Code of Federal Regulations defines low voltage, medium high voltage (greater than 1 kV) to power face equipment still
voltage, and high voltage for mine power systems as 0–660 V, requires approval from the MSHA to modify the application of
661–1000 V, and greater than 1000 V, respectively.) Ground-fault Paragraph 75.1002 of Title 30, Code of Federal Regulations,
relay pickup settings were not permitted to exceed 40% of the which states:
maximum ground-fault current. Shortly thereafter, the MSHA
began, and presently continues, requiring a much lower maximum Trolley wires and trolley feeder wires, high-voltage ca-
ground-fault current limit of 1.0 A, or even 0.5 A, with ground-trip bles and transformers shall not be located in mining termi-
settings of 100 mA. Shielded cables, which have significantly more
capacitance than their unshielded counterparts, are required for
nology by the last open crosscut and shall be kept at least
high-voltage applications in the mining industry. In an earlier 150 ft from pillar workings.
paper, the author showed that with the long cable runs of a To obtain approval from the MSHA, the mine operator must
high-voltage longwall system, capacitive charging currents could
easily exceed grounding-resistor currents under ground-fault formally submit a 101-c Petition for Modification and show that
conditions. As a result, overvoltages from inductive–capacitive a proposed alternative method will at all times guarantee no less
resonance effects can occur. Because of the large system capac- than the same measure of protection afforded by the existing
itance and low ground-trip setting, the relay selectivity of the standards. To ensure that the high-voltage systems maintain or
ground-fault protection system may also be compromised. There- exceed the same level of safety as medium-voltage systems, the
fore, an analysis of a typical 4160-V longwall power system that
utilizes very-high-resistance grounding (ground-resistor-current MSHA developed criteria for high-voltage face equipment to
limit of 0.5 A) is performed to determine if potential problems supplement existing regulations [4].
exist with the selectivity of ground-fault relaying. One MSHA criterion deals with maximum ground-fault
Index Terms—Ground-fault relaying, high-resistance ground- current. MSHA expressed a concern with limiting the amount
ing, longwall mining. of energy dissipated in an explosion-proof enclosure during a
ground fault. Title 30, Code of Federal Regulations, requires
I. INTRODUCTION that maximum ground-fault current be limited to 25 A for low-
and medium-voltage circuits. However, the industry adopted a

T HE power requirements of high-capacity longwall sys-


tems have significantly increased in recent years, such that
the combined horsepower for the face equipment can exceed
more conservative 15-A limit. As a result, the maximum power
that can be dissipated by the neutral grounding resistor, during
a ground fault, for a nominal 1040-V system is 9 kW. Using
5000 hp. The past practice of using 995 V as the utilization this 9-kW value, the MSHA then established the maximum
voltage proved inadequate for these high-capacity applications. ground-fault current limits of 6.5 A for 2400-V systems and
Excessive three-phase and line-to-line fault currents, massive 3.75 A for 4160-V systems [5]. However, these values have
cable sizes, reduced motor torque from excessive voltage drop, since been lowered to 1.0 and 0.5 A, respectively. These lower
and difficulty in maintaining the maximum instantaneous trip values were readily adopted by the mining industry and used
settings allowed by the Mine Safety and Health Administration with ground-fault relay pickup settings of 100 mA.
(MSHA) [1]–[3] have necessitated the use of high voltage, The application of very sensitive ground-fault protection
namely, 2400 and 4160 V. in underground coal mines was demonstrated in the early
1980s [6]–[8], but its application was directed toward pre-
Paper PID 00–24, presented at the 1999 Industry Applications Society Annual venting ventricular fibrillation and was limited to low- and
Meeting, Phoenix, AZ, October 3–7, and approved for publication in the IEEE medium-voltage utilization circuits. The author is unaware of
TRANSACTIONS ON INDUSTRY APPLICATIONS by the Mining Industry Committee
of the IEEE Industry Applications Society. Manuscript submitted for review any studies that document improved safety with the 1- or 0.5-A
October 15, 1999 and released for publication January 3, 2000. limits of high-voltage utilization circuits. The rationale appears
The author is with the Department of Civil and Environmental En- to be: the lower the ground-fault current, the better. However,
gineering, University of Alabama, Tuscaloosa, AL 35487 USA (e-mail:
tnovak@coe.eng.ua.edu). a point of diminishing returns occurs, as the fault current is
Publisher Item Identifier S 0093-9994(01)02120-X. limited. Reference [5] shows that a typical 4160-V longwall
0093–9994/01$10.00 ©2001 IEEE
NOVAK: GROUND-FAULT RELAYING IN HIGH-VOLTAGE LONGWALL POWER SYSTEMS 399

Fig. 1. Ungrounded system and equivalent circuit.

system begins to adopt the characteristics of an ungrounded Fig. 2. Resistance-grounded system and equivalent circuit.
system, and significant overvoltages can occur under resonant
ground-fault conditions. Another problem that may occur is reactance of the fault to the total capacitive reactance of the
the loss of selectivity with ground-fault relaying. Therefore, system. It is obvious from Fig. 1 that the highest overvoltage
the intent of this paper is to present an analysis of ground-fault will occur at system resonance, where the magnitudes of the two
relaying selectivity for a typical 4160-V longwall power reactances are equal. At resonance, overvoltages of 20 normal
system. Computer simulations are used for the analysis. can be reached. Substantial overvoltages can also be developed
by intermittent or sputtering ground faults, which are discussed
in detail in [10].
II. GROUNDING SYSTEM CHARACTERISTICS
The common grounding classifications found in industrial B. Solidly Grounded System
power systems are ungrounded, solidly grounded, and resistance The neutral point of a solidly grounded system is connected
grounded, although variations of these methods also occur [9]. to ground through no intentional impedance. A line-to-ground
Even though this paper deals with high-resistance grounding, fault results in a high current, which can easily be detected by
the features of all three systems will be briefly described since protective circuitry and isolated quickly. However, since there
high-resistance grounding can exhibit some of the characteris- is no intentional impedance in the neutral connection, a very
tics of the other two systems. high ground-fault current, which may be capable of exploding
protective enclosures, starting fires, and causing flash hazards,
A. Ungrounded System can occur. Overvoltage control is a major advantage of this
With the ungrounded system, there is no intentional connec- system, because the system neutral is solidly referenced to
tion between any part of the electrical system and ground. How- ground. Placing a short circuit around the system capacitance
ever, the term ungrounded is a misnomer because each line of in the single-phase equivalent circuit of Fig. 1 can represent a
the system is actually coupled to ground through the inherent simplified, solidly-grounded equivalent circuit.
per-phase capacitance of the cables, transformer windings, and
motor windings. Fig. 1 is a simplified representation of an un- C. Resistance-Grounded System
grounded system, which illustrates the capacitive coupling to The resistance-grounded system can be considered a compro-
ground. The cited advantage of this type of system is that the mise between the ungrounded and solidly grounded systems.
first fault between a line conductor and ground does not cause Resistance grounding is established by inserting a resistor be-
circuit interruption, thus there is no loss of power that can dis- tween the system neutral and ground [11], [12]. Thus, the max-
rupt continuous type processes. However, the capacitive cou- imum ground-fault current is controlled by the ohmic value of
pling can subject the ungrounded system to dangerous overvolt- the resistor, provided the resistor current is significantly greater
ages from intermittent ground faults and resonant effects due to than the system capacitive charging current. Fig. 2 is a simplified
ground faults through high inductive reactances [9], [10]. Thus, representation of a resistance-grounded system. The lower fault
ungrounded systems are generally considered to be susceptible current requires additional protective relaying, but practically
to insulation failures. eliminates arcing and flashover dangers, while limiting the am-
The connection of an inductive reactance between line and plitude of overvoltages. High-resistance grounding can be ap-
ground can produce serious overvoltages with respect to ground. plied where immediate service interruption, on the first ground
The degree of overvoltage is dictated by the ratio of the inductive fault, is to be avoided. However, this is not an issue in the mining
400 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 37, NO. 2, MARCH/APRIL 2001

Fig. 3. General arrangement diagram for a typical 4160-V longwall power system.

industry because ground-fault protection is required to react in- lays in the motor starting unit. Zero-sequence relays provide ex-
stantaneously, or after a short time delay when relay coordina- tremely sensitive ground-fault protection, with a typical pickup
tion is necessary. Instead, high-resistance grounding is required of 100 mA [13], [14]. With zero-sequence relaying, a single
in underground coal mining because it limits the amount of en- window-type current transformer (CT) is used as the current
ergy dissipated and controls the elevation of frame potentials, sensor. The three phase conductors pass through the core of the
during a ground fault. CT and make up its primary, while the grounding conductor re-
Standard practice requires high-resistance grounding to be mains outside of the CT window. Therefore, the resultant CT
designed so that the capacitive charging current of the system secondary current is proportional to the phasor sum of the three
is less than or equal to the resistor current under a ground-fault phase currents. Under normal conditions, with no ground cur-
condition. The intent of this practice is to prevent the system rent, the magnetic fields of the three phase currents sum to zero,
from developing some of the undesirable characteristics of an and no current flows in the secondary of the CT, but if a ground-
ungrounded system mentioned above. Fig. 2 illustrates how a fault occurs, current has a return path external to the CT core,
high-resistance-grounded system approaches an ungrounded thus resulting in an unbalanced situation. The imbalance in the
system as the ohmic value of the grounding resistor increases. line currents creates a resultant magnetic field that induces a cur-
Shielded cables, which have significantly more capacitance rent in the CT secondary, proportional to the ground-fault cur-
than unshielded cables, are required for high-voltage applica- rent. In other words, currents that originate in a particular cir-
tions in the mining industry. Thus, with the long cable runs cuit must return through that circuit, otherwise, the circuit’s CT
associated with 4160-V longwalls, the effects of system capaci- will detect the current differential and initiate a trip signal if the
tance become very pronounced. Reference [5] shows that, with CT’s output exceeds the trip setting for the ground-fault relay.
a typical 4160-V longwall power system, the magnitude of the Along these same lines, the inherent system capacitance for
system charging current significantly exceeds the magnitude a high-voltage longwall provides many paths for ground-fault
of the grounding-resistor current (by an approximate factor of current to return to the source other than the neutral grounding
seven) under a ground-fault condition. These same capacitive resistor. As a result, ground-fault current that originates in one
currents may cause erroneous tripping of circuits other than circuit can return to the source through the inherent capaci-
the faulted circuit, thus compromising ground-fault relaying tance of the other circuits. Since these currents return in circuits
selectivity. from which they did not originate, their ground-fault relays er-
roneously detect ground-faults in the associated circuits. If the
III. GROUND-FAULT RELAYING resultant currents exceed the trip settings, relay selectivity is de-
feated.
Individual ground-fault relays protect each outgoing circuit of
the motor starting unit, as well as the two parallel feeder cables
connecting the power center with the motor starting unit (Fig. 3). IV. ANALYSIS
The ground-fault relay in the power center has a time delay An analysis was performed on a typical 4160-V longwall
(up to 250 ms) to allow coordination with the downstream re- power system that utilizes very-high-resistance grounding
NOVAK: GROUND-FAULT RELAYING IN HIGH-VOLTAGE LONGWALL POWER SYSTEMS 401

Fig. 4. Simplified simulation model for a 4160-V longwall power system.

(grounding-resistor-current limit of 0.5 A), as shown in Fig. 3. the starting and stopping of the longwall face equipment. The
This diagram shows a 5-MVA power center, which steps down power ratings of face equipment and the cable lengths and sizes
the 13.8-kV distribution voltage to the 4160-V utilization are also shown in Fig. 3. A monorail cable handling system
voltage and to the 480-V auxiliary voltage. The power center supports the cables connecting the motor-starting unit with the
feeds the 4160-V motor-starting unit, which, in turn, controls face equipment. All high-voltage cables are 5-kV SHD type
402 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 37, NO. 2, MARCH/APRIL 2001

Fig. 5. Actual ground-fault current and grounding-resistor current for a fault in the crusher circuit with the 0.5-A current limit.

G-GC. The master controller is located near the longwall face tral grounding resistor (NGR) is shown connected between the
equipment and controls the motor-starting unit by means of a system neutral and ground.
programmable logic controller (PLC) and data highway cable. The equipment cables are represented as lumped impedances
Zero-sequence ground-fault protection is located in both the connected in a configuration. Cable resistances and induc-
motor-starting unit and the power center. In an attempt to pro- tances are based on the cable’s size and length [15]. The system
vide selective tripping, all outgoing circuits in the motor-starting capacitance of the model is only due to the cables; capacitances
unit have instantaneous ground-fault protection. Ground-fault from transformer and motor windings were ignored. Although
protection is also provided in the power center and generally capacitance is distributed along the cable’s entire length, the
has a time delay up to a maximum of 250 ms to provide coordi- cable capacitance is lumped and connected from line to ground
nation with the protection in the motor starting unit. at the beginning and end of each cable for simplicity. Cable ca-
pacitance per unit length was obtained from a cable manufac-
turer [16]. Each motor is modeled with three wye-connected
A. Model
impedances. These impedances are sized to reflect rated con-
The circuit model of Fig. 4 was constructed for performing ditions with typical power factors and efficiencies.
the simulations. Some liberties were taken to simplify the
model, but sufficient detail exists to determine whether or not B. Simulation Results
potential problems exist. The model consists of the longwall
equipment motors, power transformer, neutral grounding Simulations were performed with a bolted line-to-ground
resistor, and associated cables. All circuits are assumed to be fault at the terminals of the crusher motor, first with a
energized and operating at rated load. The hydraulic-pump grounding-resistor-current limit of 0.5 A, and then with a
motor circuit and the two parallel-connected 250-kcmil feeder 3.75-A limit. Figs. 5–7 show the simulation results for the
cables, between the power center and the motor starting unit, 0.5-A limit, while Figs. 8–10 present the same information
were not included to simplify the model. Also, ground paths for the 3.75-A limit. The circuit in Fig. 4 was simulated using
through equipment frames are not modeled. OrCad’s PSpice version 8.
The secondary of the power center transformer is modeled To establish a 0.5-A current limit, the value of the neutral
as three voltage sources with series impedances connected in grounding resistor was set at k . A simulation was then
a wye configuration. The voltage sources represent the three- performed for a ground fault at the terminals of the crusher
phase line-to-neutral voltages (2400 V) and are 120 out of motor with all six motors online. Fig. 5 shows that the actual
phase with each other. The series impedances are based upon (total) ground-fault current significantly exceeds the current
a 5% transformer impedance with an ratio of 4. The neu- through the grounding resistor. The total fault current leads
NOVAK: GROUND-FAULT RELAYING IN HIGH-VOLTAGE LONGWALL POWER SYSTEMS 403

Fig. 6. Actual ground-fault current and the current detected by the GF relay in the crusher circuit for the 0.5-A limit.

Fig. 7. Currents detected by the GF relays in the shearer and stage loader circuits for a fault in the crusher circuit for the 0.5-A limit.

the grounding-resistor current by approximately 90 , since current. The detected current is slightly less than the actual
the total fault current primarily consists of capacitive charging current. The small difference between the two currents is due
current. Fig. 6 shows the current detected by the ground-fault to the current that returns to the section transformer through
relay in the crusher circuit, along with the actual (total) fault the inherent capacitance of the crusher’s trailing cable. The
404 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 37, NO. 2, MARCH/APRIL 2001

Fig. 8. Actual ground-fault current and grounding-resistor current for a fault in the crusher circuit with the 3.75-A limit.

Fig. 9. Actual ground-fault current and the current detected by GF relay in the crusher circuit for the 3.75-A limit.

crusher’s ground-fault relay does not detect this current because while 0.5 A returns through the neutral grounding resistor.
it returns to the source back through the crusher’s CT window. Fig. 6 shows that the ground-fault relay in the crusher circuit
The remainder of the actual ground-fault current returns to the will detect approximately 3.2-A . With a pickup setting of
source through the system capacitance of the other five circuits, 100 mA, there is no question that the relay will be activated.
NOVAK: GROUND-FAULT RELAYING IN HIGH-VOLTAGE LONGWALL POWER SYSTEMS 405

Fig. 10. Currents detected by the GF relays in the shearer and stage loader circuits for a fault in the crusher circuit for the 3.75-A limit.

Fig. 7 shows the currents detected by the ground-fault relays in V. CONCLUSIONS


the shearer (approximate 840 mA) and stage-loader (approx-
imately 440 mA) circuits. Since ground-fault protection for With high-voltage (greater than 1 kV) longwall utilization cir-
each of the six motor circuits is set for instantaneous operation cuits, the MSHA initially required a maximum ground-fault re-
at a 100-mA pickup, it is likely that the other circuits will also sistor-current limit of 3.75 A and a maximum pickup setting of
1.5 A for 4160-V systems. However, these values have been sub-
trip. Therefore, the simulation shows that low pickup settings
sequently reduced to 0.5 A and 100 mA, respectively. Standard
with high system capacitance defeat the selectivity aspect of
practice in other industries requires high-resistance grounding
the ground-fault protection system.
to be designed so that the capacitive-charging current of the
The same simulation was then performed with a 3.75-A
system is less than or equal to the grounding-resistor current
current limit. For this current limit, the value of the neutral
under a ground-fault condition. Simulations in [5] showed, with
grounding resistor was adjusted to 640 . Also, the pickup
a typical 4160-V system with all motors online, that the mag-
setting of the ground-fault relays was assumed to be 1.5 A
nitude of the system charging current could be over 7 that
(40% of maximum grounding resistor current). As expected,
of the grounding resistor. The simulations further revealed that
Fig. 8 shows that the difference between the actual (total)
these lower values might cause detrimental effects, such as over-
ground-fault current and the grounding-resistor current has
voltage problems, since the system begins to acquire the char-
been reduced markedly. The total fault current leads the
acteristics of an ungrounded system.
grounding-resistor current by approximately 45 , since the
The analysis in this paper revealed that the MSHA’s more-
total fault current consists of approximately equal magnitudes
of grounding-resistor current and capacitive charging current. stringent requirements could also have a negative impact on
Fig. 9 shows the current detected by the ground-fault relay in ground-fault relaying. Simulations showed that the high system
the crusher circuit, along with the actual (total) fault current. capacitance, because of shielded cables, in conjunction with
Again, the detected current is slightly less than the actual cur- very-low ground-fault pickup settings could defeat relaying se-
rent because of the capacitance within the crusher circuit. Fig. 9 lectivity. The simulations verified that a ground fault in one
shows that the ground-fault relay in the crusher circuit will motor circuit could produce erroneous tripping in other circuits
detect approximately 4.8-A , which is significantly greater because of the large capacitive-charging currents that return to
than the 1.5-A pickup. Fig. 10 shows the currents detected the power-center transformer through the inherent system ca-
by the ground-fault relays in the shearer (approximately 0.85 pacitance of all online circuits. The simulations also showed that
A) and stage-loader (approximately 0.45 A) circuits. Both of these selectivity problems could be avoided if the MSHA’s orig-
these values are well below the 1.5-A pickup setting. Thus the inal requirements were used.
simulation illustrates that selectivity can be maintained with In conclusion, the analysis reveals that, in addition to the po-
the MSHA’s original requirements. tential problems documented in [5], reducing the grounding-re-
406 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 37, NO. 2, MARCH/APRIL 2001

sistor-current limit from 3.75 to 0.5 A and the maximum pickup [12] J. R. Dunki-Jacobs Jr, “The reality of high-resistance grounding,” IEEE
settings from 1.5 A to 100 mA has the detrimental effect of de- Trans. Ind. Applicat., vol. 13, pp. 469–475, Sept./Oct. 1977.
[13] “Protection, prediction, monitoring, and electric safety,” The K-Tec
feating ground-fault relaying selectivity. Corp., Paoli, PA, sales literature for GFR 3000.
[14] “GFR 500—Sensitive ground-fault relay,” Precision Design, Inc., Bar-
REFERENCES boursville, WV, sales literature.
[15] Mining Cable Engineering Handbook, Anaconda Wire and Cable Co.,
[1] T. Novak and J. L. Kohler, “Technological innovations in deep coal Greenwich, CT, 1977, p. 69.
mine power systems,” IEEE Trans. Ind. Applicat., vol. 34, pp. 196–203, [16] M. Fuller, private communication, May 1998.
Jan./Feb. 1998.
[2] T. Novak and J. K. Martin, “The application of 4160-V to longwall face
equipment,” IEEE Trans. Ind. Applicat., vol. 32, pp. 471–479, Mar./Apr.
1996.
[3] L. A. Morley, T. Novak, and I. Davidson, “The application of 2400-V
to longwall face equipment,” IEEE Trans. Ind. Applicat., vol. 26, pp. Thomas Novak (M’83–SM’93) received the B.S.
886–892, Sept./Oct. 1990. degree in electrical engineering from The Pennsyl-
[4] C. M. Boring and K. J. Porter, “Criteria for approval of mining vania State University, University Park, the M.S.
equipment incorporating on-board switching of high-voltage circuits,” degree in mining engineering from the University
in Proc. 9th WVU Int. Mining Electrotechnology Conf., July 1988, pp. of Pittsburgh, Pittsburgh, PA, and the Ph.D. degree
267–274. in mining engineering from The Pennsylvania State
[5] T. Novak, “Analysis of very-high-resistance grounding in high-voltage University in 1975, 1978, and 1984, respectively.
longwall power systems,” IEEE Trans. Ind. Applicat., vol. 37, pp. He has been an Instructor of Mining Engineering at
104–111, Jan./Feb. 2001. The Pennsylvania State University, an Electrical En-
[6] T. Novak, L. A. Morley, and F. C. Trutt, “Sensitive Ground-Fault Re- gineer for the U.S. Bureau of Mines, Pittsburgh Re-
laying,” IEEE Trans. Ind. Applicat., vol. 24, pp. 853–861, Sept./Oct. search Center, and Assistant Division Maintenance
1988. Engineer for Republic Steel Corporation, Northern Coal Mines Division. He
[7] L. A. Morley, F. C. Trutt, and T. Novak, “Sensitive Ground-Fault is presently Department Head and holder of the Drummond Endowed Chair
Protection for Mines,” U.S. Bureau of Mines, Final Rep. for Contract of Civil Engineering at the University of Alabama, Tuscaloosa, where he has
JO134025, 1984. also held the positions of Interim Department Head of Aerospace Engineering
[8] T. Novak, L. A. Morley, and F. C. Trutt, “Analysis of ac mine power and Mechanics, Professor of Electrical Engineering, and Associate Professor of
systems for the application of sensitive ground-fault protection,” Min- Mineral Engineering.
eral Resources Eng., vol. 1, no. 1, pp. 51–66, 1988. Dr. Novak is a member of the IEEE Industry Applications Society (IAS) Ex-
[9] IEEE Recommended Practice for Electric Power Distribution for Indus- ecutive Board and is the current Chairman of its Meetings Department. He has
trial Plants, IEEE Std 141-1993. also served as Chairman of the IAS Process Industries Department (1994–1998),
[10] C. H. Titus, “Evaluation and feasibility study of isolated electrical dis- Chairman (1992–1994) and Vice-Chairman (1990–1992) of the IAS Mining
tribution systems in underground coal mines,” U.S. Bureau of Mines, Industry Committee, and Co-chairman of the IAS Mining Industry Technical
Final Rep. for Contract HO111465, 1972. Conference (1987). He is a member of the Society of Mining, Metallurgy, and
[11] B. Bridger Jr, “High-resistance grounding,” IEEE Trans. Ind. Applicat., Exploration, Inc. and the American Society of Civil Engineers. He is a Licensed
vol. 19, pp. 15–21, Jan./Feb. 1983. Professional Engineer in the States of Alabama and Pennsylvania.

Вам также может понравиться