Project Site :
BLOCK-AE
MADE BY : www.winntra.com
$ INPUT $ CALCULATION $ OUTPUT AS PER IS875-1987(REAFFIRMED 2003)
DEAD LOAD (DL)
Wt. of sheet&purline = 10.00 Kg/m² Gbale End MEZZANINE RCC AND DECK SHEET LOAD = 250.00 Kg/m²
Dead Load (DL) Spacing 7.66 = 0.77 KN/m 0.383 Dead Load (DL) = 19.34 KN/m
Dead Load (DL) Spacing 6.5 0.65 KN/m 0.325
COLLATERAL LOAD
Collateral Load on Rafter = 0.00 Kg/m² MEZZANINE LIVE OR UTILITY LOAD = 1000.00 Kg/m²
Collateral Load on Rafter 7.66 = 0.00 KN/m 0 LIVE LOAD LL = 77.36 KN/m
Collateral Load on Rafter 6.5 0.00 KN/m 0
LIVE LOAD (LL)
Live load/unit area, roof = 57.00 Kg/m² (As per MBMA 2012)
Live Load (LL) 7.66 = 4.37 KN/m 2.1831
Live Load (LL) 6.5 = 3.71 KN/m 1.8525
BUILDING DATA
LENGTH OF THE BUILDING 38.68 meters ROOF SLOPE 1 : 10
WIDTH OF THE BUILDING 23 meters WIND SPEED 47 m/s (As per Cl.5.3, IS:875 Part 3)
EAVE HEIGHT 12.8 meters TERRAIN CATEGORY 3 (As per Cl.5.3.2, IS:875 Part 3)
BAY SPACING 7.736 meters BUILDING CATEGORY B
5.34 2.93
2.93 5.34
52.5 15
525 150
262.5 75
6.60 LOAD 0.73 -0.73 LOAD -6.60 52.5 15
Y CASE 3 CASE 4
LOAD LOAD
CASE 5 CASE 6
Y -5.13 5.13 -2.20 2.20
* LEFT WALL 0.700 0.50 x0.9477x7.736= 3.67 kN/m (pressure) Seismic Load Condition
* LEFT ROOF -0.929 -1.13 x0.9477x7.736= -8.27 kN/m (suction) Seismic Zone V
* RIGHT ROOF -0.600 -0.80 x0.9477x7.736= -5.87 kN/m (suction) Seismic Zone Factor 0.36
* RIGHT WALL -0.300 -0.50 x0.9477x7.736= -3.67 kN/m (suction) Response reduction factor (RF) 5
* Importance Factor 1.5
* (-i) TRANSVERSE WIND SUCTION Soil Type Medium type
* GCPe (GCPe - GCPi) WIND LOAD
* LEFT WALL 0.700 0.90 x0.9477x7.736= 6.60 kN/m (pressure)
* LEFT ROOF -0.929 -0.73 x0.9477x7.736= -5.34 kN/m (suction)
* RIGHT ROOF -0.600 -0.40 x0.9477x7.736= -2.93 kN/m (suction)
* RIGHT WALL -0.300 -0.10 x0.9477x7.736= -0.73 kN/m (suction)
*
* (+i) LONGITUDINAL WIND PRESSURE
* GCPe (GCPe - GCPi) WIND LOAD
* LEFT WALL -0.500 -0.70 x0.9477x7.736= -5.13 kN/m (suction)
* LEFT ROOF -0.886 -1.09 x0.9477x7.736= -7.96 kN/m (suction)
* RIGHT ROOF -0.886 -1.09 x0.9477x7.736= -7.96 kN/m (suction)
* RIGHT WALL -0.500 -0.70 x0.9477x7.736= -5.13 kN/m (suction)
*
* (-i) LONGITUDINAL WIND SUCTION
* GCPe (GCPe - GCPi) WIND LOAD
* LEFT WALL -0.50 -0.30 x0.9477x7.736= -2.20 kN/m (suction)
* LEFT ROOF -0.89 -0.69 x0.9477x7.736= -5.03 kN/m (suction)
* RIGHT ROOF -0.89 -0.69 x0.9477x7.736= -5.03 kN/m (suction)
* RIGHT WALL -0.50 -0.30 x0.9477x7.736= -2.20 kN/m (suction)
CALCULATION OF EXTERNAL PRESSURE COEEFFICIENT ON PITCHED ROOFS
(AS PER IS-875 1987:PART 3 ;REAFFIRMED 2003)
α= 5.71
w (in meters) = 23
h/w = 0.6
ROOF ANGLE WIND ANGLE = 0 deg. WIND ANGLE = 90 deg.
α E F G H E F G H
5.71 -0.929 -0.929 -0.600 -0.600 -0.886 -0.600 -0.886 -0.600