LOAD CALCULATION SHEET

Project Site :
BLOCK-AE
MADE BY : www.winntra.com
$ INPUT $ CALCULATION $ OUTPUT AS PER IS875-1987(REAFFIRMED 2003)
DEAD LOAD (DL)
Wt. of sheet&purline = 10.00 Kg/m² Gbale End MEZZANINE RCC AND DECK SHEET LOAD = 250.00 Kg/m²
Dead Load (DL) Spacing 7.66 = 0.77 KN/m 0.383 Dead Load (DL) = 19.34 KN/m
Dead Load (DL) Spacing 6.5 0.65 KN/m 0.325
COLLATERAL LOAD
Collateral Load on Rafter = 0.00 Kg/m² MEZZANINE LIVE OR UTILITY LOAD = 1000.00 Kg/m²
Collateral Load on Rafter 7.66 = 0.00 KN/m 0 LIVE LOAD LL = 77.36 KN/m
Collateral Load on Rafter 6.5 0.00 KN/m 0
LIVE LOAD (LL)
Live load/unit area, roof = 57.00 Kg/m² (As per MBMA 2012)
Live Load (LL) 7.66 = 4.37 KN/m 2.1831
Live Load (LL) 6.5 = 3.71 KN/m 1.8525

BUILDING DATA
LENGTH OF THE BUILDING 38.68 meters ROOF SLOPE 1 : 10
WIDTH OF THE BUILDING 23 meters WIND SPEED 47 m/s (As per Cl.5.3, IS:875 Part 3)
EAVE HEIGHT 12.8 meters TERRAIN CATEGORY 3 (As per Cl.5.3.2, IS:875 Part 3)
BAY SPACING 7.736 meters BUILDING CATEGORY B

BUILDING PERMEABILITY CONDITION SMALL(OPENINGS <5%) (OF WALL AREA)


LOADING ON FRAME MEMBERS
(NOTE: ALL VALUES IN KN/m)

8.27 5.87 5.87 8.27

Y 3.67 LOAD 3.67 -3.67 LOAD -3.67


CASE 1 CASE 2

5.34 2.93
2.93 5.34
52.5 15
525 150
262.5 75
6.60 LOAD 0.73 -0.73 LOAD -6.60 52.5 15
Y CASE 3 CASE 4

7.96 7.96 5.03 5.03

LOAD LOAD
CASE 5 CASE 6
Y -5.13 5.13 -2.20 2.20

K1 K2 K3 INTERNAL PRESSURE CO-EFFICIENT


1.08 0.91 1.00 0.2
H/W 0.56 0.5<h/w≤1.5 GCpi
DESIGN WIND VELOCITY 46.38 m/s L/W 1.68 1.5<l/w≤4 -0.2
WIND PRESSURE 1.300
DESIGN PRESSURE Pz 0.948
kN/m²
Design wind pressure Pd = Kd. Ka. Kc . Pz
(As per Cl.5.4, IS:875 Part 3)
CLICK ON '+' ON THE LEFT TO VIEW ( STADD USER CAN COPY THE DETAILS SHOWN BELOW IN STADD EDITOR FOR REFERENCE) (As per Cl.6.2.2.1 & Cl.6.2.2.2, IS:875 Part 3)
* (+i) TRANSVERSE WIND PRESSURE
* GCPe (GCPe - GCPi) WIND LOAD

* LEFT WALL 0.700 0.50 x0.9477x7.736= 3.67 kN/m (pressure) Seismic Load Condition
* LEFT ROOF -0.929 -1.13 x0.9477x7.736= -8.27 kN/m (suction) Seismic Zone V
* RIGHT ROOF -0.600 -0.80 x0.9477x7.736= -5.87 kN/m (suction) Seismic Zone Factor 0.36
* RIGHT WALL -0.300 -0.50 x0.9477x7.736= -3.67 kN/m (suction) Response reduction factor (RF) 5
* Importance Factor 1.5
* (-i) TRANSVERSE WIND SUCTION Soil Type Medium type
* GCPe (GCPe - GCPi) WIND LOAD
* LEFT WALL 0.700 0.90 x0.9477x7.736= 6.60 kN/m (pressure)
* LEFT ROOF -0.929 -0.73 x0.9477x7.736= -5.34 kN/m (suction)
* RIGHT ROOF -0.600 -0.40 x0.9477x7.736= -2.93 kN/m (suction)
* RIGHT WALL -0.300 -0.10 x0.9477x7.736= -0.73 kN/m (suction)
*
* (+i) LONGITUDINAL WIND PRESSURE
* GCPe (GCPe - GCPi) WIND LOAD
* LEFT WALL -0.500 -0.70 x0.9477x7.736= -5.13 kN/m (suction)
* LEFT ROOF -0.886 -1.09 x0.9477x7.736= -7.96 kN/m (suction)
* RIGHT ROOF -0.886 -1.09 x0.9477x7.736= -7.96 kN/m (suction)
* RIGHT WALL -0.500 -0.70 x0.9477x7.736= -5.13 kN/m (suction)
*
* (-i) LONGITUDINAL WIND SUCTION
* GCPe (GCPe - GCPi) WIND LOAD
* LEFT WALL -0.50 -0.30 x0.9477x7.736= -2.20 kN/m (suction)
* LEFT ROOF -0.89 -0.69 x0.9477x7.736= -5.03 kN/m (suction)
* RIGHT ROOF -0.89 -0.69 x0.9477x7.736= -5.03 kN/m (suction)
* RIGHT WALL -0.50 -0.30 x0.9477x7.736= -2.20 kN/m (suction)
CALCULATION OF EXTERNAL PRESSURE COEEFFICIENT ON PITCHED ROOFS
(AS PER IS-875 1987:PART 3 ;REAFFIRMED 2003)

α= 5.71

h (in meters) = 12.8

w (in meters) = 23

h/w = 0.6
ROOF ANGLE WIND ANGLE = 0 deg. WIND ANGLE = 90 deg.
α E F G H E F G H
5.71 -0.929 -0.929 -0.600 -0.600 -0.886 -0.600 -0.886 -0.600

EXTERNAL PRESSURE COEEFFICIENT ON PITCHED ROOFS (AS PER TABLE 5 OF IS-875:PART 3)

ROOF WIND ANGLE = 0 deg. WIND ANGLE = 90 deg.


ANGLE(α) E F G H E F G H
0 -0.8 -0.8 -0.4 -0.4 -0.8 -0.4 -0.8 -0.4
5 -0.9 -0.9 -0.4 -0.4 -0.8 -0.4 -0.8 -0.4
10 -1.2 -1.2 -0.4 -0.4 -0.8 -0.6 -0.8 -0.6 FOR H/W <= 1/2
20 -0.4 -0.4 -0.4 -0.4 -0.7 -0.6 -0.7 -0.6
30 0 0 -0.4 -0.4 -0.7 -0.6 -0.7 -0.6
45 0.3 0.3 -0.5 -0.5 -0.7 -0.6 -0.7 -0.6
60 0.7 0.7 -0.6 -0.6 -0.7 -0.6 -0.7 -0.6
5.71 -0.943 -0.943 -0.400 -0.400 -0.800 -0.429 -0.800 -0.429

ROOF ANG WIND ANGLE = 0 deg. WIND ANGLE = 90 deg.


α E F G H E F G H
0 -0.8 -0.8 -0.6 -0.6 -1.0 -0.6 -1.0 -0.6
5 -0.9 -0.9 -0.6 -0.6 -0.9 -0.6 -0.9 -0.6
NOTE: 10 -1.1 -1.1 -0.6 -0.6 -0.8 -0.6 -0.8 -0.6
when wind acts in lateral direction of frame ( i.e 0 deg wind angle) 20 -0.7 -0.7 -0.5 -0.5 -0.8 -0.6 -0.8 -0.6 1/2 < H/W <= 3/2
*E & F falls on windward side & has same co-efficients 30 -0.2 -0.2 -0.5 -0.5 -0.8 -0.8 -0.8 -0.8
*G & H falls on leeward side & has same co-efficients 45 0.2 0.2 -0.5 -0.5 -0.8 -0.8 -0.8 -0.8
60 0.6 0.6 -0.5 -0.5 -0.8 -0.8 -0.8 -0.8
when wind acts in longitudinal direction of frame ( i.e 90 deg wind angle) 5.71 -0.929 -0.929 -0.600 -0.600 -0.886 -0.600 -0.886 -0.600
*E & G has same coefficients
*F & H has same co-efficients ROOF ANG WIND ANGLE = 0 deg. WIND ANGLE = 90 deg
α E F G H E F G H
the coefficients are assumed to act outwards i.e suction pressure 0 -0.7 -0.7 -0.6 -0.6 -0.9 -0.7 -0.9 -0.7
(as mentioned in clause 6.2.2.2 of IS 875) 5 -0.7 -0.7 -0.6 -0.6 -0.8 -0.8 -0.8 -0.8
10 -0.7 -0.7 -0.6 -0.6 -0.8 -0.8 -0.8 -0.8
20 -0.8 -0.8 -0.6 -0.6 -0.8 -0.8 -0.8 -0.8 3/2 < H/W < 6
co-efficients for the local effects are not used for calculating 30 -1.0 -1.0 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
40 -0.2 -0.2 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
force on structural elements(as mentioned in clause 6.2 of IS 875) 50 0.2 0.2 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
60 0.5 0.5 -0.5 -0.5 -0.8 -0.7 -0.8 -0.7
5.71 -0.700 -0.700 -0.600 -0.600 -0.800 -0.800 -0.800 -0.800
21000
180 116.6667
3780000
x y z
30 8.5 71.96