Академический Документы
Профессиональный Документы
Культура Документы
Generators are high quality machines and for securing the best possible continuity of power supply, in
addition to a suitable technical design and responsible mode of operation, provision should be made for
automatic protection facilities. The protective equipment serves for quick and selective detection of any
faults and for minimizing damage to electric apparatus during faults.
The protective equipment should be designed so that on occurrence of any serious fault the generator will
be disconnected from the system and de-excited immediately. Faults, which do not result in any direct
damage, are to be reported to the operating staff, permitting the unit to be operated outside the critical
range or to take precautionary measures for shutdown.
The generator protection can be broadly classified in two groups, the first one being the protection against
electrical faults and the second one protection against mechanical faults.
In certain cases the generator may also be included in the differential protection for the main transformer
and station service feeder, resulting in the detection of generator faults by two differential protection
devices.
The load resistance of an earthing transformer and any required boost to raise the neutral point potential
should be selected so that in the event of a fault the earth current will amount to less than 15A.
A momentary excursion beyond the steady state stability limit must not necessarily result in a loss of
stability. Therefore, it is advisable to design the under-excitation protection so that an alarm will be given on
reaching the steady-state stability limit, with shut down of the generator being effected after a delay of a
few seconds only.
For avoiding longer relay times, it is recommended to equip larger generators with an inverse- time lag
(impedance ) relay, which will be energised on over current and operate with long or short time setting
dependent on the location of the short circuit. If connected to the generator neutral point, the over-current
protection serves as back up protection for the differential protection.
It is recommended to provide a two stage load unbalance protection. When the continuously permissible
load unbalance is reached an alarm is given, while time-dependent tripping occurs when this value is
exceeded.
In case of large units, it is recommended to provide a protection with unbalanced load/time characteristic.
Operating value and relay time should be matched to the load unbalance/time characteristic applicable to
the particular generator.
For avoiding excessive magnetic and thermal stressing, it is recommended to provided an under-frequency
protection.
Since the frequency variation due to a system disturbance is normally accompanied by a voltage variation,
the protection should be designed on the basis of the permissible load characteristic of the generator on
frequency and voltage variations.
Faults in the turbine interior initiate emergency tripping, resulting in interruption of steam supply to the
turbine. A reliable criterion of perfectly tight closure of the emergency stop valves is the flow of power from
the system back into the generator.
Disconnection of the turboset from the system by the generator circuit breaker is only permissible after this
reverse power has been drawn by the generator.
Normally, the surge diverters are installed in the direct vicinity of the unit transformer, assuming that
switching surge resulting from any load isolator or circuit breaker arranged between generator and
transformer will not endanger the generator.
Care should be taken to provide explosion-proof surge diverters or suitable constructional measures in
order to avoid danger to persons or nearby plant components on over voltage.
The trip signals of these circuits only affect the turbine trip. The generator itself is then isolated from the
grid and de-excited by the reverse power protection or, if the turbine generator set is working in isolated
operation, by the under frequency protection.