MOUNTING
1. Any Switch box shown on the edge of the wall shall be
SYMBOL DESCRIPTION HEIGHT
200mm away from the edge unless other wise specified.
1
FROM FFL
2 2
W W The two way switch shown beside the door shall be
2.
STBR I.D.U. A / C 200mm away from the opened shutter of the door. CEILING FAN -----
1245
3.
EL +600 mm EXHAUST FAN WITH SOCKET AT 7'-8"HT
only after tile marking. Sockets has to be provided to EF
KITCHEN 2
FD match inline with either to the top corner or bottom RECESSED TYPE CEILING -----
TV(A)
TV
2
EC
1730 corner of the tile. (NOT in between tile joint). LIGHT FITTING
Connected in ONLINE UPS Circuit
4. Power point circuit wiring & light circuit wiring should
NOT be drawn in same conduit i.e Wiring for both shall FTL PATTI FITTING AT 7'-8"HT
1570
( WALL MOUNTED TYPE )
be drawn directly from the DB through Individual
2 wiring & conduit system,similarly two different phase FTL PATTI FITTING
( WALL MOUNTED TYPE ) AT 7'-8"HT
wires should Not be drawn in a same conduit.
D
BED ROOM 1 Connected in ONLINE UPS Circuit
2100
3 KW 3 W1 5. Also in a single circuit of same Phase where Two or WALL LIGHT FITTING AT 7'-8"HT
DINING 2 More SB's are Interlinked, The circuit wiring from WALL LIGHT FITTING
AT 7'-8"HT
1st SB to Subsequent SB's can be drawn through Connected in ONLINE UPS Circuit
2 2 same Light Point Conduiting. Otherwise from DB BULK HEAD FITTING AT 7'-8"HT
3 to First Switch Board for Lighting Circuit main
ONE WAY SWITCH AT 4'-0" HT
seperate wiring & conduiting to be laid.
V V ONE WAY SWITCH
POWDER AT 4'-0" HT
EL ±00 mm 6. For last Light points/Fan points/6A Socket outlets Connected in ONLINE UPS Circuit
4
ROOM TOILET
UP wherever maximum 4 nos wires are involved in such
cases 20mmØ conduit shall be used otherwise all other
TWO WAY SWITCH
Connected in ONLINE UPS Circuit
AT 4'-0" HT
places wherever morethan 4 nos wires are involved 6A SOCKET & SWITCH
2 IN SWITCH BOARD ( DEP )
AT 4'-0" HT
2 25mmØ conduit shall be used in the light points /
UP Fan points / 6A Sockets outlets wiring system. ELECTRIC BELL AT 4'-0" HT
EL +750 mm
7. For Individual Light Circuit Wiring & Power Circuit TELEPHONE OUTLET WITH
wiring 20mmØ conduit shall be used as indicated in 6A ( INDEP ) SWITCH WITH
TP(A)
COURTYARD
5
W1 TV AND TELEPHONE
TV(A)
12. For Television point Wiring, i.e,. 20mm dia conduit JUNCTION BOX AT 8'-0" HT
D
8
shall be used right from Apartment JB to TV Socket
4 BED ROOM 2 UPS DB AT 5'-6" HT
2 Outlets. ( looping of One TV PT to other subseqent
UP
1785
AT 8'-0" HT
necessary to be mounted in invisible location.
8
FD 1 x 28W FTL PATTI FITTING -----
UP
1245
UP A/C
8
EL +/- 0.0 mm TV TV