Flat Conductor Cable – 3 or more flat copper conductors placed edge to edge and separated
and enclosed within an insulating assembly.
Bottom Shield - The top protective layer installed between the floor and type FCC for
protection.
Top Shield - A grounded metal shield covering under-carpet components.
Cable Connector - Connector designed to join Type FCC without using a junction box.
FCC System - Complete wiring system for branch circuits design for installation under carpet
squares.
Insulating End - Insulator designed to electrically insulate the end of Type FCC.
Metal Shield Connections - Means of connection designed to electrically and mechanically
connect a metal shield to another metal.
Transition Assembly - Incorporated with electrical connection and a suitable box or covering
for safety.
• Branch Circuit Ratings
o Voltage – Ungrounded not exceed 300 volts, Grounded not exceed 150 volts.
o Current – General-Purpose and Appliance branch circuit not exceeding 20
amperes, Individual branch circuit not exceeding 30 amperes.
• Installation shall be permitted on the following condition:
o Floors – Hard, sound, smooth, continuous floor surface made of concrete,
ceramic, and woods
o Walls – in surface metal raceway
o Heated floors – Materials used in floors heated in excess of 30ºC.
o System Height – Above floor level exceeding 2.3 mm shall be tapered at the
edge of floor level.
o Coverings – Insulating end shall be covered with carpet squares not larger than
1000 mm.
• Securing and Supporting – All FCC system components shall be firmly anchored to
the floor or wall using an adhesive or mechanical anchoring system.
• Construction – shall consists of 3, 4 or 5 flat copper conductor, 1 for equipment
grounding conductor.
• Metal Components and Insulation – shall be corrosion resistant, moisture resistant
and flame retardant.
• Cable Markings – shall be clearly and durable marked on both sides at interval not
more than 610 mm with the information required.
Integrated Gas Spacer Cable – A factory assembly of one or more conductors, each
individually insulated and enclosed in a loose fit, nonmetallic flexible conduits as an
integrated gas spacer cable rated 0 through 600 volts.
• Bends – A run type IGS cable between pull boxes or termination shall not
contain more than the equivalent of 4 quarter bends ( 360º total).
• Fittings – The termination and splices for type IGS shall be suitable for
maintaining gas pressure within the conduit.
o Valve and Cap – shall be provided to check the gas pressure or to inject
gas into the conduit.
• Conductors – Solid aluminum rods, laid parallel, consisting of 1 to 19 (12.7 mm
diameter rods)
o Minimum Conductors Size – shall be 125 mm2 with an ampacity of 119
amperes.
o Maximum Conductor Size – shall be 2375 mm2 with an ampacity of 519
amperes.
• Insulation – shall be dry kraft paper tapes and a pressurized sulfur hexafluoride
(SF6)
o Nominal Gas Pressure – shall be 138 kPa gauge.
• Paper Size Thickness – 125 mm to 500 mm, thickness is 1.02 mm, 600 mm to
2375 mm, thickness is 1.52 mm.
• Conduit – shall be a medium density polyethylene with natural gas rated in
metric designator 53, 78, or 103.
Power and Control Tray Cable – A factory assembly of two or more insulated conductors,
with or without associated bare or covered grounding conductors, under a nonmetallic jacket.
• Bending Radius
o Type TC with metal shielding - the minimum bending radius shall have
not less than 12 times the cable overall diameter
o Type TC without metal shielding - the minimum bending radius shall be:
§ 4 times the overall diameter – for cable 25 mm or less in
diameter.
§ 5 times the overall diameter – for cable larger than 25 mm but not
more than 50 mm in diameter.
§ 6 times the overall diameter – larger than 50 mm in diameter.
• Construction – shall not be permitted either over or under the nonmetallic
jacket.
• Conductors
o Insulated conductors – shall be in sizes 0.75 mm2 (1.0 mm dia.) to 500
mm2 copper, nickel, or nickel-coated copper, and 3.5 mm2 (2.0mm dia.)
through 500 mm2 aluminum or copper-clad aluminum.
o Fire Alarm System, Thermocouple, and Class 1 Circuit Conductors.
• Jacket – Outer jacket shall be a flame retardant, non metallic material.
• Marking – shall be no voltage marking on a Type TC cable employing
thermocouple extension.
Rigid Metal Conduit – A steel threadable raceway of circular cross section designed
for the physical protection and routing of conductors and cables and for use as an
equipment grounding conductor when installed with its integral or associated coupling
and appropriate fittings.
• Dissimilar Metals
o Galvanized Steel – Aluminum fittings and enclosure shall be permitted.
o Stainless Steel – Only used with stainless steel fittings and approved
accessories, outlet boxes, and enclosures.
• Size
o Minimum – metric designator 16 (trade size 1/2), raceway size 15mm.
o Maximum – metric designator 155 (trade size 6), raceway size 150mm.
• Bends, Number in one run – There shall not be more than the equivalent of 4
quarter bends (360º total).
• Reaming and Threading – All the cut ends shall be reamed to remove rough
edges. Where conduit is threaded in the field, a standard cutting die with a taper
of 1 in 16 (3/4 in. taper per foot).
• Securing and Supporting
o Securely Fastened
§ within 900 mm of each outlet box, junction box, device box, cabinet,
conduit body, and other conduit termination.
§ shall be permitted to be increased to a distance of 1500 mm.
o Supports
§ Conduits – shall be supported at intervals not exceeding 3000 mm.
§ Support for RMC
• Trimming – All the cut ends shall be trimmed or otherwise finished to remove rough
edges.
• Bushings – to protect the wire from abrasion.
• Joints – all joints between length of conduit, and between conduit and couplings,
fittings, and boxes shall be made by an approved method.
• Construction
o General – NUCC is an assembly that is provided in continuous length shipped in
a coil, reel, or carton.
o Nonmetallic Underground Conduit - is resistant to moisture and corrosive
agents and capable of being supplied on reels without damage or distortion and
shall be of sufficient strength to withstand abuse.
• Markings – shall be clearly and durably marked at least every 3000 mm.
• Trimming – All the cut ends shall be trimmed or otherwise finished to remove
rough edges.
• Bushings – to protect the wire from abrasion.
• Expansion Fittings – where the length change is expected to be 6 mm (¼ in).
• Joints – all joints between length of conduit, and between conduit and couplings,
fittings, and boxes shall be made by an approved method.
• Construction – RTRC and fittings composed of suitable nonmetallic material
that is resistant to moisture and chemical atmosphere.
o For Above Ground – shall be flame retardant, resistant to impact and
crushing, resistant to distortion form heat
o For Underground – shall be resistant to moisture, corrosive agents and
withstand abuse.
• Markings – shall be clearly and durably marked at least every 3000 mm as
required in the first sentence.
Uses Permitted Uses Not Permitted
Concealed in walls, floors and ceiling In hazardous (classified) location
Corrosive Influences Class 1, Division 2
Cinders (Cinder Fill) Support of luminaires
Wet location Where subject to physical damage
Dry and Damp location
Exposed Where subject to ambient temperatures in
(RTRC, Type XW is identified for areas of excess of 50ºC unless listed otherwise
physical damage)
Underground
Support of Conduit Bodies Theaters and similar location
Insulation Temperature Limitation
LIQUIDTIGHT FLEXIBLE NONMETALLIC CONDUIT: TYPE LFNC
Flexible Metal Tubing – A metal raceway that is circular in cross section, flexible
metallic tubing (FMT) and associated fittings.
• Size
o Minimum – metric designator 16 (trade size 1/2), raceway size 15 mm.
o Maximum – metric designator 21 (trade size ¾), raceway size 20 mm.
• Bends
o Minimum Radii for Flexing Use