Project Requirements
Emissions : No Preference
Step01 Motor Load 1 1 312.5 343.41 844.49 3016.05 None None 35.0 10.0 0.0
Step Summary 313.0 343.0 844.0 3016.0 None None 35.0 10.0 0.0
Step02 Motor Load 2 1 312.5 411.18 371.58 1327.06 None None 35.0 10.0 0.0
Step Summary 313.0 411.0 372.0 1327.0 None None 35.0 10.0 0.0
Project
Running Max Starting Cumulative Step Cumulative Peak
VTHD%
Project Summary
kW kVA kW kVA kW kVA kW kVA Limit
Emissions : No Preference
Running kVA : 754.6 Max. Step kVA : 3016.1 In Step 1 Cumulative Step kVA : 3016.1
Running NLL kVA : None Peak kVA : None Cumulative Peak kVA : None
Alternator kW : 625.0
Step1
Running kVA : 343.0 Starting kVA : 3016.0 Cumulative Step kVA : 3016.0
Alternator kW : 312.5
Category : Motor
Running Amps : 60.15 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Running kVA : 411.0 Starting kVA : 1327.0 Cumulative Step kVA : 1670.0
Alternator kW : 312.5
Category : Motor
Running Amps : 72.02 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
1 35 23 100043.7 10 8 100043.7
2 35 11 106220.0 10 4 106220.0
Note: Please refer to the model Spec. sheet for bandwidths used to report recovery times. For products manufactured in the United
Kingdom it may be assumed that recovery times are based on ISO8528-5 G2 class bandwidths. Voltage and frequency recovery times
are estimates. Typically, allow five to ten seconds between application of load steps when designing your system.
**Please note that in some cases the voltage and frequency recovery time estimates are not shown in list. This is a result of "dummy"
data points temporarily being used to fill data gaps in the GenSize database. Please disregard these blank results.
Value
0 1 2 3 4 5 6 7 8 9 10
Step #