Вы находитесь на странице: 1из 10

Midos Type MVTU 11, 12, 13, 18

Definite Time Delayed


Voltage Relays

Features
l Compact size
l High resolution and precise
voltage/time settings
l Wide voltage setting range
Low ac burden
l Drop-off/pick-up ratio close to
unity
l High continuous withstand rating
l Non-volatile trip indication

Figure 1: MVTU 11 withdrawn from case.

which is included primarily for the


Application earth fault protection of alternator
stator windings where the neutral is
The MVTU range of relays provides
earthed through a voltage
definite time voltage protection with a
transformer or distribution
choice of three versions.
transformer, as shown in Figure 4.
The MVTU 11 and 12 provide definite
The relay is designed such that its
time undervoltage and overvoltage
response to third harmonic
protection respectively and can be
frequencies is suppressed, thus
employed for the protection of plant
making it inoperative to the third
and feeder systems. An application of
harmonic load imbalance which
the MVTU 11 includes the protection
normally flows in the generator
of induction motors against the
neutral. The applications of the relay
restoration of supply following the
also include protection against
loss or severe reduction in that supply.
unbalance conditions in capacitor
The MVTU 12 can be used for the banks and the detection of earth
protection of synchronous motors and faults in impedance earthed, solidly
motors driving high inertia loads.The earthed or un-earthed systems as
relay has been designed to operate depicted in Figure 5.
over a wide frequency range. It can
The MVTU 18 is a definite time
be used for the protection of hydro-
delayed neutral displacement relay
generators against overspeed.
virtually identical to type MVTU 13
The MVTU 13 is a definite time with a second time delay starting
delayed neutral displacement relay, after the first has elapsed.

2
Description remain in that state until the input to the type MVTU 12, with the
voltage rises above the setting following differences:
The MVTU range of relays uses solid voltage, causing the relay to reset. The input circuit has an additional
state design techniques. The required
low-pass filter fitted to suppress third
setting voltage is selected by means of
MVTU 12 - Definite time delayed harmonic components with a third
dual-in-line switches and the
overvoltage (Refer to Figure 3) harmonic rejection ratio of better
operating time by means of
When the ac input voltage rises above than 20:1.
thumbwheel switches, both mounted
on the relay frontplate. The output the selected setting voltage the output The voltage setting range is lower on
element is an attracted armature relay will energise after the selected the MVTU 13. See Technical Data.
relay, the contacts of which are time duration has elapsed. The ac
capable of circuit breaker tripping. input voltage must remain above the MVTU 18 - Definite time delayed
setting voltage throughout the time- neutral displacement
MVTU 11 - Definite time delayed out period otherwise the relay will (Refer to Figures 6 and 7)
undervoltage (Refer to Figure 2) reset. Once energised, the output will The operation of this relay is identical
remain in that state until the input to the type MVTU 13 with the
When the ac input voltage falls below
voltage falls below the setting voltage, following differences:
the selected setting voltage, the output
causing the relay to reset.
relay will energise after the selected After the first time delay t1
time duration has elapsed. The ac has elapsed, the output element RL1
input voltage must remain below the MVTU 13 - Definite time delayed is energised and the second time
setting voltage throughout the time- neutral displacement delay t2 starts. RL2 is then operated
out period otherwise the relay will (Refer to Figures 4 and 5) after the second time delay t2 has
reset. Once energised, the output will The operation of this relay is identical elapsed.

A A A
B B
C C C B
Phase rotation
B C
(See note 3)
b c
Rext (2) 27
(See note 6) Output
28 >Vs t circuits
RL1
2

Case earth 5
RL1-1 1
1 2 Rext (1) 13 9 OP
+ Power 3
3 4 supply Reset Output
(See note 4) 14 RL2
6 – circuits 1
5 9 6 contacts
18 secs RL1-2 2

Case earth connection 4


13 14
(See note 2)
18
Note: 1
21 22 (a) CT shorting links make 6 Rext (2) is required for AC voltage inputs
before (b) & (c) disconnect. greater than 110 i.e. when used on low voltage
(b) Short terminals break before (c). (220-415) systems where no VT is available.
(c) Long terminal.
27 28 2 Earthing connections as shown are typical only.
3 VT connections are typical only.
4 Rext(1) is required only for DC supplies greater than 30V.
Module terminal block 5 Contacts RL1-1 & RL1-2 are shown in the de-energised state.
viewed from rear
(with integral case earth strap)

Figure 2: Application diagram: definite time delayed undervoltage relay - Type MVTU 11.

3
A
A A
B B
C C C B
Phase rotation
B C
(See note 3)
b c
Rext (2) 27
(See note 5) Output
28 V
> s t circuits
RL1
2

Case earth 5
RL1-1 1
1 2 Rext (1) 13 9 OP
3 4 + Power 3
(See note 4) 14 supply Reset RL2 Output
5 6 – circuits 1
9 6 contacts
18 secs RL1-2 2
4
13 14 Case earth connection
(See note 2)
18

21 22 Note: 1
(a) CT shorting links make 6 Rext (2) is required for AC voltage
before (b) & (c) disconnect. inputs greater than 110 i.e. when used
(b) Short terminals break before (c). on low voltage (220-415V) systems
Long terminal. where no VT is available.
(c)
27 28 2 Earthing connections as shown are typical only.
3 VT connections are typical only.
Module terminal block 4 Rext(1) is required only for DC supplies greater than 30V.
viewed from rear
(with integral case earth strap)

Figure 3: Application diagram: definite time delayed over voltage relay - Type MVTU 12.

Distribution Generator
transformer A A
E N B
C C B
e n Phase rotation
(See note 3)

27
Output
28 >Vs t circuits
RL1
2 RL1-1 5
Case earth 1
Rext (1) 3
1 2
+
13 Power 9 Output
3 4 (See note 4) 14 supply OP RL1-2 6 contacts
6 – circuits
5 2
18 Reset RL2
9 1 4
secs
13 14 Case earth connection
(See note 2)
18
Note: 1
(a) CT shorting links make
21 22 before (b) & (c) disconnect.
(b) Short terminals break before (c).
(c) Long terminal.
2 Earthing connections as shown are typical only.
27 28 3 VT connections are typical only.
4 Rext(1) is required only for DC supplies greater than 30V.
Module terminal block
viewed from rear
(with integral case earth strap)

Figure 4: Application diagram: definite time delayed neutral displacement voltage relay - Type MVTU 13.

4
A A A
B B
C C C B
A B C
Phase rotation
(See note 3)

da dn 27
Output RL1
28 >Vs
t1 circuits 2 RL1-1 5
Case earth 1
3
1 2 13 9 Output
+ Power
3 4 (See note 4) 14 supply OP RL1-2 6 contacts
5 6 —
circuits 2
18 Reset RL2
9 1 4
secs
13 14 Case earth connection

18 (See note 2)
Note: 1
(a) CT shorting links make
before (b) & (c) disconnect.
(b) Short terminals break before (c).
(c) Long terminal.
27 28
2 Earthing connections as shown are typical only.
3 VT connections are typical only.
Module terminal block
viewed from rear
(with integral case earth strap)

Figure 5: Application diagram: definite time delayed neutral displacement voltage relay - Type MVTU 13.

A A A
B B
C C C B
A B C RL1-1 5
Phase rotation
(See note 3) 1
t1
N 3
Output
t1 RL1-2 6 contacts
Output RL1 t2
2 2
circuits
4
da dn 27
t2 RL2
28 >Vs
t1 t2 Output 2 RL2-1 11
circuits
Case earth 7
1 2 9
+
13
Power 9 9 Output
3 4 RL2-2 12
Vx 14 supply contacts
5 6 — circuits
18 8
7 8
9 10
9 9 10
secs secs
11 12
13 14 Case earth connection
(See note 2)
18
Note: 1
(a) CT shorting links make
before (b) & (c) disconnect.
(b) Short terminals break before (c).
(c) Long terminal.
27 28
2 Earthing connections as shown are typical only.
3 VT connections are typical only.
Module terminal block
viewed from rear
(with integral case earth strap)

Figure 6: Application diagram: static modular definite time delayed neutral displacement voltage relay - Type MVTU 18.

5
Distribution Generator A
transformer A
B N B
C B RL1-1 5
e C Phase rotation
n 1
t1
(See note 3)
3
Output
t1 RL1-2 6 contacts
Output RL1 t2
2 2
contacts
4
27
t2
t t Output RL2
RL2-1 11
1 2
>Vs 2
28 contacts
Case earth 9

1 2 3
+
13
Power 9 9 Output
3 4
Vx – 14 supply RL2-2 12 contacts
5 6 circuits
18 8
7 8
9 10
9 9 10
secs secs
11 12
13 14
Case earth connection
(See note 2)
18

Note: 1
(a) CT shorting links make
before (b) & (c) disconnect.
(b) Short terminals break before (c).
27 28 (c) Long terminal.
2 Earthing connections as shown are typical only.
3 VT connections are typical only.
Module terminal blocks
viewed from rear
(with integral case earth strap)

Figure 7: Application diagram: static modular definite time delayed neutral displacement voltage relay - Type MVTU 18.

Technical Data
Ratings
AC Voltage ratings
Relay type Rated Rated Operating Maximum
voltage frequency frequency continuous
(V) (Hz) range (Hz) withstand
voltage (V)
MVTU 11 57/70 50/60 30-70 144
(Undervoltage) 100/120 50/60 30-70 252
220/250 50/60 30-70 863
380/440 50/60 30-70 863
MVTU 12 57/70 50/60 25-180 144
(Overvoltage) 100/120 50/60 25-180 252
220/250 50/60 25-180 863
380/440 50/60 25-180 863
MVTU 13, 18 57/120 50 47-52 252
(Neutral
displacement) 57/120 60 57-62 252
DC Auxiliary voltage ratings Auxiliary Operative range
voltage (Vx)
30/34 24-37.5
48/54 37-66
110/125 87-150
220/250* 175-300
*A 220/250V MVTU 18 is not available at present

6
Burdens
AC 57/70 (MVTU 11,12)
100/120 (MVTU 11,12)
57/120 (MVTU 13)
} <1.5VA at rated voltage
on any setting

380/440 (MVTU 11,12)


220/250 (MVTU 11,12) } <3VA at rated voltage
on any setting
DC (Typical values) Auxiliary Quiescent Operated
MVTU 11, 12, 13 voltage (Vx) condition (W) condition (W)
30 <1 <3
48 <2.5 <4.5
110 <8 <10
220 <17 <21
MVTU 18 only Auxiliary Quiescent Trip indicators t1 &
voltage (Vx) condition (W) t2 and both output
relays operated
(W)
30 <1.5 <7.5
48 <2 <7
110 <4.5 <10
Setting ranges
Voltage setting ranges
Relay type AC Rated Setting
voltage (V) range (Vs) Increments (V)
MVTU 11 57/70 32-63 1.0
100/120 62-108.5 1.5
220/250 135-228 3.0
380/440 210-396 6.0
MVTU 12 57/70 60-106.5 1.5
100/120 105-182.5 2.5
220/250 230-385 5.0
380/440 400-710 10.0
MVTU 13 57/120 5-36 1.0
(for 50 & 60 Hz versions)
Time delay setting ranges (tsec) Time delay range Increment (s)
Relay type 0.1 - 9.9 0.1
MVTU 11, 12, 13 First time delay
MVTU 18 0.1 - 9.9 0.1
Second time delay
0.1 - 9.9 0.1
Drop-off/pick-up ratio MVTU 11 <105%
MVTU 12,13,18
>95%
Resetting and disengaging times MVTU 11 <25ms
MVTU 12 <65ms
MVTU 13 <130ms
MVTU 18 <130ms

7
Accuracy – reference conditions
AC Setting voltage (Vs) 32V for MVTU 11 32 - 63V version
62V for MVTU 11 62 - 108.5V version
135V for MVTU 11 135 - 228V version
210V for MVTU 11 210 - 396V version
60V for MVTU 12 60 - 106.5V version
105V for MVTU 12 105 - 182.5V
version
230V for MVTU 12 230 - 385V version
400V for MVTU 12 400 - 710V version
5V for MVTU 13 5 - 36V versions
and MVTU 18
DC Auxiliary supply (Vx) Rated reference range
(30/34, 48/54, 110/125 or 220/250V dc)
Frequency 50Hz (60Hz for 60Hz version of MVTU13)
Temperature 208C

Accuracy – at reference conditions


Operating voltage Within ± 1% of setting voltage
Operating time Within ± 2% of the time setting or 50ms,
whichever is the greater
Repeatability of operating times Better than ± 1% or 10ms, whichever is the
greater

Accuracy – influencing quantities


Variation of operating voltage over full
setting range: Better than ± 3% of setting voltage
Variation of operating voltage over full
operating frequency range:
MVTU 11 30 - 70Hz ± 3% of the setting voltage
MVTU 12 45 - 100Hz ± 1% of the setting voltage
25 - 180Hz ± 3% of the setting voltage
MVTU 13 and 47 - 52Hz (50Hz version) ± 1% of the setting voltage
MVTU 18 57 - 62Hz (60Hz version) ± 1% of the setting voltage
Variation of operating time over the 3% of the time setting or 50ms
full dc auxiliary voltage range (whichever is the greater)
Variation of operating voltage over
full operating temperature range
(-258C to + 558C) ± 2% change in the setting voltage
Variation of operating time over the ± 2% of the time setting or 50ms
full operating temperature range (whichever is the greater)

Contacts
MVTU 11, 12, 13 2 changeover self reset
MVTU 18 t1 2 changeover self reset
MVTU 18 t2 2 changeover self reset
Contact ratings
Current Make and carry Make and carry Break
continuously for 0.2 seconds
AC 1250VA with 7500VA with 1250V with
maxima of 5A maxima of 30A maxima of 5A
and 300V and 300V and 300V
DC 1250W with 7500W with 50W (resistive)
maxima of 5A maxima of 30A 25W (inductive)
and 300V and 300V with L/R = 40ms
with maxima of
5A and 300V
Durabiliy
Loaded contact 10,000 operations minimum
8 Unloaded contact 100,000 operations minimum
Operation indicators Non-volatile, hand-reset led trip
indicators are fitted to all relays.

Auxiliary equipment
DC external series resistors MVTU 11, 12, 13 relays with auxiliary
supply ratings of 48/54V, 110/125V
or 220/250V dc are supplied with an
external resistor assembly.
This resistor is connected in series
with the positive auxiliary supply
(terminal 13), as shown in Figures 2,
3, 4 and 5.
AC external series resistors 220/250V & 380/440V ac versions of
the MVTU 11 and 12 require external
resistors connected in series with
the ac input, terminals 27 and 28,
mounted on an external resistor
assembly (Refer to Figure 3).
Relays requiring both external ac and
dc series resistors are supplied with a
common assembly.

High Voltage Withstand


Dielectric withstand
IEC 255-5: 1977 2kV rms for 1 minute between all
terminals and case earth.
2kV rms for 1 minute between
terminals of independent circuits
including contact circuits, with
terminals on each independent circuit
connected together.
1kV rms for 1 minute across open
contacts of output relays.
High voltage impulse
IEC 255-5: 1977 Three positive and three negative
impulses of 5kV peak, 1.2/50 µs,
0.5J between all terminals and all
terminals and case earth.
Insulation resistance
IEC 255-5: 1977 >100MΩ when measured at 500V dc

Electrical Environment
DC supply interruption
IEC255-11: 1979 The unit will withstand a 10ms
interruption in the auxiliary supply,
under normal operating conditions,
without de-energising.
AC ripple on DC supply
IEC 255-11: 1979 The unit will withstand 12% AC ripple
on the DC supply.
High frequency disturbance
IEC 255-22-1: 1988 Class III 2.5kV peak between independent
circuits and case.
1.0kV peak across terminals of the
same circuit.

9
Electrostatic Discharge
IEC 255-22-2: 1989 Class II 4.0kV discharge in air with cover in
place
IEC 801-2: 1991 Level 2 4.0kV point contact discharge with
cover removed.
Fast Transient disturbance
IEC 255-22-4: 1992 Class IV 4.0kV, 2.5kHz applied directly to
auxiliary supply
IEC 801-4: 1988 Level 4 4.0kV, 2.5kHz applied directly to
all inputs
EMC Compliance
89/336/EEC Compliance with the European
Commission Directive on EMC is
claimed via the Technical
Construction File route.
EN 50081-2: 1994 Generic Standards were used to
EN 50082-2: 1995 establish conformity.

Atmospheric environment
Temperature
IEC 255-6: 1988 Storage and transit -25°C to +70°C
Operating -25°C to +55°C
IEC 68-2-1: 1990 Cold
IEC 68-2-2: 1974 Dry Heat
Humidity
IEC 68-2-3: 1969 56 days at 93% RH and 40°C
Enclosure Protection
IEC 529: 1989 IP50 (dust protected)

Mechanical environment
Vibration
IEC 255-21-1: 1988 Response Class 1

10
Cases
26
Types MVTU 11 and MVTU 12 relays 4 holes 4.4
71 23.5
are housed in size 3 cases, as shown
in Figure 8.
Type MVTU 13 and MVTU 18 relays
are housed in size 4 cases, as shown 168 159
in Figure 9.

Information Required Push button


projection 10 max. 73
with Order
Panel cut-out:
Relay type: Flush mounting fixing details
MVTU 11 undervoltage
MVTU 12 overvoltage 32 212 25 min.
MVTU 13 neutral displacement
MVTU 18 neutral displacement
Rated voltage and frequency
177 157 max.
DC auxiliary voltage

Reset
Additional Information
77 Flush mounting
Associated Publications
MIDOS System R6001 All dimensions in mm

MVTI Instantaneous overvoltage


Figure 8: Case outline size 3.
and undervoltage relay
R6033
MVTD Inverse time delayed voltage
relay R6051
MVTT Digital time delayed relay 52
R6012 4 holes 4.4
97 23.5

168 159

Push button
projection 10 max. 99
Panel cut-out:
Flush mounting fixing details

32 212 25 min.

177 157 max.

Reset

77 Flush mounting 11
All dimensions in mm

Figure 9: Case outline size 4.

11

Вам также может понравиться